Azbil INFILEX GC WY5311 Скачать руководство пользователя страница 1

AB-6580 

  Azbil Corporation’s Infilex series controllers: Infilex is named for “Infinity” and “Flexible.” 

 

Specifications/Instructions

 

Infilex

 GC 

Multipurpose Controller 

Model WY5311 

 

General 

Infilex GC (Infilex: named for “Infinity” and “Flexible”) Model 
WY5311 is a multipurpose controller designed to control 
building equipment, such as air handling unit (AHU).  Infilex 
GC enables to control the temperature and humidity, as well 
as building equipment operation. 

Infilex GC can be operated with a user terminal and with 
Operator Panel.  Besides, Infilex GC can communicate with 
BMS (building management system) Azbil Corporation’s  
savic-net

 FX via LonTalk

®

 protocol.  By sending the 

operation status to the main control unit (monitoring 
computer) and by controlling the operation based on the 
commands sent from the main control unit, the integrated 
control of the entire building can be executed. 

Infilex GC consists of a basic unit and connectable I/O 
modules (and a user interface module).  The number and 
types of the modules can be flexibly changed corresponding 
to the control or management to fit in various applications.  
Additionally, since the software to be installed can be freely 
edited, an optimum application for building equipment can be 
configured in terms of both the software and hardware. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Features 

 Compact 

design: 

Small size body allows free installation in a desired 
place. 

 

Various input/output (I/O) configurations: 
Input and output types can be selected, and the number 
of points to be mounted can be increased or decreased 
corresponding to the application. 

 

Editable software configurations: 
Optimal software for the contents of the application can 
be configured. 

 

User interface module (Operator Panel): 
Operator Panel (panel mount type/integral type) 
connected to Infilex GC allows you, without changing the 
settings from the BMS center unit, to change the Infilex 
GC settings. 

 

Remote control with a user terminal: 
Neopanel

 or Neoplate is connectable, so that a user at 

a remote location can perform ON/OFF operation and 
change temperature setting. 

 

 

 

Autonomous distributed control: 
Even if a trouble occurs in the BMS, the backup 
operation is performed individually to distribute potential 
risks caused by malfunction of the system. 

 Installation: 

A quick-fit screwless (clamp) terminal block is used for 
the communication terminal block of the I/O module, 
ensuring the labor saving of the wiring work. 
Additionally, either DIN rail mounting or screw mounting 
can be selected. 

 

L

ON

M

ARK

®

 certified product: 

Infilex GC is L

ON

M

ARK

®

 certified and thus interoperable 

integrated in the L

ON

W

ORKS

®

 system. 

 

CE Marking certified product: 
Infilex GC conforms to all the applicable standards of CE 
Marking (Class A). 

 

 

 

Содержание INFILEX GC WY5311

Страница 1: ...ed in terms of both the software and hardware Features Compact design Small size body allows free installation in a desired place Various input output I O configurations Input and output types can be...

Страница 2: ...les Use crimp terminal lugs with insulation for electric wires connected to the screw terminals Connect cables to the power source with terminals or the like for permanent connection Make sure all the...

Страница 3: ...e Digital user terminal Analog user terminal Figure 2 System configuration example of standalone Infilex GC Notes On LS bus max 50 controllers can be connected Max wiring length of LS bus is 900 m Inf...

Страница 4: ...odules to be combined with Model WY5311 refer to AB 6527 Specifications Instructions of Model RY50XX Parts for Installation For details regarding Infilex GC installation refer to Installation manual o...

Страница 5: ...Transmit RX Receive SERV Service RAM RTC Lithium battery backup Power failure backup Data file Non volatile memory flash memory backup Transmission system LonTalk protocol TP FT 10 transceiver Transmi...

Страница 6: ...fications of I O modules user interface modules and Operator Panel For the specifications of I O modules and user interface modules refer to Specifications Instructions of Model RY50XX AB 6527 For the...

Страница 7: ...AB 6580 7 Dimensions Figure 4 Dimensions mm 60 90 140...

Страница 8: ...See Table 2 for SERV LED operation Major alarm initializing ERR1 ON Minor alarm initializing ERR2 ON Table 2 Indication and operation of SERV LED Status LED indication ON OFF Normal Normal Application...

Страница 9: ...LC bus LonTalk For setting Infilex GC and other remote units connected on both protocol LC bus and LS bus Connect Data Setter with Data Setter adaptor to LC bus port or CONF port of Infilex GC LS bus...

Страница 10: ...ON If the product has never or hardly been operated in OFF state for a year replace the lithium battery before the product operation Battery replacement Replace the lithium battery with Infilex GC in...

Страница 11: ...Several tens of seconds are required for the product normal operation after the power is turned on During this time the ERR1 LED red for major alarm lights up temporarily but this does not indicate a...

Страница 12: ...AB 6580 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 4 0 Sep 2015 AB 6580 H W03 J AI 6580 Rev 3 1 Printed in Japan 12...