7-30
●
C93
(time proportional output system)
0: Goes not go on again within time proportional cycle
1: Does on again within time proportional cycle
• This setting determines whether the output is to go on again after the result of a
PID computation has changed in a time proportional cycle (cycle time) and the
output has been turned off.
• The difference between the two settings is illustrated below.
●
C95
(voltage output control)
[Constant current type]
• Input current (maximum):
Check that the input current is within the
maximum allowable current or less, then the
parallel connection can be made.
• Operating voltage range (input): Check that the voltage between the terminals
of the voltage pulse output is within the
specified range.
This example shows the calculation for the connection of this unit and the
PGM10N015.
(Note: For connection with other model number, check the specifications of each
model.)
• Input current(maximum):
Since the input current is 10mA or less, up to
two units (10mA X 2 = 20mA < 24mA
[maximum allowable current]) can be
connected in parallel.
• Operating voltage range (input): The rating voltage is 3.5 to 30Vdc. Therefore,
terminal voltage when terminals are opened, is
within the range.
Connection diagram
When set to 0
20% 65% 40%
OFF
ON
PID computation
result
20% 65% 40%
OFF
ON
PID computation
result
When set to 1
Cycle time
Cycle time
Cycle time
Cycle time
Chapter 7. PARAMETER SETUP
This unit
+
–
+
–
PGM10N
+
–
PGM10N