Body
■
Base
■
Mounting Locations
Avoid installing the DMC10E in the following locations:
• Locations subject to high and low temperature, high and
low humidity exceeding the specified ranges
• Locations subject to corrosive gases such as sulfide
gases
• Locations subject to dust or oil smoke
• Locations subject to direct sunlight, wind or rain
• Locations subject to vibration or shock exceeding the
specified ranges
• Locations under high-voltage lines and near sources of
electrical noise such as welders
• Locations within 15 meters of high-voltage ignition
equipment such as boilers
• Locations where magnetic fields are generated
• Locations near flammable liquid or steam
■
Linking modules
The
DMC10E
can be linked with other modules by the
connectors on the left and right of the base.
Modules must be linked before the
DMC10E
is mounted
on the DIN rail or mounted by screws.
By linking modules together, the power supply of each
module and CPL communications are connected,
eliminating the need for wiring.
CPL communications can be disconnected by the
communications disconnection switch on the base.
■
Installation Procedure
The
DMC10E
can be mounted in either of two ways, by
mounting its base by screws or by securing on a DIN rail.
Handling Precautions
• Install this module so that it is vertical, with the DIN
rail locking tab at the bottom.
●
When mounting the base by screws
Secure the two mounting holes on the base by M3
screws.
Unit: mm
●
When securing on a DIN rail
Secure the DMC10E on the DIN rail, fully draw out
the DIN rail locking tab and hook the base onto the
DIN rail. Next, push the DIN rail locking tab upwards
until you hear it click into place.
■
Mounting the body on the base
Fit the hook into the base and push the body into the base
until you hear it click into place.
To remove the body from the base, pull the body towards
you while pressing down the lever.
1. Model Selection Guide
Basic .
Number of
Wiring Control
Option
Additional
Specifications
Model No Channels
Method
Output
Processing
DMC10E
4
4-channel output
C
Connector wiring
R
Relay output
00
None
00
None
2. Names and Fanctions of Parts
EV1 to EV4 operation lamps:
Light when the relay contact
of the target channel inside
the module turns ON.
Mounting holes
(2 locations)
:
For securing the
base with M3 screws
Power supply terminal
Lever
:
For securing
the body
Communications
disconnection
switch
:
Used for disabling
local
CPL communications
with devices linked on
the left side
(factory setting:
CONNECT )
(linked state)
DIN rail locking tab:
Used for locking on
a DIN rail
Mounting hole
No.
Signal
4
DA
5
DB
6
SG
Local CPL
communications
terminal
:
3-lead RS-485
connector terminal
No.
Signal
1
24Vdc(+)
2
24Vdc(-)
3
Do not use
1
2
3
4
5
5
6
3. Installation
(30)
5
10
0.2
30
+ 0.9
+ 0.3
5
78.5
0.2
(100)
M3
E2
Hook
Lever