5 Test Procedure
©
b2 electronic
GmbH
DHV0078 b2 EN
35
5.2
Manual Test Mode
This HVA test mode facilitates rapid testing. If the default is the “Manual Mode
Screen,” a test with the same settings as the previous test can be started directly
after activating the system. Similarly, if the “Main Menu” is set as the 1
st
screen,
select “Manual Mode.” Otherwise, select “Start a New Test” to change test
parameters or to activate reporting.
Main Menu
Default Screen
Manual Mode
Default Screen
USB - Main Menu
Use Last Test Seq.?
3.0kV Maint. C. HYBR (T)
Start a New Test
Manual Mode
Reports & Setup
13.3.2009 10:23
Start a New Test
Manual Mode
USB - Main Menu
Use Last Test Seq.?
3.0kV Maint. C. HYBR (T)
Start a New Test
Manual Mode
Reports & Setup
13.3.2009 10:23
Start a New Test
Do you want to
store a report?
Yes
No
MAIN
Start a New Test
Do you want to
store a report?
Yes
No
MAIN
Report?
Setup Report
HVA guides user through series of questions (see section 6):
•
DUT type
•
Voltage rating
•
(Cable) insulation
•
Report title
Manual Test Sine 0.1Hz
Timer: 30 min
MAIN
SETUP
Trip out on Arc
START
0.0
HVA guides user through
series of questions:
•
Waveform
•
Frequency
•
Duration
Setup Test
Test Mode?
Use an existing
Auto Test Sequence
or use Manual Mode?
Auto Seq.
Manual
MAIN PREV
Start a New Test
Manual Test Sine 0.1Hz
Timer: 30 min
MAIN SETUP
Trip out on Arc
START
Manual Test Sine 0.1Hz
Timer: 30 min
MAIN SETUP
Trip out on Arc
START
Manual Test Sine 0.1Hz
Timer: 30 min
MAIN SETUP Trip
out on Arc
START
Modify arc management
mode
Modify test voltage
0.0
kV
rms
kV
rms
kV
rms
0.0
0.0
kV
rms
Manual Test Sine 0.1Hz
Timer: 30 m 0s, report active
DUT 1.0kV Cable XLPE
MAIN SETUP
Trip out on Arc
START
0.0
kV
rms
NOTE: If Reporting is active, screen displays additional info.
To test with identical parameters as last
manual test
(i.e. parameter as seen on screen.)
No reporting is possible!
Содержание HVA120
Страница 2: ...1 Introduction 2 DHV0078 b2 EN b2 electronic GmbH...
Страница 11: ...2 Safety b2 electronic GmbH DHV0078 b2 EN 11...
Страница 22: ...4 Design and Construction 22 DHV0078 b2 EN b2 electronic GmbH Switches and controls Front panel HVA34...
Страница 33: ...5 Test Procedure b2 electronic GmbH DHV0078 b2 EN 33 Connection diagram vacuum bottle test...
Страница 47: ...5 Test Procedure b2 electronic GmbH DHV0078 b2 EN 47 5 5 Discharge Status...
Страница 62: ...11 Declaration of Conformity 62 DHV0078 b2 EN b2 electronic GmbH 11 Declaration of Conformity HVA34...
Страница 63: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 63 HVA30 5...
Страница 64: ...11 Declaration of Conformity 64 DHV0078 b2 EN b2 electronic GmbH HVA30 7 HVA40 5 HVA54 3...
Страница 65: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 65 HVA54 5...
Страница 66: ...11 Declaration of Conformity 66 DHV0078 b2 EN b2 electronic GmbH HVA60...
Страница 67: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 67 HVA68 2...
Страница 68: ...11 Declaration of Conformity 68 DHV0078 b2 EN b2 electronic GmbH HVA90 HVA94...
Страница 69: ...11 Declaration of Conformity b2 electronic GmbH DHV0078 b2 EN 69 HVA120...