7-25
0: Displayed
1: Not displayed
0
C
57
57
Programming item
event
0: Displayed
1: Not displayed
0
C
58
58
Programming item
PID group, output limiter group
0: Displayed
1: Not displayed
0
C
59
59
Programming item
G.SOAK, PV shift, repeat
0: Displayed
1: Not displayed
0
C
60
60
Programming item
PV start, cycle, pattern link
0: RAMP-X and RAMP-T (
θ
) combined
1: RAMP-X and RAMP-E (
∆
SP) combined
0
C
61
61
Programming system
0: hours, min (SPU/hour for RAMP-T)
0: min, sec (SPU/min for RAMP-T)
0: 0.1 sec (SPU/sec for RAMP-T)
0
C
62
62
Programming time unit
0
C
63
63
Time display
(display panel 2)
[Description:]
“-----” is displayed and setting is not possible.
----
C
64
64
Unused
0 to 4
A setting of 0 means no decimal point and a setting between 1
and 4 indicates the number of decimal digits.
[Description:]
This setting is reflected in “PVU (SPU)” units.
1
C
65
65
SP decimal point position
PV1 range
lower limit
C
66
66
SP limit lower limit
-19999 to +20000 SPU
[Description:]
When
C01
to
C06
are set,
C66
and
C67
are
automatically set as the upper limit and lower limit of the
range.
PV1 range
upper limit
C
67
67
SP limit upper limit
[Description:]
“-----” is displayed and setting is not possible.
----
C
68
68
Unused
----
C
69
69
Unused
----
C
70
70
Unused
0: SP
1: PV
2: Deviation (DEV)
3: Manipulated variable (MV)
4: PV1
5: PV2
[Description:]
“-----” is displayed and setting is not possible on model
without auxiliary output or with one auxiliary output.
0
C 48
48
Auxiliary output 2 type
-19999 to +20000 SPU (
C48
not equal to 3)
-1999.9 to +2000.0% (
C48
set to 3)
[Description:]
“-----” is displayed and setting is not possible on model
without auxiliary output or with one auxiliary output.
0 SPU
C
49
49
Auxiliary output lower limit (4mA)
10000SPU
C
50
50
Auxiliary output upper limit (20mA)
[Description:]
“-----” is displayed and setting is not possible.
----
C
51
51
Unused
-19999 to +20000 SPU
[Description:]
“-----” is displayed and setting is not possible when
C21
is not equal to 0.
0 SPU
C
52
52
SP output lower limit (4mA)
10000SPU
C
53
53
SP output upper limit (20mA)
[Description:]
“-----” is displayed and setting is not possible.
----
C
54
54
Unused
----
C
55
55
Unused
----
C
56
56
Unused
Item code
Item
No.
User
settings
Settings and descriptions
Factory default
settings
0: remaining segment time
1: total operation time (after READY RUN start)
Chapter 7. PARAMETER SETUP