background image

WIRING

At installation, be sure to comply with the following require-
ments:

IMPORTANT!

• Disconnect power to the unit before attempting any

connection or service to the unit

Do not bundle or route signal lines with power lines

Keep all lines as short as possible

Use twisted pair shielded wire for all output wiring

Observe all applicable local electrical codes

For the AC power connections use three wire sheathed cable with
overall cable diameter of 0.2" to 0.45" (5mm to 12mm). For signal
output use 18 to 22 gauge (0.25 mm

2

 to 0.75mm

2

) shielded wire.

Overall cable diameter between 0.12" to 0.35" (3mm to 9mm).

WIRING FOR REMOTE PRIMO

®

 CONFIGURATION

Wiring between the detector and the Primo amplifier comes complete
from the factory. If your installation requires the use of conduit, the
following are recommended steps for wiring of the detector to the
amplifier.

1. Remove the junction box lid. Carefully remove the wires connected

to the terminal blocks that run to the Primo amplifier. Note which
wire goes into which terminal. The chart below may be of assis-
tance for reference of wire color and terminal connection.

2. Run cable through conduit from Primo amplifier location, retaining

the wiring of the cable to the amplifier as supplied.

3. Complete conduit assembly on both ends and rewire cable into

junction box as wired when received.  See wiring diagram below.

Connection No.

Description

Wire color

11

Coil

Green

12

Coil

Yellow

13

Main Shield

Yellow/green

45

Electrode

White

44*

Electrode Shield

Black

46

Electrode

Brown

40

Empty Pipe

Pink

44*

Empty Pipe Shield

Black

*Connections with the No. 44 are lying on the same potential

Remote style Primo Amplifier models can be ordered with longer
cable than our standard stock lengths of the standard cable; 15, 30,
50 and 100 feet. The following chart shows the cable style options
and the maximum flow medium temperature that can exist in the
application environment at a given length of that cable.

7

Wiring for Remote Primo Configuration

44
40
44
46
44
45

13
12
11

  

  

shield (black)

pink

brown

shield (black)
white

yellow/green

yellow
green

green

yellow

yellow/green

white

shield (black)

brown

pink

shield (black)

45

44

46

44

40

44

13  12 11 

Содержание Magnetoflow Mag Meter

Страница 1: ...BadgerMeter Inc Installation Operation Manual IOM 103 02 53400 103 3 09 Magnetoflow Mag Meter Wafer Meter with Model Primo 3 1...

Страница 2: ...ing any instruc tions that may be marked on the exterior Remove all cushioning material surrounding the meter B Carefully lift the meter from the container C Retain the shipping box and all packing ma...

Страница 3: ...estriction or turbulence Do not use graphite or any electrically conductive sealing compound to hold the gaskets in place during installation This could affect the reading accuracy of the measuring si...

Страница 4: ...e following guidelines Avoid installing the detector in the highest point of the pipe line Do not install the detector in vertical downward flow sections of the pipe ON OFF valves should ALWAYS be loc...

Страница 5: ...Box Enclosure Protection For Remote Converter Option Powder coated die cast aluminum Nema 4 Cable Entries 1 2 NPT Cord Grip Meter with Primo converter Meter with junction box for remote Primo converte...

Страница 6: ...ollector Max 5Khz Digital Outputs Voltage sourcing transistor 24VDC 100mA max 3 AC electro mechanical relays 48VAC 0 5 amp max Outputs All ouputs are short circuit safe Noise Dampening Programmable fr...

Страница 7: ...ich wire goes into which terminal The chart below may be of assis tance for reference of wire color and terminal connection 2 Run cable through conduit from Primo amplifier location retaining the wiri...

Страница 8: ...ecommended that the internal fuse protection be maintained Use a 2 amp slow blow fuse How to connect the amplifier to remote digital indicators totalizers that do not require external power supply Thi...

Страница 9: ...error messages that may occur during operation of the meter The main display screen will be in one of the following modes See Flow Direction on page 11 for additional detail Uni Directional Mode Bi D...

Страница 10: ...d analog signal outputs Adjust the desired new full scale setting based on your meter size and your applications requirements making sure that it falls within the sug gested flow range of the meter Wh...

Страница 11: ...dy hit ENTER This new screen is the hysteresis value entered This value is set at the factory at 1000 mV to allow some variation in empty pipe detection to eliminate the potential for false empty pipe...

Страница 12: ...Power Up Counter This can assist in checking possible power failures Line up the with change and hit the key This will bring up the 1st error Continue hitting the key to toggle through the last 8 err...

Страница 13: ...g output ranges 4 to 20 mA 0 to 20 mA 2 to 10 mA 0 to 10 mA Press the key at the change line the following screen will appear Press or keys until you find the type of analog output that you desire amo...

Страница 14: ...en will appear Use the and keys to change the value to the desired pulse rate This value may be set from 001 to 10 000 pulses unit of measure Maximum frequency of 10kHz can not be exceeded Based on ma...

Страница 15: ...nimum flow percentage and press ENTER the following screen will appear Use the and arrows to change the maximum flow percentage and press ENTER NOTE On the signal output the relays will remain ener gi...

Страница 16: ...t be reduced by a calibration correction When finished with detector factor parameter hit ENTER and then hit key to go to the next parameter METER PIPE SIZE Place the arrow next to change and press th...

Страница 17: ...w on the nameplate reprogram to biodirectional mode Coil or electrode cables exchanged Check cable connections for cross wiring Inaccurate measuring Parameter wrong Check the parameters transmitter de...

Страница 18: ...r Contact Technical Support Water in detector Contact Technical Support Err Output Micro processor output control defective Contact Technical Support Err unknown Program error Contact Technical Suppor...

Страница 19: ...ing 1 Pull the electrode coil and display wiring plugs Loosen the screws S1 to S5 and remove the existing board assembly 2 Put in new board assembly and reassemble screws to S1 and S5 Reinstall the 3...

Страница 20: ...ions without notice except to the extent an outstanding bid obligation exists BadgerMeter Inc P O Box 245036 Milwaukee WI 53224 9536 Telephone 414 355 0400 800 456 5023 Fax 414 355 7499 866 613 9305 w...

Отзывы: