background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

21

FAULT FINDING

Red LED permanently illuminated
indicates one of the following faults.

High limit thermostat has operated or faulty electrical
connections
The high limit thermostat is fitted to the front top of the
copper heat exchanger and secured in position with 2
retaining clamps.
Check electrical connections on thermostat and PCB to
check thermostat has not failed using a multi meter
check continuity across terminals of thermostat.
To reset press red button in centre of thermostat.
Thermostat may have tripped due to one of the following:-
1. Faulty circulation pump
2. Isolation valve on system closed
3. Air trapped in system
4. Out of calibration limit thermostat
5. Temperature settings on PCB board incorrect
6. No water in system

Thermistor
The thermistor is fitted to the front top of the heat
exchanger and secured in position with a clamp, the
other end terminates with a white connector that plugs on
to the PCB
Check the connections on the board to make sure it is
correctly fitted; also inspect the thermistor for any broken wires.

Mains Inlet Wiring
If the mains supply to the boiler is wired incorrectly on
the inlet terminal block.

PCB Board Damage
Inspect the LED lights and the boiler temperature control
adjuster for any damage to connections to PCB 
controller.

Voltage Drop
If the voltage drops below 207 volts.

Red LED flashes indicates one of the
following faults.

Poor electrical connection
Check the electrical connections to the elements and the
PCB controller, a poor controller would show up a fault.

Element Failure
To check elements for failure, disconnect each individual
element and check continuity through the element if there
is continuity between the two terminals the element is ok.
Check each element individually replacing the electrical
connectors after testing.

Element Cables
If there is a break in the element cable, this would show
up as a fault. Check all element cables and connections.

PCB Running Temperature
The PCB control unit has a built in temperature control
sensor which protects the PCB from overheating, if the
board was to overheat the sensor would detect the high
temperature and shut off the power to the board until the
board temperature has returned to normal running 
temperature. The boiler will resume operation but the red
light will continue to flash to indicate a fault has occurred.
To reset the board the power must be turned off for 30
seconds then switched on again.

On the 9, 11 and 12 kW boilers a cooling fan is fitted to
the heatsink if this has failed, it would cause the PCB to
overheat. 
To differentiate between a temperature or element problem,
switch off the power supply to the boiler allow the boiler
to cool down then switch the power back on, if the LED
continues to flash then check elements and connections.

Green LED
If the green LED is illuminated but the boiler is not 
functioning, check that any external controls fitted are
calling for heat. If no external controls are fitted check
that link wire is in place on call terminal block (refer to
wiring diagram Fig 1)

Blown Fuse on board
If there is power to the boiler but no LED illuminated then
the fuse on the PCB may have blown. The fuse is located
above the PCB transformer (fuse type 20mm 630Ma anti
surge Bessman type S560)

The fuse may have blown due to one of the following:-

1.  When multiple boilers are fitted and a larger pump is 

used. If the pump is wired directly into the PCB the 
fuse may need upgrading. (see page 11)

2.  If the call terminal is used to supply power to ancillary

controls.

Element Jumper Connection
Fitted on 11 and 12 kw models only. If fitted to 6 and 9
kw models it will show up as a fault.

RCD UNIT TRIPS

Check that the RCD unit is correctly rated for boiler size.
If under size change.
Inspect mains terminal block wiring for short-circuiting.
Check electrical elements for earth continuity, if element
is found to be faulty fit new element.

                           

Содержание EB 897 01

Страница 1: ...er commissioning is carried out b It is a requirement of the boiler s guarantee and any extended warranty that an annual service is carried out by a qualified engineer Installation Engineer s Signatur...

Страница 2: ...nce may contain some of the items below When working on the appliance it is the Users Engineers responsibility to ensure that any necessary personal protective clothing or equipment is worn appropriat...

Страница 3: ...learance dimensions Power Supply and Wiring The power supply to the premises must meet the minimum requirements of the unit being installed with special attention paid to the supply current cable size...

Страница 4: ...ares List 22 23 Important General Information To keep your boiler running efficiently DO NOT OBSTRUCT OR COVER any ventilation air inlet on the appliance or the compartment where it is installed To ke...

Страница 5: ...N THIS APPLIANCE BY ANY THIRD PARTY WILL NOT BE ACCEPTED BY TRIANCO A step by step guide to reporting a fault with your appliance A qualified field SERVICE ENGINEER is available to attend a breakdown...

Страница 6: ...EN60335 1 1994 A16 2001 EN60335 2 35 1998 A1 2000 EN55014 1 2000 EN55014 2 1997 EN61000 3 2 2000 and EN61000 3 3 1995 THE PERSON S WHO INSTALLS THIS APPLIANCE SERVICES OR CARRIES OUT ANY REMEDIAL WOR...

Страница 7: ...wer on to the boiler AMBER Illuminated In run mode Flashing Temperature Satisfied RED Boiler Fault If the red LED light flashes this means a fault has occurred This would result in the boiler continui...

Страница 8: ...Check for blown fuse or thrown power breaker If replacement fuse or power breaker fail again call service engineer If the red LED is permanently illuminated contact your service engineer Flashing red...

Страница 9: ...l during such times When installed in a compartment with a hot water cylinder see Fig 1 we recommend that the boiler is fitted in position 1 if fitted in position 2 provision should be made at the fro...

Страница 10: ...p casing panel and cut off end to allow pipe to slide through see diagram IMPORTANT TOP CASING PANEL WITH GROMMET MUST BE RE FITTED BACK IN POSITION BEFORE MAKING TOP PIPE CONNECTION 9 When re fitting...

Страница 11: ...pe expansion vessel conforming to the current issue of BS4814 The expansion vessel must be connected to the systems at a point close to the inlet side of the circulating pump The expansion vessel volu...

Страница 12: ...er power demand the PCB circuit protection fuse may require up rating from the 630ma one supplied as standard Alternatively the pump could be wired using a relay See Wiring Instructions page 10 for fu...

Страница 13: ...led System 3 port valve Aztec Boiler Drain Valve CENTRAL HEATING DHW CYLINDER air vent Safety Valve Pressure Gauge Expansion Vessel Bypass valve Alternative pump position Auto Air Vent PUMP Service Va...

Страница 14: ...f 100A per phase and meet the requirements of IEC 60417 5855 The 12 kW boiler must be installed in premises having a NOTE RCD UNIT can be used as the isolating switch if mounted close enough to the bo...

Страница 15: ...HECKED LOOSE CONNECTIONS CAN CAUSE PROBLEMS WARNING THIS APPLIANCE MUST BE EARTHED 1 Any exposed pipe work must be earthed in accordance with IEE regulations 2 On completion of installation all electr...

Страница 16: ...ING SHOWING 1 ELEMENTS 2 KW MODEL IMPORTANT When fitting programmer always connect to boiler as shown in wiring diagram IMPORTANT REMOVE LINK WIRE A WHEN WIRING CALL SIGNAL INTO SL TERMINAL IMPORTANT...

Страница 17: ...Tel 0161 620 6677 13 INTERNAL WIRING SHOWING 3 ELEMENTS 6 9 KW MODEL IMPORTANT When fitting programmer always connect to boiler as shown in wiring diagram IMPORTANT REMOVE LINK WIRE A WHEN WIRING CAL...

Страница 18: ...0161 620 6677 14 INTERNAL WIRING SHOWING 4 ELEMENTS 11 12 KW MODEL IMPORTANT When fitting programmer always connect to boiler as shown in wiring diagram IMPORTANT REMOVE LINK WIRE A WHEN WIRING CALL...

Страница 19: ...By www heating spares co Tel 0161 620 6677 MODEL SUPPLY BOILER RATING CURRENT MCB RCD 2 Kw 8 5A 13A 6 Kw 25A 32A 9 Kw 39A 40A 11 Kw 45A 50A 12Kw 51A 63A 15 WIRING DIAGRAM FOR HEATING ONLY GREY SL FIG...

Страница 20: ...w heating spares co Tel 0161 620 6677 16 WIRING DIAGRAM FOR Y PLAN CONTROL SYSTEM MODEL SUPPLY RATING BOILER CURRENT MCB RCD 2 Kw 8 5A 13A 6 Kw 25A 32A 9 Kw 39A 40A 11 Kw 45A 50A 12 Kw 51A 63A ORANGE...

Страница 21: ...heating spares co Tel 0161 620 6677 17 WIRING DIAGRAM FOR S PLAN CONTROL SYSTEM FIG 21 GREY SL ORANGE FIG 21 MODEL SUPPLY RATING BOILER CURRENT RCD 2 Kw 8 5A 13A 6 Kw 25A 32A 9 Kw 39A 40A 11 Kw 45A 50...

Страница 22: ...element 6 With all elements disconnected again taking note of wiring arrangement carefully disconnect and remove the element cables from the PCB Important care MUST be taken when handling the PCB 7 Di...

Страница 23: ...on bottom of boiler then carefully remove top bracket 8 Boiler unit can now be carefully removed 9 Remove eight fixing screws on top flange and with draw element assembly 10 Remove bottom element posi...

Страница 24: ...d By www heating spares co Tel 0161 620 6677 20 WIRING ARRANGEMENTS FOR AZTEC 11 12 KW MODELS ON AZTEC 6 9KW MODELS ELEMENT 1 CONNECTIONS ARE NOT USED ELEMENT JUMPER NOT USED ON 6 9 KW BOILERS FIG 24...

Страница 25: ...here is a break in the element cable this would show up as a fault Check all element cables and connections PCB Running Temperature The PCB control unit has a built in temperature control sensor which...

Страница 26: ...ares co Tel 0161 620 6677 18 8 10 11 2 21 20 1 14 9 12 19 15 7 22 17 18 5 16 17 16 18 11 10 6 23 4 18 3 25 24 B L N E A C A B C 19 13 24 25 12 19 33 31 22 29 27 30 26 43 34 28 35 39 38 32 40 35 16 16...

Страница 27: ...W 1 221880 3 E94 759 PCB Control Unit 2kW 1 222558 3 E94 760 PCB Control Unit 6 9 11 12 kW 1 221823 4 E94 761 2 kW Electric Element 2 kW boiler 1 221838 4 E94 762 2 kW Electric Element 6 kW boiler 3 2...

Страница 28: ...uk Trianco Limited Copyright in this brochure and the drawings or illustrations contained in it is vested in Trianco Limited and neither the brochure or any part thereof may be reproduced without pri...

Отзывы: