Azbil INFILEX GC WY5311 Скачать руководство пользователя страница 2

AB-6580 

Safety Instructions 

Please read instructions carefully and use the product as specified in this manual.  Be sure to keep this manual near by for ready 
reference.  

Usage Restrictions 

This product is targeted for general air conditioning.  Do not use this product in a situation where human life may be affected.  If 
this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact Azbil 
Corporation’s sales representative.  Azbil Corporation will not bear any responsibility for the results produced by the operators.

 

 WARNING  

 

  DANGER: To prevent the risk of severe or fatal electrical shock, always disconnect power source and product 

power supply before performing any wiring. 

 

  Be sure to ground with 100 

Ω

 or lower ground resistance.  Improper grounding may cause electrical shock or

equipment damages. 

 

  Do not detach the terminal cover at any time except when wiring.  After wiring, be sure to attach the terminal cover. 

Before attaching/detaching the terminal cover, make sure that the wires are not current-carrying to prevent 
electrical shock. 

 

  Disconnect power before the product replacement to prevent electrical shock. 

 

  Do not disassemble the product.  Disassembly may result in electrical shock or equipment damage. 

 

  CAUTION 

 

  Installation and wiring must be performed by qualified personnel in accordance with all applicable safety 

standards. 

 

  This product must be operated under the operating conditions (power, temperature, humidity, vibration, shock, 

installation position, atmospheric condition, etc) specified in this manual to prevent equipment damages. 

 

  All wiring must comply with local codes of indoor wiring and electric installation rules. 

 

  Use crimp terminal lugs with insulation for electric wires connected to the screw terminals. 

 

  Connect cables to the power source with terminals or the like for permanent connection. 

 

  Make sure all the wires are tightly connected to prevent heat generation or equipment damages. 

 

  If more than the rated power supply voltage is applied, product replacement is required for safety. 

 

  Install this product in a location out of reach of unauthorized people. (e.g. Inside of the control panel cabinet) 

 

  Lightning protection based on regional characteristics and building structure is needed in order to minimize 

lightning damages. 

 

  Noise protection is necessary when the product is installed in a location close to many noise sources. 

 

  Do not block the vent holes of the product to prevent equipment damages.  Remove protective sheet after 

installation and wiring. 

 

  After mounting the product on DIN rail, make sure that the holding parts of all the modules are properly fixed with 

their whole parts lifted.  The product may drop from the DIN rail and be damaged due to improper mounting. 

 

  Do not plug in or out I/O modules or user interface modules with the product power turned on to prevent equipment 

damages. 

 

  Dispose of the lithium battery in accordance with your local regulations. 

 

  Dispose of this product in accordance with your local regulations.  Do not reuse all or part of this product. 

 
Trademark information: 
Infilex, Neopanel, PARAMATRIX and savic-net are trademarks or registered trademarks of Azbil Corporation in Japan or in other countries. 
BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). 
CompactFlash is a U.S. registered trademark of SanDisk Corporation. 
KPEV is a registered trademark of Furukawa Electric Co., Ltd. 
LONMARK, LonTalk, and LONWORKS are trademarks of Echelon Corporation registered in the United States and other countries. 

Содержание INFILEX GC WY5311

Страница 1: ...ed in terms of both the software and hardware Features Compact design Small size body allows free installation in a desired place Various input output I O configurations Input and output types can be...

Страница 2: ...les Use crimp terminal lugs with insulation for electric wires connected to the screw terminals Connect cables to the power source with terminals or the like for permanent connection Make sure all the...

Страница 3: ...e Digital user terminal Analog user terminal Figure 2 System configuration example of standalone Infilex GC Notes On LS bus max 50 controllers can be connected Max wiring length of LS bus is 900 m Inf...

Страница 4: ...odules to be combined with Model WY5311 refer to AB 6527 Specifications Instructions of Model RY50XX Parts for Installation For details regarding Infilex GC installation refer to Installation manual o...

Страница 5: ...Transmit RX Receive SERV Service RAM RTC Lithium battery backup Power failure backup Data file Non volatile memory flash memory backup Transmission system LonTalk protocol TP FT 10 transceiver Transmi...

Страница 6: ...fications of I O modules user interface modules and Operator Panel For the specifications of I O modules and user interface modules refer to Specifications Instructions of Model RY50XX AB 6527 For the...

Страница 7: ...AB 6580 7 Dimensions Figure 4 Dimensions mm 60 90 140...

Страница 8: ...See Table 2 for SERV LED operation Major alarm initializing ERR1 ON Minor alarm initializing ERR2 ON Table 2 Indication and operation of SERV LED Status LED indication ON OFF Normal Normal Application...

Страница 9: ...LC bus LonTalk For setting Infilex GC and other remote units connected on both protocol LC bus and LS bus Connect Data Setter with Data Setter adaptor to LC bus port or CONF port of Infilex GC LS bus...

Страница 10: ...ON If the product has never or hardly been operated in OFF state for a year replace the lithium battery before the product operation Battery replacement Replace the lithium battery with Infilex GC in...

Страница 11: ...Several tens of seconds are required for the product normal operation after the power is turned on During this time the ERR1 LED red for major alarm lights up temporarily but this does not indicate a...

Страница 12: ...AB 6580 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 4 0 Sep 2015 AB 6580 H W03 J AI 6580 Rev 3 1 Printed in Japan 12...

Отзывы: