![Badger Meter ModMAG M Series Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/badger-meter/modmag-m-series/modmag-m-series_user-manual_3659202019.webp)
External Disconnect
INSTALL AN EXTERNAL DISCONNECT SWITCH OR CIRCUIT BREAKER THAT MEETS LOCAL STANDARDS.
POSITION THE M2000 METER IN AN ACCESSIBLE LOCATION.
POSITION AND IDENTIFY THE DISCONNECT DEVICE SO AS TO PROVIDE SAFE AND EASY OPERATION.
LABEL THE DISCONNECT DEVICE AS BEING FOR THE MAG METER.
AC Power Wiring
For the AC power connections, use a three-wire sheathed connection cable suitable for the rating of this device . For signal
output use 18…22 gauge (0 .25…0 .75 mm
2
) shielded wire . Overall cable diameter between 0 .20…0 .39 inch (5…10 mm) .
TO PREVENT ACCIDENTS, CONNECT MAIN POWER ONLY AFTER ALL OTHER WIRING HAS BEEN COMPLETED.
The transmitter is a microprocessor device . It is important that the power supply be as “clean” as possible . Avoid using
power lines that feed heavy loads: pumps, motors, etc . If dedicated lines are not available, a filtering or isolation system may
be required .
Power wiring is the same for meter mount and remote mount transmitters .
Auxiliary Power
DO NOT CONNECT METER UNDER IMPRESSED MAINS VOLTAGE.
TAKE NATIONAL APPLICABLE RULES INTO ACCOUNT.
OBSERVE TYPE PLATE (MAINS VOLTAGE AND FREQUENCY).
1 . Slightly loosen both of the left cover screws and loosen the two right cover screws completely . Open cover to the left side .
2 . Push auxiliary power cable through the upper cable inlet .
3 . Connection as shown in
4 . Close connection cover firmly .
Remote Mount Installation
Follow these instructions to install the M2000 remote transmitter .
Mount Bracket to Transmitter
1 . Align bracket-mounting holes with transmitter mounting holes .
2 . Attach bracket to transmitter with supplied screws . Torque screws to 80 inch pounds .
Wiring Configuration
Wiring between the sensor and the M2000 transmitter comes complete from the factory . If your installation requires the use
of conduit, we recommend that you follow these steps when wiring the sensor to the transmitter .
1 . Remove the junction box lid . Carefully remove the wires connected to the terminal blocks that run to the M2000
transmitter . See
for a reference of wire color to terminal connection .
2 . Run cable through the conduit from the transmitter location while retaining the wiring of the cable to the transmitter,
as supplied .
3 . Complete conduit assembly on both ends and rewire the cable into the junction box as it was previously wired .
Wiring
Page 19
March 2022
MAG-UM-01272-EN-21