Opening the M1000 Cover
The M1000 amplifier's design lets you open the cover
without completely removing it .
Follow these steps:
1 . Completely remove the top two screws from the
amplifier using a blade/slotted screwdriver .
2 . Loosen both of the bottom screws so that the round
head of each screw clears the top face of the cover .
3 . Pull down the cover to the open position .
• For the 2 x M20 cable inlets, use only flexible electric
cables .
• Use separate cable inlets for auxiliary power, signal and
input/output cables .
Figure 18: Remove two screws
Figure 19: Open the cover
Auxiliary Power
TO PREVENT ACCIDENTS, CONNECT MAIN POWER ONLY AFTER ALL OTHER WIRING HAS BEEN COMPLETED.
ATTENTION
AFIN D'ÉVITER LES ACCIDENTS, BRANCHEZ L'ALIMENTATION PRINCIPALE SEULEMENT UNE FOIS TOUT LE CÂBLAGE
COMPLÉTÉ.
Take national applicable rules into account.
• Observe type plate (mains voltage and frequency)
• Equipment shall be provided with a external means for disconnecting it from each operating energy supply source . The
disconnecting means shall disconnect all current-carrying conductors .
1 . Open the cover (see
"Opening the M1000 Cover" on page 16
) .
2 . Push the auxiliary power cable through the upper cable inlet .
3 . Connect as shown in
Figure 20
.
4 . Close the cover and tighten the screws .
Power supply 92…275V AC (50/60 Hz)
Recommended cable size min . 0 .75 mm²
Power supply 9…36V DC (13VA)
Recommended cable size min . 0 .75 mm²
Figure 20: Auxiliary power connection
Power Connections
Page 16
January 2018
MAG-UM-00379-EN-04