![Azbil dcp551 mark II Скачать руководство пользователя страница 108](http://html1.mh-extra.com/html/azbil/dcp551-mark-ii/dcp551-mark-ii_user-manual_3042608108.webp)
7-2
■
Modifying individual items and exiting the setting mode
Pressing the
ENTER key
while an individual item is displayed causes the set
value to flash and enables the registration state. At this point, the
key
and
key
allow you to increase or decrease the values, while the
key
and
key
move the digit positions on the display at which the values flash.
Pressing the
ENTER key
after the flashing number has been changed to the
desired value stops the flashing, the number reverts to the on state and the new
setting is stored in internal memory.
Modification of settings is terminated by pressing either the
PARA key
(valid for
variable parameters and event configuration data),
PID key
(valid for PID
parameters and constant value control data),
SETUP key
(valid for setup data) or
DISP key
. Pressing the
PARA key
,
PID key
or
SETUP key
moves the cursor
to the next item stops the flashing and the number reverts to its normal on state.
Pressing the
DISP key
enables the normal display mode.
Should display panel 2 show “-----” during display of an individual item or
pressing the
ENTER key
not enable the registration state, it means that settings
cannot be made or modified for that item.
Handling Precautions
• When
PA01
is set to more than 1 in a variable parameter setting,
PA03
and items beyond are not displayed.
PA03
and items beyond cannot be
changed when
PA02
is set to 1 or more.
• Event configuration data settings cannot be changed when
PA02
is set
to a value more than 1. Also, when
PA02
is set to 0 or 1, the event type
setting and some auxiliary settings (output points of code events) cannot
be changed.
• PID parameter settings cannot be changed when
PA02
is set to 4 or 5.
• Setup data settings cannot be changed when
PA02
is set to a value
more than 1 and cannot be displayed in modes other than the READY
mode.
• The fixed control data setting cannot be changed when
PA02
is set to 4
or 5. And, since the
FUNC
and
PID keys
are invalid in modes other than
the READY mode, a
ConSt
setting cannot be displayed or changed.
Chapter 7. PARAMETER SETUP