4.2 Steps before measurement
Setting up flowtube data
Getting started
Select and configure the constant of the flowtube used in combination with the
transmitter, flowtube type, and diameter.
Default settings
The settings of EX 300.0, MGG, and DIA 050.0 are applied when no flowmeter is specified
for the combined use with the transmitter.
Note:
ȲIf you have purchased a combination set including a transmitter and a flowtube, the
flowtube data are already configured by real current calibration. Note that any change
will result in an output error from the flowmeter. Refer to Table 4-1.
WARNING
Improper setting of flowtube information can result in
output errors from the flowmeter.
Step
Procedure
Screen
1
Follow the procedure for entering BASIC SETUP MODE
to display the screen for setting up the flowtube data.
m
3
/h
2
Touch the → key to set up the constant for the flowtube.
Use the and keys to enter the value for the EX section
which is printed on the name plate of the flowtube to be
used in combination with the transmitter.
m
3
/h
3
Next, touch the → key to select the flowtube type.#Use
the and keys to select the MODEL number which is
printed on the name plate of the flowtube to be used in
combination with the transmitter.
m
3
/h
4
Next, touch the → key to select the diameter.#Use the
and keys to select the diameter of the flowtube used in
combination with the transmitter.
m
3
/h
5
Touch the →key to move the cursor underneath the *
mark.
m
3
/h
Содержание MagneW Plus+ MGG14C
Страница 6: ...iv ...
Страница 8: ...vi ...
Страница 11: ...1 3 Figure1 3 System using a Foundation Fieldbus ...
Страница 14: ...1 6 The following table is a summary of the functions of each of the keys ...
Страница 20: ...1 12 CALIBRATION OFF SHIPPING INFO OFF MAINTENANCE MODE MODE RETURN BASIC SETUP Figure1 10 MAINTENANCE MODE ...
Страница 26: ...2 6 ...
Страница 42: ...4 6 ...
Страница 78: ...A 10 ...
Страница 105: ......
Страница 108: ......
Страница 110: ......