5 Test Procedure
44
DHV0078 b2 EN
©
b2 electronic
GmbH
Running an automatic test – detailed steps
Steps
AR1-AR9
describe how to
run a test in the automatic mode.
Step
Procedure
(run automatic test)
Example
AR1:
Use Last Seq. or
Start New Test
To repeat the previous test sequence:
•
Select “Use Last Test Sequence” from “Main Menu”
•
Proceed to step AR5
Otherwise, select:
•
“Start a new Test”
AR2:
De-/activate
Reporting
To activate reporting:
•
Select “YES”, See 6 – Reporting
To conduct a test without generating a report:
•
Select “NO”
AR3:
(If Reporting
active: this step
follows report
setup completion)
To run an test sequence:
•
Select “Auto Seq”
AR4:
Select sequence
•
Select the appropriate test sequence
•
To continue, select “NEXT”
AR5:
Parameter
verification
•
Verify that the selected sequence defines the
correct test parameters
To run the auto test sequence:
•
Select “START” from the bottom of the screen
AR6:
HV activation
Once the activation screen appears,
•
Press the HV switch
within 10 seconds.
If the HV switch is not activated within the 10-second
window, the “Start Auto Test Seq.” screen will reappear.
USB - Main Menu – HVA120
Use Last Test Seq.?
3.0kV Maint. C. HYBR (T)
Start a New Test
Manual Mode
Reports & Setup
13.3.2009 10:23
Start a New Test
Do you want to
store a report?
Yes
No
MAIN
Start a New Test
Use an existing
Auto Test Sequence
or use Manual Mode?
Auto Seq.
Manual
MAIN PREV
Select Auto Test Seq.
3.0kV Maint. C. HYBR (T)
1.0kV Maint. C. XLPE (T)
BACK SELECT NEXT
Start Auto Test Seq.
1.0 kV Cable XPLE
Maintenance Test Sequence
Test Voltage: 1.0kVrms
Duration: 15 min
Waveform: Sine 0.1Hz
Trip out on
Reporting Active
MAIN BACK
START
ATTENTION
High Voltage!
Press I/O Button to
switch ON High Voltage
Содержание HVA120
Страница 2: ...1 Introduction 2 DHV0078 b2 EN b2 electronic GmbH...
Страница 11: ...2 Safety b2 electronic GmbH DHV0078 b2 EN 11...
Страница 22: ...4 Design and Construction 22 DHV0078 b2 EN b2 electronic GmbH Switches and controls Front panel HVA34...
Страница 33: ...5 Test Procedure b2 electronic GmbH DHV0078 b2 EN 33 Connection diagram vacuum bottle test...
Страница 47: ...5 Test Procedure b2 electronic GmbH DHV0078 b2 EN 47 5 5 Discharge Status...
Страница 62: ...11 Declaration of Conformity 62 DHV0078 b2 EN b2 electronic GmbH 11 Declaration of Conformity HVA34...
Страница 63: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 63 HVA30 5...
Страница 64: ...11 Declaration of Conformity 64 DHV0078 b2 EN b2 electronic GmbH HVA30 7 HVA40 5 HVA54 3...
Страница 65: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 65 HVA54 5...
Страница 66: ...11 Declaration of Conformity 66 DHV0078 b2 EN b2 electronic GmbH HVA60...
Страница 67: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 67 HVA68 2...
Страница 68: ...11 Declaration of Conformity 68 DHV0078 b2 EN b2 electronic GmbH HVA90 HVA94...
Страница 69: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 69 HVA120...