AB-6580 

Specifications 

Basic specifications 

Item Specification 

Rated voltage 

100 V AC to 240 V AC, 50 Hz/60 Hz 

Allowable voltage range 85 V AC to 264 V AC, 50 Hz/60 Hz 
Power shutdown 
detection 

80 V AC or less 

Power supply 

Power consumption 

40 VA 

Ambient temperature 

°

C to 50 

°

Ambient humidity 

10 %RH to 90 %RH (non-condensing) 

Altitude 

2000 m or lower 

Rated operating 
conditions 

Vibration 

Max. 3.2 m/s

2

 at 10 Hz to 150 Hz 

Ambient temperature 

-20 

°

C to 60 

°

Ambient humidity 

5 %RH to 95 %RH (non-condensing) 

Vibration for storage 

Max. 3.2 m/s

2

 at 10 Hz to 150 Hz 

Environmental 
conditions 

Transport/storag
e conditions 

Vibration for 
transportation 

Max. 9.8 m/s

2

 at 10 Hz to 150 Hz 

Green LED ON: 

Power ON 

Power supply (POWER)

Green LED OFF: 

Power OFF 

Red LED ON: 

Major failure or system restart 

Major failure (ERR1) 

Red LED OFF: 

Normal operation 

Red LED ON: 

Minor failure or system restart 

Operation 

Minor failure (ERR2) 

Red LED OFF: 

Normal operation 

LED indication 

Communication LC-bus 

TX: 

Transmit, RX: Receive, SERV: Service 

RAM, RTC* 

Lithium battery backup 

Power failure backup 

Data file 

Non-volatile memory (flash memory) backup 

Transmission system 

LonTalk protocol (TP/FT-10 transceiver) 

Transmission speed 

78 kbps 

Transmission distance 

900 m (for bus topology connection) 

Communications LC-bus 

Remote units 

Max. 50 remote units connectable 

Weight 400 

Material (housing), color 

Modified PPE, light gray 

Power supply, ground 

M3 (7.62 mm pitch between terminals) 

Terminals connection 

LC-bus communication 

Modular connector 

Note: 

  RTC: Real Time Clock.  RTC is backed up by a lithium battery to ensure accurate clocking while the power is OFF. 

 

Wiring specifications 

Basic unit 

Item Wiring*

1

 Wiring 

length 

Condition 

Power supply*

2

 JIS*

IV2.0 mm

2

 or JIS CVV 2.0 mm

2

 or greater 

 

 

Ground*

2

 

JIS IV 2.0 mm

2

 or JIS CVV 2.0 mm

2

 or greater 

 

Ground resistance: 100 

Ω

 or lower 

LC-bus 

EIA/TIA-568 category 5 or over (

φ

0.5 

×

 4 poles) 

900 m 

For bus network topology 

Notes 

1  Pin terminal is not applicable to wiring of Infilex GC. 

2  M3 screw terminal block is provided for wiring of power supply and ground.  Be sure to crimp the crimp terminal lugs on the wire ends. 

3  JIS: Japanese Industrial Standards 

 

Содержание INFILEX GC WY5311

Страница 1: ...ed in terms of both the software and hardware Features Compact design Small size body allows free installation in a desired place Various input output I O configurations Input and output types can be...

Страница 2: ...les Use crimp terminal lugs with insulation for electric wires connected to the screw terminals Connect cables to the power source with terminals or the like for permanent connection Make sure all the...

Страница 3: ...e Digital user terminal Analog user terminal Figure 2 System configuration example of standalone Infilex GC Notes On LS bus max 50 controllers can be connected Max wiring length of LS bus is 900 m Inf...

Страница 4: ...odules to be combined with Model WY5311 refer to AB 6527 Specifications Instructions of Model RY50XX Parts for Installation For details regarding Infilex GC installation refer to Installation manual o...

Страница 5: ...Transmit RX Receive SERV Service RAM RTC Lithium battery backup Power failure backup Data file Non volatile memory flash memory backup Transmission system LonTalk protocol TP FT 10 transceiver Transmi...

Страница 6: ...fications of I O modules user interface modules and Operator Panel For the specifications of I O modules and user interface modules refer to Specifications Instructions of Model RY50XX AB 6527 For the...

Страница 7: ...AB 6580 7 Dimensions Figure 4 Dimensions mm 60 90 140...

Страница 8: ...See Table 2 for SERV LED operation Major alarm initializing ERR1 ON Minor alarm initializing ERR2 ON Table 2 Indication and operation of SERV LED Status LED indication ON OFF Normal Normal Application...

Страница 9: ...LC bus LonTalk For setting Infilex GC and other remote units connected on both protocol LC bus and LS bus Connect Data Setter with Data Setter adaptor to LC bus port or CONF port of Infilex GC LS bus...

Страница 10: ...ON If the product has never or hardly been operated in OFF state for a year replace the lithium battery before the product operation Battery replacement Replace the lithium battery with Infilex GC in...

Страница 11: ...Several tens of seconds are required for the product normal operation after the power is turned on During this time the ERR1 LED red for major alarm lights up temporarily but this does not indicate a...

Страница 12: ...AB 6580 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 4 0 Sep 2015 AB 6580 H W03 J AI 6580 Rev 3 1 Printed in Japan 12...

Отзывы: