AB-6529 

Specifications 

Basic specifications 

Item Specification 

Rated voltage 

100 V AC to 240 V AC, 50 Hz/60 Hz 

Allowable voltage 
range 

85 V AC to 264 V AC, 50 Hz/60 Hz 

Power shutdown 
detection 

80 V AC or less 

Power consumption 

40 VA 

Power supply 

Leakage current 

1 mA or less 

Ambient temperature 

C to 50 

Ambient humidity 

10 %RH to 90 %RH (Non-condensing) 

Altitude 

2000 m or lower 

Rated operating 
conditions 

Vibration 

Max. 3.2 m/s² (at 10 Hz to 150 Hz) 

Ambient temperature 

-20 

C to 60 

Ambient humidity 

5 %RH to 95 %RH (Non-condensing) 

Vibration for storage 

Max. 3.2 m/s² (at 10 Hz to 150 Hz) 

Environmental 
conditions 

Transport/storage 
conditions 

Vibration for transport

Max. 9.8 m/s² (at 10 Hz to 150 Hz) 
Green LED ON: 

Power ON 

Power supply 
(POWER) 

Green LED OFF: 

Poser OFF 

Red LED ON: 

Major failure or system restart 

Major failure (ERR1) 

Red LED OFF: 

Normal operation 

Red LED ON: 

Minor failure or system restart 

Operation 

Minor failure (ERR2) 

Red LED OFF: 

Normal operation 

LED indication 

Communication 

NC-bus 

Transmit (TX), Receive (RX) 

RAM, RTC 

Lithium battery backup 

Power failure backup 

Data file 

Non-volatile memory backup 

Transmission system 

Current transmission 

Transmission speed 

4800 bps 

Transmission distance

500 m 

Communications NC-bus 

Remote units 

Max. 25 remote units connectable 

Weight 400 

Material (housing), color 

Modified PPE, light gray 

Power supply, ground 

M3 screw terminals (7.62 mm pitch between terminals)  

Terminals connection 

NC-bus communication 

Quick-fit screwless (clamp) terminal block 

 

Wiring specifications 

Basic unit 

Item Wiring 

Wiring 

length 

Condition 

Power supply 

JIS IV

 

2.0 mm² or JIS CVV

 

2.0 mm² or greater 

 

 

Grounding 

JIS IV2.0 mm² or JIS CVV2.0 mm² or greater 

 

Ground resistance: 100 

 or lower 

NC-bus 

 

JCS  IPEV-S 0.9 mm² 

500 m 

 

Notes: 

  Pin terminals cannot be used. 

  JIS: Japanese Industrial Standards 

  JCS: Japanese Electric Wire and Cable Makers’ Association

 

Содержание Inflex GD WY5110

Страница 1: ...d Azbil Corporation s field devices Intelligent Component Series devices are also connectable to Infilex GD via SAnet allowing high performance control Features Compact design Small size body allows free installation in a desired place I O module configurations Input and output types can be selected and the number of points to be mounted can be increased or decreased corresponding to the applicati...

Страница 2: ...ce with all applicable safety standards Installation must be carried out according to the operating conditions power temperature humidity vibration shock installation position atmospheric condition etc specified in this manual to prevent equipment damages All wiring must comply with local codes of indoor wiring and electric installation rules Use crimp terminal lugs with insulation for electric wi...

Страница 3: ...module to be combined with Infilex GD Model WY5110 separate order is required Regarding I O modules UT module integral type Operator Panel and SAnet interface module to be combined with Model WY5111 refer to AB 6527 Specifications Instructions of Model RY50XX Parts for Installation Part number Description 83165861 001 Screw tab 83104567 001 DIN rail mounting bracket Note For mounting Infilex GD ei...

Страница 4: ...ed LED OFF Normal operation Red LED ON Minor failure or system restart Operation Minor failure ERR2 Red LED OFF Normal operation LED indication Communication NC bus Transmit TX Receive RX RAM RTC Lithium battery backup Power failure backup Data file Non volatile memory backup Transmission system Current transmission Transmission speed 4800 bps Transmission distance 500 m Communications NC bus Remo...

Страница 5: ...ype Operator Panel UT module and SAnet I F module For the specifications of I O modules UT module and SAnet interface module refer to Specifications Instructions of Model RY50XX AB 6527 For the specifications of integral type of Operator Panel refer to Specifications Instructions of Model RY5001Q QY5100W AB 6546 CE Marking Conformity This product must be installed in a panel cabinet Besides the pr...

Страница 6: ...AB 6529 6 Dimensions Figure 3 Dimensions mm 60 90 140 ...

Страница 7: ...lex GD basic unit At this time hold the male connector with the mark facing left and insert it as the mark points to the mark on the Infilex GD basic unit 2 Connection of Data Setter Model QY7211B PC MMI Convert the D SUB connector to the mini DIN connector with the conversion cable Part No 83104995 001 At this time hold the male connector with the mark facing left and insert it as the mark points...

Страница 8: ...ule UT module integral type Operator Panel and or SAnet I F module to be assembled Their dimensions are the same Width of Infilex GD One module 30 mm n quantity Infilex GD basic unit 60 mm Notes Panel mount type Operator Panel is not directly assembled with Infilex GD To connect it to Infilex GD a UT module is required For details of panel mount type Operator Panel please refer to Specifications I...

Страница 9: ...UT module integral type Operator Panel and or SAnet I F module to be assembled Their outside dimensions are the same Width of Infilex GD One module 30 mm n quantity Infilex GD basic unit 60 mm Notes Panel mount type Operator Panel is not directly assembled with Infilex GD To connect it to Infilex GD a UT module is required For the dimensions of panel mount type Operator Panel please refer to Speci...

Страница 10: ...place the wires using cable ties or the like connected to Infilex GD so as not to hide LED Data Setter connector mark S1 switch battery holder or indication tag as shown in Fig 8 Make sure there is no slack in the wires from the cable ducts to Infilex GD Figure 8 Connected cables in position Tube marker Since Infilex GD adopts a quick fit screwless terminal block wires are connected without crimp ...

Страница 11: ...he power ON If the product has never or hardly been operated in OFF state for a year replace the lithium battery before the product operation Battery replacement Replace the lithium battery while Infilex GD is ON Figure 11 Battery replacement 1 Pull out the battery holder using a slotted screwdriver 2 Disconnect the connector and detach the lithium battery from the battery holder 3 Place a new lit...

Страница 12: ...urning on the power make sure that the wires are correctly connected Several tens of seconds are required for the product normal operation after the power is turned on During this time the red LED ERR1 major failure on the front lights up indicating major failure temporarily but this does not indicate an error Do not connect wires to vacant terminals Leave at least 35 mm clearance between the top ...

Отзывы: