Relay Wiring Terminals

Using the   and   key select which flow direction mode you want
and press ENTER. Hit the   key to go to the next parameter.

FILTER DAMPENING

This feature is for dampening of all output signals and flow rate
display. This function has no effect on the totalizers.

The factory setting is 1. If you notice too much back and forth
oscillation of the flow rate indication, increase this value incremen-
tally until the display is more stable. Your choices are 1 though 6 or
"Inactive." To change the filter value, place the arrow next to "change"
and press the   key. The following screen will show:

Using the   and   keys select the desired filter value and then
press ENTER. Hit   key to go to last parameter of this submenu.

ERROR LIST (MESSAGES)

The error list in the program menu indicates the last 8 error types
that have occurred and the frequency of each. The sum of all
switching on processes can be read on the "Power Up -
Counter." This can assist in checking possible power failures.

Line up the > with "change" and hit the 

 

key. This will bring up

the 1st error. Continue hitting the   key to toggle through the last
8 errors that occured, with #1 being the most recent error and the
power-up indication screens.

Any error is indicated via the error relay as well as displayed on
line 4 of the LCD display. The relay is normally closed during
normal operation and is opened when an error occurs.

Error Relay

Now hit the   key again and you will be at the screen for clearing
all the error list information.

Hit Enter to clear and the following screen will appear with "Done"
indication.

An overview of the possible errors and causes can be found in
the Troubleshooting section.

Now hit enter twice and you will be back at the submenu screen.

PROGRAMMING OF OUTPUTS/TOTALS
PARAMETERS

The next submenu is outputs/totals.

From the main submenu screen, position the > next to the "outputs/
totals" submenu and press the 

 key.

The following screen will appear:

RESETTING OF TOTALIZERS

This parameter is used to reset either of the totalizers to zero.

12

Содержание Magnetoflow Mag Meter

Страница 1: ...BadgerMeter Inc Installation Operation Manual IOM 103 02 53400 103 3 09 Magnetoflow Mag Meter Wafer Meter with Model Primo 3 1...

Страница 2: ...ing any instruc tions that may be marked on the exterior Remove all cushioning material surrounding the meter B Carefully lift the meter from the container C Retain the shipping box and all packing ma...

Страница 3: ...estriction or turbulence Do not use graphite or any electrically conductive sealing compound to hold the gaskets in place during installation This could affect the reading accuracy of the measuring si...

Страница 4: ...e following guidelines Avoid installing the detector in the highest point of the pipe line Do not install the detector in vertical downward flow sections of the pipe ON OFF valves should ALWAYS be loc...

Страница 5: ...Box Enclosure Protection For Remote Converter Option Powder coated die cast aluminum Nema 4 Cable Entries 1 2 NPT Cord Grip Meter with Primo converter Meter with junction box for remote Primo converte...

Страница 6: ...ollector Max 5Khz Digital Outputs Voltage sourcing transistor 24VDC 100mA max 3 AC electro mechanical relays 48VAC 0 5 amp max Outputs All ouputs are short circuit safe Noise Dampening Programmable fr...

Страница 7: ...ich wire goes into which terminal The chart below may be of assis tance for reference of wire color and terminal connection 2 Run cable through conduit from Primo amplifier location retaining the wiri...

Страница 8: ...ecommended that the internal fuse protection be maintained Use a 2 amp slow blow fuse How to connect the amplifier to remote digital indicators totalizers that do not require external power supply Thi...

Страница 9: ...error messages that may occur during operation of the meter The main display screen will be in one of the following modes See Flow Direction on page 11 for additional detail Uni Directional Mode Bi D...

Страница 10: ...d analog signal outputs Adjust the desired new full scale setting based on your meter size and your applications requirements making sure that it falls within the sug gested flow range of the meter Wh...

Страница 11: ...dy hit ENTER This new screen is the hysteresis value entered This value is set at the factory at 1000 mV to allow some variation in empty pipe detection to eliminate the potential for false empty pipe...

Страница 12: ...Power Up Counter This can assist in checking possible power failures Line up the with change and hit the key This will bring up the 1st error Continue hitting the key to toggle through the last 8 err...

Страница 13: ...g output ranges 4 to 20 mA 0 to 20 mA 2 to 10 mA 0 to 10 mA Press the key at the change line the following screen will appear Press or keys until you find the type of analog output that you desire amo...

Страница 14: ...en will appear Use the and keys to change the value to the desired pulse rate This value may be set from 001 to 10 000 pulses unit of measure Maximum frequency of 10kHz can not be exceeded Based on ma...

Страница 15: ...nimum flow percentage and press ENTER the following screen will appear Use the and arrows to change the maximum flow percentage and press ENTER NOTE On the signal output the relays will remain ener gi...

Страница 16: ...t be reduced by a calibration correction When finished with detector factor parameter hit ENTER and then hit key to go to the next parameter METER PIPE SIZE Place the arrow next to change and press th...

Страница 17: ...w on the nameplate reprogram to biodirectional mode Coil or electrode cables exchanged Check cable connections for cross wiring Inaccurate measuring Parameter wrong Check the parameters transmitter de...

Страница 18: ...r Contact Technical Support Water in detector Contact Technical Support Err Output Micro processor output control defective Contact Technical Support Err unknown Program error Contact Technical Suppor...

Страница 19: ...ing 1 Pull the electrode coil and display wiring plugs Loosen the screws S1 to S5 and remove the existing board assembly 2 Put in new board assembly and reassemble screws to S1 and S5 Reinstall the 3...

Страница 20: ...ions without notice except to the extent an outstanding bid obligation exists BadgerMeter Inc P O Box 245036 Milwaukee WI 53224 9536 Telephone 414 355 0400 800 456 5023 Fax 414 355 7499 866 613 9305 w...

Отзывы: