List of operation displays
Display
Upper display: PV
Lower display: SP
Item
Contents
Initial
value
Setting
value
PV
SP
SP (Target value)
SP low limit to SP high limit
0
LSP
1
(Display example)
LSP
LSP No.
(1st digit: Value at the right end digit)
1 to LSP system group (Max. 8)
1
St
1-
(Display example)
Step No.
Step remaining time
Step operation remaining time
Setting is disabled.
The step No. distinguishes up ramp, down ramp,
and soak.
–
PV
MV
MV (Manipulated Variable)
-10.0 to +110.0% Setting is enabled in MANUAL
mode (Numeric value flashed)
–
HEAt
Numeric value
Heat MV (Manipulated Variable)
Setting is disabled.
-10.0 to +110.0%
–
COOL
Numeric value
Cool MV (Manipulated Variable)
–
fb
Numeric value
MFB (Motor opening feedback
value)
Setting is disabled. +10.0 to +110.0%
Flashing when the value is 0.0 to 100.0% during estimate.
–
PV
At
1
(Display example)
AT progress display (1st digit=
Numeric value at right end digit)
Setting is disabled.
–
Ct
1
Numeric value
CT current value 1
Setting is disabled.
–
Ct2
Numeric value
CT current value 2
Setting is disabled.
–
E
1
Numeric value
Internal Event 1 main setting
-1999 to +9999U or 0 to 9999U
0
E
1.Sb
Numeric value
Internal Event 1 sub setting
0
t
1.--
(Display example)
Numeric value
Timer remaining time 1
Setting is disabled.
Upper display: The distinction by ON delay or
OFF delay is displayed at the side location of “t1.”.
–
E2
Numeric value
Internal Event 2 main setting
Same as Internal Event 1 main setting
0
E2.Sb
Numeric value
Internal Event 2 sub setting
Same as Internal Event 1 sub setting
0
t2.--
(Display example)
Numeric value
Timer remaining time 2
Same as Timer remaining time 1
–
E3
Numeric value
Internal Event 3 main setting
Same as Internal Event 1 main setting
0
E3.Sb
Numeric value
Internal Event 3 sub setting
Same as Internal Event 1 sub setting
0
t3.--
(Display example)
Numeric value
Timer remaining time 3
Same as Timer remaining time 1
–
List of parameter setting displays
MOdE
[Mode bank]
Display
Item
Contents
Initial value Setting value
A--M
AUTO/MANUAL
AUTO
: AUTO mode
MAN
: MANUAL mode
AUTO
r--r
RUN/READY
RUN
: RUN mode
RDY
: READY mode
RUN
l--r
LSP/RSP
lSp
: LSP
RSp
: RSP
LSP
At
AT stop/start
At.OF
: AT stop
At.ON
: AT start
AT stop
dO.Lt
Release all DO latches
Lt.ON
: Latch continue
Lt.OF
: Latch release
Latch continue
C.dI
1
Communication DI1
dI
.OF
: OFF
dI
.On
: ON
OFF
SP
[SP bank]
Display
Item
Contents
Initial value Setting value
RSP
RSP
Setting is disabled.
–
PIDr
PID group No. (RSP)
1 to 8
1
SP-
1
to
SP-8
SP (for LSP 1 to 8)
SP low limit to SP high limit
0
Pid.
1
to
Pid.8
PID group No. (for LSP 1 to 8) 1 to 8
1
rMP.
1
to
rMP.8
Ramp (for LSP1 to 8)
0 to 9999
0
tIM.
1
to
tI
M.8
Time (for LSP to 8)
0.0 to 999.9 or 0 to 9999
0
Ev
[Event bank]
Display
Item
Contents
Initial value Setting value
E
1
to
E8
Internal Event 1 to 8 main setting -1999 to +9999 or 0 to 9999 *
0
E
1.Sb
to
E8.Sb
Internal Event 1 to 8 sub setting
0
E
1.Hy
to
E8.Hy
Internal Event 1 to 8 hysteresis 0 to 9999 *
5
E
1.On
to
E8.On
Internal Event 1 to 8 ON delay time 0.0 to 999.9 or 0 to 9999
0
E
1.OF
to
E8.OF
Internal Event 1 to 8 OFF delay time
0
* The decimal point position varies by meeting the internal event operation type.
PI
D
[PID bank]
Display
Item
Contents
Initial value Setting value
P-
1
to
P-8
Proportional band (PID1 to 8 group) 0.1 to 999.9%
5.0
I
-
1
to
I
-8
Integration time (PID1 to 8 group) 0 to 9999s or 0.0 to 999.9s
(No integration control action when set at "0")
120
d-
1
to
d-8
Derivative time (PID1 to 8 group) 0 to 9999s or 0.0 to 999.9s
(No derivative control action when set at "0")
30
rE-
1
to
rE-8
Manual reset (PID1 to 8 group)
-10.0 to +110.0%
50.0
OL-
1
to
OL-8
MV low limit (PID1 to 8 group)
-10.0 to +110.0%
0.0
OH-
1
to
OH-8
MV high limit (PID1 to 8 group)
-10.0 to +110.0%
100.0
P-
1C
to
P-8C
Cool-side proportional band
(PID1 to 8 group)
0.1 to 999.9%
5.0
I
-
1C
to
I
-8C
Cool-side Integration time (PID1
to 8 group)
0 to 9999s or 0.0 to 999.9s
(No integration control action when set at "0")
120
d-
1C
to
d-8C
Cool-side derivative time (PID1
to 8 group)
0 to 9999s or 0.0 to 999.9s
(No derivative control action when set at "0")
30
OL.
1C
to
OL.8C
Cool-side MV low limit (PID1 to 8 group) -10.0 to +110.0%
0.0
OH.
1C
to
OH.8C
Cool-side MV high limit (PID1 to 8 group) -10.0 to +110.0%
100.0
PARA
[Parameter bank]
Display
Item
Contents
Initial value Setting value
Con
tr
ol
CtrL
Control method
0: ON/OFF control 1: Fixed PID
0 or 1
At.
OL
MV low limit at AT
-10.0 to +110.0%
0.0
At.
OH
MV high limit at AT
-10.0 to +110.0%
100.0
dI
FF
ON/OFF control differential
0 to 9999U
5
OFFS
ON/OFF control operating point offset -1999 to +9999U
0
PV
FL
PV filter
0.0 to 120.0s
0.0
rA
PV ratio
0.001 to 9.999
1.000
bI
PV bias
-1999 to +9999U
0
fl2
RSP filter
0.0 to 120.0s
0.0
ra2
RSP ratio
0.001 to 9.999
1.000
bI2
RSP bias
-1999 to +9999U
0
Time pr
opor
tional output
CyU
Time proportional cycle unit 1 0 to 3 *
1
0
Cy
Time proportional cycle 1
5 to 120s or 1 to 120s *
2
10 or 2
CyU2
Time proportional cycle unit 2 0 to 3 *
1
0
Cy2
Time proportional cycle 2
5 to 120s or 1 to 120s *
2
10 or 2
tP.
ty
Time proportional cycle mode 0: Controllability aiming type
1: Operation end service life aiming type (Only ON/
OFF operation within Time proportional cycle)
0 or 1
MV
outl
MV variation limit
0.0 to 999.9%(No limit when set at "0.0U")
0.0
SP
SPU
SP up ramp (U/min)
0.0 to 999.9U(No ramp when set at "0.0U")
0.0
SPd
SP down ramp (U/min)
0.0
*1 0: Unit of "1s" 1: Fixed at 0.5s 2: Fixed at 0.2s 3: Fixed at 0.1s
*2 5 to 120s when output includes the relay output
U: Unit Maximum unit of Industrial volume in
PV range (°C, Pa,L/min, etc.)
: Essential parameters for PV measurement and control
: Basic parameters
: Required parameters when using optional functions
Et
[Extended tuning bank]
Display
Item
Contents
Initial value Setting value
At.ty
AT type
0: Normal 1: Immediate response 2: Stable *
1
0
JF.bd
Just-FiTTER setting band
0.00 to 10.00
0.30
SP.LG
SP lag constant
0.0 to 999.9
0.0
At-P
AT Proportional Band adjust
0.00 to 99.99
1.00
At-I
AT Integral time adjust
0.00 to 99.99
1.00
At-d
AT Derivative time adjust
0.00 to 99.99
1.00
Ctr.A
Control algorithm
0: PID(Conventional PID) 1: Ra-PID(High-performance PID)
0
JF.Ov
Just-FiTTER assistance coefficient 0 to 100
0
*1 Normal = Standard control characteristics, Immediate response = Control characteristics that respond immediately to
external disturbance, Stable = Control characteristics having less up/down fluctuation of PV
ZOne
[Zone bank]
Display
Item
Contents
Initial value Setting value
ZO-
1
to
ZO-7
Zone 1 to 7
-1999 to +9999U
9999U
ZOdf
Zone hysteresis
0 to 9999 5U
5U
List of setup setting displays
StUP
[Setup bank]
Display
Item
Contents
Initial value Setting value
A
nalog input
C0
1
PV input range type
For details, refer to the PV Input Range Table
88
C02
Temperature unit
0: Celsius (°C) 1: Fahrenheit (°F)
0
C03
Cold junction compensation
0: Performed (internal) 1: Not performed (external)
0
C04
Decimal point position
0: No decimal point
1 to 3: 1 to 3 digits below decimal point
0
C05
PV range low limit
When the PV input type is DC voltage/DC current,
-1999 to +9999U
0
C06
PV range high limit
1000
C07
SP low limit
PV input range low limit to PV input range high
limit
0
C08
SP high limit
1000
C09
PV square root extraction dropout 0.0 to 100.0% (PV square root extraction is not
performed when set at "0.0".)
0.0
C
10
RSP input range type
0: 4 to 20mA 1: 0 to 20mA 2: 0 to 5V
3: 1 to 5V 4: 0 to 10V
0
C
1
1
RSP range low limit
-1999 to +9999U
0
C
12
RSP range high limit
1000
Con
tr
ol ac
tion
C
13
PID calculation adjustment function *
1
0: Enabled 1: Disabled
0
C
14
Control action (Direct/Reverse) 0: Heat control (Reverse action) 1: Cool control (Direct action)
0
C
15
Output operation at PV alarm 0: Control calculation is continued.
1: Output at PV alarm is output.
0
C
16
Output at PV alarm
-10.0 to +110.0%
0.0
C
17
Output at READY (Heat)
-10.0 to +110.0%
0.0
C
18
Output at READY (Cool)
-10.0 to +110.0%
0.0
C
19
Output operation at changing AUTO/MANUAL 0: Bumpless transfer 1: Preset
0
C20
Preset MANUAL value
-10.0 to +110.0%
0.0 or 50.0
C2
1
Initial output type (mode) of PID control 0: Auto 1: Not initialized 2: Initialized
0
C22
Initial output of PID control
-10.0 to +110.0%
0.0 or 50.0
C23
PID decimal point position (decimal
point of integral time and delivative time)
0: No decimal point
1: 1 digit after decimal point
0
C24
Zone PID operation
0: Disabled 1: Changed by SP 2: Changed by PV
0
C26
Heat/Cool control
0: Not used 1: Used
0
C27
Heat/Cool
0: Normal 1: Energy saving
0
C28
Heat/Cool control dead zone -100.0 to +100.0%
0.0
C29
Heat/Cool change point
-10.0 to +110.0%
50.0
SP
C30
LSP system group
1 to 8
1
C3
1
SP ramp type
0: Standard 1: Multi-ram
2: Step operation When the power is turned ON
again, the step operation is stopped (READY)
3: Step operation When the power is turned ON
again, the step operation is reset
0
C32
SP ramp unit
0: 0.1U/s 1: 0.1U/min 2: 0.1U/h
1
C33
STEP time unit
0: 0.1s 1: 1s 2: 1min
0
C34
STEP PV start
0: Disabled 1: Enabled
0
C35
STEP loop
0: Stop 1: Loop 2: Final step continued
0
C36
CT1 operation type
0: Heater burnout detection 1: Current value measurement
0
C37
CT1 output
0 to 1: Control output 1 to 2, 2 to 4: Event output 1 to 3
0
C38
CT1 measurement wait time
30 to 300ms
30
C39
CT2 operation type
Same as CT1
0
C40
CT2 output
Same as CT1
0
C4
1
CT2 measurement wait time
Same as CT1
30
Con
tinuous output
C42
Control output 1 range
Current output 1: 4 to 20mA 2: 0 to 20mA
Continuous voltage output 1: 1 to 5 V 2: 0 to 5 V 3: 0 to 10 V
1
C43
Control output 1 type
0: MV 1: Heat MV 2: Cool MV 3: PV
4: PV before ratio, bias, and filter 5: SP 6: Deviation
7: CT1 current value 8: CT2 current value
9: MFB (Including estimation MFB) 10: SP+MV 11: PV+MV
0
C44
Control output 1 scaling low limit -1999 to +9999U
0.0
C45
Control output 1 scaling high limit
100.0
C46
Control output 1 MV scalable bandwidth 0 to 9999 (Valid when control output 1 type is 10 or 11)
200
C47
Control output 2 range
Same as control output 1
1
C48
Control output 2 type
Same as control output 1
3
C49
Control output 2 scaling low limit Same as control output 1
0
C50
Control output 2 scaling high limit Same as control output 1
1000
C5
1
Control output 2 MV scalable bandwidth Same as control output 1
200
C52
Auxiliary output range
Same as control output 1
1
C53
Auxiliary output type
Same as control output 1
3
C54
Auxiliary output scaling low limit Same as control output 1
0
C55
Auxiliary output scaling high limit Same as control output 1
1000
C56
Auxiliary output MV scalable bandwidth Same as control output 1
200
Position pr
opor
tional
C57
Position proportional type
0: MFB c Estimated position control
1: MFB control
2: Estimated position control (MFB disabled)
3: Estimated position control (MFB disabled)
+ Position adjustment at power ON.
0
C58
Position proportional dead zone 0.5 to 25.0%
10.0
C59
Motor long life mode
0: Aiming at controllability
1: Aiming at service life of potentiometer
1
C60
Motor adjust
0: Stop 1: Start
0
C6
1
Input with motor fully closed 0 to 9999
1000
C62
Input with motor fully open
0 to 9999
3000
C63
Motor full close-full open time 5.0 to 240.0s
30.0
Communica
tion
C64
Communication type
0: CPL 1: Modbus (ASCII format) 2: Modbus (RTU format)
0
C65
Station address
0 to 127 (Communication is disabled when set at "0".)
0
C66
Transmission speed (bps)
0: 4800 1: 9600 2: 19200 3: 38400
2
C67
Data format (Data length)
0: 7 bits 1: 8 bits
1
C68
Data format (Parity)
0: Even parity 1: Odd parity 2: No parity
0
C69
Data format (Stop bit)
0: 1 bit 1: 2 bits
0
C70
Communication minimum response time 1 to 250ms
3
Key oper
ation • displa
y
C7
1
Key operation type
0: Standard type 1: Special type
0
C72
[mode] key function
0: Invalid 1: AUTO/MANUAL selection
2: RUN/READY selection 3: AT Stop/Start
4: LSP group selection 5: Release all DO latches
6: LSP/RSP selection
7: Communication DI1 selection 8: Invalid
1
C73
MODE display setup
(Sum of the weighting)
Bit 0: AUTO/MANUAL display (Enabled: +1)
Bit 1: RUN/READY display (Enabled: +2)
Bit 2: LSP/RSP display (Enabled: +4)
Bit 3: AT Stop/Start display (Enabled: +8)
Bit 4: Release all DO latches display (Enabled: +16)
Bit 5: Communication DI1 ON/OFF display (Enabled: +32)
Other invalid setting, 0, +64, +128
255
C74
PV/SP display setup
(Sum of the weighting)
Bit 0: PV display (Enabled: +1)
Bit 1: SP display (Enabled: +2)
Bit 2: LSP group number display (Enabled: +4)
Other invalid setting, 0, +8
15
List of parameters