Change factory settings
Page 40
LM_OGP2Adv_BA_99_0045
May 2019
9.3
Change scale factor
CHANGING THE SCALE FACTOR CHANGES THE ACCURACY OF THE METER, POTENTIALLY
CAUSING IT TO OVERFILL OR UNDER FILL. THIS HAS THE POTENTIAL TO CAUSE A MECHANICAL
BREAKDOWN.
Scale factor display
1.
Press the
RESET
button to advance through the scale factor
digits.
2.
Press the
TOTAL
button to change the selected number.
NOTE:
All digits can be scrolled between 0 and 9 except the first. It can
only be scrolled from 0 to 1 or from 1 to 0.
3.
Press the
RESET
button to advance to the next number in scale factor.
4.
Repeat steps 2 and 3 for all five digits in scale factor.
9.4
Save changes
To save changes and exit the programming mode:
1.
Push and hold at the same time the
TOTAL
and
AUTO
buttons.
2.
The display will flash 3 times and go blank.
3.
Press the
RESET
button and the display will turn back on.
9.5
Verify changes
1.
Verify unit of measure is correct.
2.
Push and hold the TOTAL button and AUTO button together, to verify that the scale factor is correct.
Scale factor digits