[Heat]
target value: When the current temperature of the device is lower than this value, then the
heating is started. The target value set needs to be lower than the high temperature protection value
minus the deadband value, and needs to be higher than the low temperature protection value.
[Cool]
target value: When the current temperature of the device is higher than this value, and the
cooling is started. The target value set needs to be higher than the low temperature protection value
plus the deadband value, and needs to be lower than the high temperature protection value.
[Deadband]
value: The value set needs to be lower than (Cool target value minus heat target
value)/2 and the value needs to be greater than 0.
[Low Temp Protection]
value: The value set needs to be lower than the [Heat] target value of
cooling & humidification.
[High Temp Protection]
value : The value set needs to be higher than the [Cool] target value of
heating.
After the data are set, the Save button will light up. At this time, press the Save button to save the data,
after which a dialogue box will pop up prompting you to save the data; the data modified will not take
effect unless they are saved.
Different parameters need to be set in different light environments.
(7.2) Default parameters
(7.3) Day and night setting
On the left side of the interface, the working modes of the device are shown, which are Heat mode,
Cool, Heat & Cool mode.
(7.4) Working mode setting
25
Working Mode
Parameter Type
Default Parameter
Day Mode
Heating on value (℃)
12.0
Cooling on value (℃)
30.0
Deadband (℃)
2.0
Low humidity
protection value (℃)
10.0
High humidity
protection value (℃)
35.0
Night Mode
Heating on value (℃)
12.0
Cooling on value (℃)
30.0
Deadband (℃)
2.0
Low humidity
protection value (℃)
10.0
High humidity
protection value (℃)
35.0
Default working
Mode
Heat mode
OFF state
Cool mode
OFF state
Heat & cool mode
OFF state