Wiring Precautions

Be sure to use crimped terminals for wiring terminals.
When wiring is finished, check the connections for any
miswiring before turning the power ON.

Connecting the Power Supply

Connect the power terminal as follows:

The power supply unit must be a UL approved Class 2 power
supply unit or Class 2 transformer in order to apply UL.

Handling Precautions

• Power is mutually connected between linked

modules.

• Supply power to one of the linked modules.
• Select a power supply that can cover the total

power consumption of all linked modules.

• Use of free terminal (3) is prohibited.

Do not use this terminal, for example, for wiring
relays.

Connecting CPL communications

CPL communications (RS-485) is performed using a 3-
lead connection.

Ex : Connection with a 5-lead device

Handling Precautions

• Do not connect an external terminator as the

DMC10E has a built-in resistor equivalent to a
terminator.

• Be sure to connect SG terminals each other.

Failure to do so might cause unstable
communications.

Specifications

* For details refer to the Distributed Multi-channel

controller DMC10 User's Manual (Description of
Functions Version)  CP-UM-5143E.

1

2

3

+        -

24Vdc

Do not use

14

Extended event
(CH2)

15

11

Extended event
(CH1)

12

13

NO

NC

16

Extended event
(CH3)

17

18

NO

NC

19

Extended event
(CH4)

20

11

12

13

14

15

16

17

18

19

20

NO: Normally Open (Open)
NC: Normally Close (Close)

E3

4. Wiring

5. Specificathions

Item

Specifications

Extended

Number of

4

event output

points

Output rating

Output type

: Relay contact output

Contact type : SPST/2, SPDT/2
Contact rating : 250Vac, 1A

30Vdc, 1A

Life

: Min. 100,000 operations

(resistive load)

Min. switching specification: 5V, 10mA

Type of action Type of action on DMC10*

The type of action can be enabled
by setting to bus event output on the
DMC10.*

Optional

The same bus event output of each

functions

DMC10 is ORed.*

General

Rated power

24Vdc

specifications voltage

Power

Max. 3W (in operating state)

consumption

Insulation

Across primary and secondary sides:

resistance

Min. 500Vdc 20M

Dielectric

Across primary and secondary sides:

strength

1500Vac 1min

Power ON

Max. 10A

rush current

Case, base

Polycarbonate/light gray

material/color

(munsell: 2.5Y7.5/1 or equivalent)

Operating

Ambient temperature : 0 to 50

˚

C

conditions

Ambient humidity

: 10

˚

 to 90%RH

Power voltage

: 21.6 to 26.4Vdc

Vibration resistance : 0 to 2m/s

2

(10 to 60Hz, for 2h each in X, Y and

Z directions)

Impact resistance

: 10m/s

2

Mounting angle

10

˚

of reference plane

Transport/

Ambient temperature : -20 to +70

˚

C

storage

Ambient humidity

: 10

˚

 to 95%RH

conditions

(condensation not allowed)
Vibration resistance : 0 to 5m/s

2

(10 to 60Hz, for 2h each in X, Y and

Z directions)

Impact resistance

: 392m/s

2

(screw mount)
196m/s

2

(DIN rail mount)

Package drop test : Drop height 60cm
(free fall on one corner, three sides

and six surfaces)

Mass

Max.200g

Содержание DMC10E

Страница 1: ...CP UM 5131JE DMC10E 1999 Yamatake Corporation ALL RIGHTS RESERVED DMC10E DMC10 CP UM 5143 10 100W 2 1 J1...

Страница 2: ...ON 2 M3 CPL CONNECT DIN DIN 1 DC24V 2 DC24V 3 4 DA 5 DB 6 SG CPL 3 RS 485 1 2 3 4 5 5 6 3 15m DIN CPL CPL DIN DIN 2 M3 DIN DIN DIN DIN 30 5 10 0 2 30 0 9 0 3 5 78 5 0 2 100 M3 mm 1 CH DMC10E 4CH 4 C...

Страница 3: ...13 14 15 16 17 18 19 20 NO Normally Open NC Normally Close 4 5 4 SPST 2 SPDT 2 AC250V 1A DC30V 1A 10 5V 10mA DMC10 DMC10 DMC10 OR DC24V 3W 1 2 DC500V 20M 1 2 AC1500V 1min 10A PC 2 5Y7 5 1 0 50 10 90 R...

Страница 4: ...15 100 6419 2 7 3 1999 4 R 2008 5 10 A 011 781 5396 052 238 3037 022 292 2004 06 6881 3383 4 048 653 8733 082 554 0750 03 6810 1200 093 952 1210 COMPO CLUB http www compoclub com http jp azbil com 046...

Страница 5: ...re the DMC10E properly according to predetermined standards Also wire the DMC10E using designated power leads according to recognized installation methods Failure to do so might cause electric shock f...

Страница 6: ...rtical with the DIN rail locking tab at the bottom When mounting the base by screws Secure the two mounting holes on the base by M3 screws Unit mm When securing on a DIN rail Secure the DMC10E on the...

Страница 7: ...14 15 16 17 18 19 20 NO Normally Open Open NC Normally Close Close E3 4 Wiring 5 Specificathions Item Specifications Extended Number of 4 event output points Output rating Output type Relay contact ou...

Страница 8: ...mounting and removal of the body Unit mm External Dimensions E4 Specifications are subject to change without notice 08 Advanced Automation Company 1 12 2 Kawana Fujisawa Kanagawa 251 8522 Japan URL h...

Отзывы: