Azbil C35 Скачать руководство пользователя страница 6

6

List of operation displays

Display

Upper display: PV

Lower display: SP

Item

Contents

Initial 

value

Setting 

value

PV

SP

SP (Target value)

SP low limit to SP high limit

0

LSP

 

1

 (Display example)

LSP

LSP No.

(1st digit: Value at the right end digit)

1 to LSP system group (Max. 8)

1

St

 

1-

 (Display example)

Step No.

Step remaining time

Step operation remaining time 

Setting is disabled. 

The step No. distinguishes up ramp, down ramp, 

and soak.

PV

MV

MV (Manipulated Variable)

-10.0 to +110.0%   Setting is enabled in MANUAL 

mode (Numeric value flashed)

HEAt

Numeric value

Heat MV (Manipulated Variable)

Setting is disabled.

-10.0 to +110.0%

COOL

Numeric value

Cool MV (Manipulated Variable)

fb

Numeric value 

MFB (Motor opening feedback 

value) 

Setting is disabled.  +10.0 to +110.0%

Flashing when the value is 0.0 to 100.0% during estimate.

PV

At

 

1

 (Display example)

AT progress display (1st digit= 

Numeric value at right end digit)

Setting is disabled.

Ct

 

1

Numeric value

CT current value 1

Setting is disabled.

Ct2

Numeric value

CT current value 2

Setting is disabled.

E

 

1

Numeric value

Internal Event 1 main setting

-1999 to +9999U or 0 to 9999U

0

E

 

1.Sb

Numeric value

Internal Event 1 sub setting

0

t

 

1.--

(Display example)

Numeric value

Timer remaining time 1

Setting is disabled.

Upper display: The distinction by ON delay or 

OFF delay is displayed at the side location of “t1.”. 

E2

Numeric value

Internal Event 2 main setting

Same as Internal Event 1 main setting

0

E2.Sb

Numeric value

Internal Event 2 sub setting

Same as Internal Event 1 sub setting

0

t2.--

(Display example)

Numeric value

Timer remaining time 2

Same as Timer remaining time 1

E3

Numeric value

Internal Event 3 main setting

Same as Internal Event 1 main setting

0

E3.Sb

Numeric value

Internal Event 3 sub setting

Same as Internal Event 1 sub setting

0

t3.--

(Display example)

Numeric value

Timer remaining time 3

Same as Timer remaining time 1

List of parameter setting displays

MOdE

  [Mode bank]

Display

Item

Contents

Initial value Setting value

A--M

AUTO/MANUAL

AUTO

: AUTO mode   

MAN

: MANUAL mode

AUTO

r--r

RUN/READY

RUN

: RUN mode   

RDY

: READY mode

RUN

l--r

LSP/RSP 

lSp

: LSP   

RSp

: RSP

LSP

At

AT stop/start

At.OF

: AT stop   

At.ON

: AT start

AT stop

dO.Lt

Release all DO latches

Lt.ON

: Latch continue   

Lt.OF

: Latch release

Latch continue

C.dI

 

1

Communication DI1

dI

 

.OF

: OFF   

dI

 

.On

: ON

OFF

SP

 

[SP bank]

Display

Item

Contents

Initial value Setting value

RSP

RSP 

Setting is disabled. 

PIDr

PID group No. (RSP) 

1 to 8 

1

SP-

 

1

 to 

SP-8

SP (for LSP 1 to 8) 

SP low limit to SP high limit 

0

Pid.

 

1

 to 

Pid.8

 

PID group No. (for LSP 1 to 8)  1 to 8  

1

rMP.

 

1

 to 

rMP.8

Ramp (for LSP1 to 8) 

0 to 9999

0

tIM.

 

1

 to 

tI

 

M.8

Time (for LSP to 8) 

0.0 to 999.9 or 0 to 9999

0

Ev

 

[Event bank]

Display

Item

Contents

Initial value Setting value

E

 

1

 to 

E8

Internal Event 1 to 8 main setting -1999 to +9999 or 0 to 9999 *

0

E

 

1.Sb

 to 

E8.Sb

Internal Event 1 to 8 sub setting

0

E

 

1.Hy

 to 

E8.Hy

Internal Event 1 to 8 hysteresis 0 to 9999 *

5

E

 

1.On

 to 

E8.On

Internal Event 1 to 8 ON delay time 0.0 to 999.9 or 0 to 9999

0

E

 

1.OF

 to 

E8.OF

Internal Event 1 to 8 OFF delay time

0

* The decimal point position varies by meeting the internal event operation type.

PI

 

D

 

[PID bank]

Display

Item

Contents

Initial value Setting value

P-

 

1

 to 

P-8

Proportional band (PID1 to 8 group) 0.1 to 999.9%

5.0

I

 

-

 

1

 to 

I

 

-8

Integration time (PID1 to 8 group) 0 to 9999s or 0.0 to 999.9s  

(No integration control action when set at "0")

120

d-

 

1

 to 

d-8

Derivative time (PID1 to 8 group) 0 to 9999s or 0.0 to 999.9s  

(No derivative control action when set at "0")

30

rE-

 

1

 to 

rE-8

Manual reset (PID1 to 8 group)

-10.0 to +110.0%

50.0

OL-

 

1

 to 

OL-8

MV low limit (PID1 to 8 group)

-10.0 to +110.0%

0.0

OH-

 

1

 to 

OH-8

MV high limit (PID1 to 8 group)

-10.0 to +110.0%

100.0

P-

 

1C

 to 

P-8C

Cool-side proportional band 

(PID1 to 8 group)

0.1 to 999.9%

5.0

I

 

-

 

1C

 to 

I

 

-8C

Cool-side Integration time (PID1 

to 8 group)

0 to 9999s or 0.0 to 999.9s  

(No integration control action when set at "0")

120

d-

 

1C

 to 

d-8C

Cool-side derivative time (PID1 

to 8 group)

0 to 9999s or 0.0 to 999.9s  

(No derivative control action when set at "0")

30

OL.

 

1C

 to 

OL.8C

Cool-side MV low limit (PID1 to 8 group) -10.0 to +110.0%

0.0

OH.

 

1C

 to 

OH.8C

Cool-side MV high limit (PID1 to 8 group) -10.0 to +110.0%

100.0

PARA

  [Parameter bank]

Display

Item

Contents

Initial value Setting value

Con

tr

ol

CtrL

Control method

0: ON/OFF control  1: Fixed PID

0 or 1

At.

 

OL

MV low limit at AT

-10.0 to +110.0%

0.0

At.

 

OH

MV high limit at AT

-10.0 to +110.0%

100.0

dI

 

FF

ON/OFF control differential

0 to 9999U

5

OFFS

ON/OFF control operating point offset -1999 to +9999U

0

PV

FL

PV filter

0.0 to 120.0s

0.0

rA

PV ratio

0.001 to 9.999

1.000

bI

PV bias

-1999 to +9999U

0

fl2

RSP filter

0.0 to 120.0s 

0.0

ra2

RSP ratio 

0.001 to 9.999 

1.000

bI2

RSP bias

-1999 to +9999U

0

Time pr

opor

tional output

CyU

Time proportional cycle unit 1 0 to 3 *

1

0

Cy

Time proportional cycle 1

5 to 120s or 1 to 120s *

2

10 or 2

CyU2

Time proportional cycle unit 2 0 to 3 *

1

0

Cy2

Time proportional cycle 2

5 to 120s or 1 to 120s *

2

10 or 2

tP.

 

ty

Time proportional cycle mode 0: Controllability aiming type

1: Operation end service life aiming type (Only ON/ 

OFF operation within Time proportional cycle)

0 or 1

MV

outl

MV variation limit

0.0 to 999.9%(No limit when set at "0.0U") 

0.0

SP

SPU

SP up ramp (U/min)

0.0 to 999.9U(No ramp when set at "0.0U")

0.0

SPd

SP down ramp (U/min)

0.0

*1  0: Unit of "1s"   1: Fixed at 0.5s   2: Fixed at 0.2s   3: Fixed at 0.1s 

*2  5 to 120s when output includes the relay output

U: Unit Maximum unit of Industrial volume in 

PV range (°C, Pa,L/min, etc.)

: Essential parameters for PV measurement and control
: Basic parameters
: Required parameters when using optional functions

Et

 

[Extended tuning bank]

Display

Item

Contents

Initial value Setting value

At.ty

AT type

0: Normal   1: Immediate response   2: Stable *

1

0

JF.bd

Just-FiTTER setting band

0.00 to 10.00

0.30

SP.LG

SP lag constant

0.0 to 999.9

0.0

At-P

AT Proportional Band adjust

0.00 to 99.99

1.00

At-I

AT Integral time adjust

0.00 to 99.99

1.00

At-d

AT Derivative time adjust

0.00 to 99.99

1.00

Ctr.A

Control algorithm

0: PID(Conventional PID)   1: Ra-PID(High-performance PID)

0

JF.Ov

Just-FiTTER assistance coefficient 0 to 100

0

*1   Normal = Standard control characteristics, Immediate response = Control characteristics that respond immediately to 

external disturbance, Stable = Control characteristics having less up/down fluctuation of PV

ZOne

  [Zone bank]

Display

Item

Contents

Initial value Setting value

ZO-

 

1

 to 

ZO-7

Zone 1 to 7

-1999 to +9999U

9999U

ZOdf

Zone hysteresis

0 to 9999 5U

5U

List of setup setting displays

StUP

  [Setup bank]

Display

Item

Contents

Initial value Setting value

A

nalog input

C0

 

1

PV input range type

For details, refer to the PV Input Range Table

88

C02

Temperature unit

0: Celsius (°C)   1: Fahrenheit (°F)

0

C03

Cold junction compensation

0: Performed (internal)   1: Not performed (external)

0

C04

Decimal point position

0: No decimal point 

1 to 3: 1 to 3 digits below decimal point

0

C05

PV range low limit

When the PV input type is DC voltage/DC current,  

-1999 to +9999U

0

C06

PV range high limit

1000

C07

SP low limit

PV input range low limit to PV input range high  

limit

0

C08

SP high limit

1000

C09

PV square root extraction dropout 0.0 to 100.0% (PV square root extraction is not 

performed when set at "0.0".)

0.0

C

 

10

RSP input range type

0: 4 to 20mA   1: 0 to 20mA   2: 0 to 5V 

3: 1 to 5V   4: 0 to 10V

0

C

 

1

 

1

RSP range low limit

-1999 to +9999U

0

C

 

12

RSP range high limit

1000

Con

tr

ol ac

tion

C

 

13

PID calculation adjustment function *

1

0: Enabled   1: Disabled

0

C

 

14

Control action (Direct/Reverse) 0: Heat control (Reverse action)   1: Cool control (Direct action)

0

C

 

15

Output operation at PV alarm 0: Control calculation is continued.    

1: Output at PV alarm is output.

0

C

 

16

Output at PV alarm

-10.0 to +110.0%

0.0

C

 

17

Output at READY (Heat)

-10.0 to +110.0%

0.0

C

 

18

Output at READY (Cool)

-10.0 to +110.0%

0.0

C

 

19

Output operation at changing AUTO/MANUAL 0: Bumpless transfer   1: Preset

0

C20

Preset MANUAL value

-10.0 to +110.0%

0.0 or 50.0

C2

 

1

Initial output type (mode) of PID control 0: Auto   1: Not initialized   2: Initialized

0

C22

Initial output of PID control

-10.0 to +110.0%

0.0 or 50.0

C23

PID decimal point position (decimal  

point of integral time and delivative time)

0: No decimal point 

1: 1 digit after decimal point

0

C24

Zone PID operation

0: Disabled   1: Changed by SP   2: Changed by PV

0

C26

Heat/Cool control

0: Not used   1: Used

0

C27

Heat/Cool

0: Normal   1: Energy saving

0

C28

Heat/Cool control dead zone -100.0 to +100.0%

0.0

C29

Heat/Cool change point

-10.0 to +110.0%

50.0

SP

C30

LSP system group

1 to 8

1

C3

 

1

SP ramp type

0: Standard   1: Multi-ram    

2:  Step operation When the power is turned ON 

again, the step operation is stopped (READY)

3:  Step operation When the power is turned ON 

again, the step operation is reset

0

C32

SP ramp unit

0: 0.1U/s   1: 0.1U/min   2: 0.1U/h

1

C33

STEP time unit

0: 0.1s   1: 1s 2: 1min

0

C34

STEP PV start

0: Disabled   1: Enabled

0

C35

STEP loop

0: Stop   1: Loop   2: Final step continued

0

C36

CT1 operation type

0: Heater burnout detection   1: Current value measurement

0

C37

CT1 output

0 to 1: Control output 1 to 2, 2 to 4: Event output 1 to 3

0

C38

CT1 measurement wait time

30 to 300ms

30

C39

CT2 operation type

Same as CT1

0

C40

CT2 output

Same as CT1

0

C4

 

1

CT2 measurement wait time

Same as CT1

30

Con

tinuous output

C42

Control output 1 range

Current output   1: 4 to 20mA   2: 0 to 20mA 

Continuous voltage output   1: 1 to 5 V  2: 0 to 5 V  3: 0 to 10 V

1

C43

Control output 1 type

0: MV 1: Heat MV   2: Cool MV   3: PV 

4: PV before ratio, bias, and filter   5: SP   6: Deviation 

7: CT1 current value   8: CT2 current value 

9: MFB (Including estimation MFB)   10: SP+MV   11: PV+MV

0

C44

Control output 1 scaling low limit -1999 to +9999U

0.0

C45

Control output 1 scaling high limit

100.0

C46

Control output 1 MV scalable bandwidth 0 to 9999 (Valid when control output 1 type is 10 or 11)

200

C47

Control output 2 range

Same as control output 1

1

C48

Control output 2 type

Same as control output 1

3

C49

Control output 2 scaling low limit Same as control output 1

0

C50

Control output 2 scaling high limit Same as control output 1

1000

C5

 

1

Control output 2 MV scalable  bandwidth Same as control output 1

200

C52

Auxiliary output range

Same as control output 1

1

C53

Auxiliary output type

Same as control output 1

3

C54

Auxiliary output scaling low limit Same as control output 1

0

C55

Auxiliary output scaling high limit Same as control output 1

1000

C56

Auxiliary output MV scalable bandwidth  Same as control output 1

200

Position pr

opor

tional

C57

Position proportional type

0: MFB c Estimated position control  

1: MFB control 

2: Estimated position control (MFB disabled) 

3: Estimated position control (MFB disabled) 

+ Position adjustment at power ON.

0

C58

Position proportional dead zone 0.5 to 25.0%

10.0

C59

Motor long life mode

0: Aiming at controllability    

1: Aiming at service life of potentiometer

1

C60

Motor adjust

0: Stop 1: Start

0

C6

 

1

Input with motor fully closed 0 to 9999

1000

C62

Input with motor fully open

0 to 9999

3000

C63

Motor full close-full open time 5.0 to 240.0s

30.0

Communica

tion

C64

Communication type

0: CPL   1: Modbus (ASCII format)   2: Modbus (RTU format)

0

C65

Station address

0 to 127 (Communication is disabled when set at "0".)

0

C66

Transmission speed (bps)

0: 4800   1: 9600   2: 19200 3: 38400

2

C67

Data format (Data length)

0: 7 bits   1: 8 bits

1

C68

Data format (Parity)

0: Even parity   1: Odd parity   2: No parity

0

C69

Data format (Stop bit)

0: 1 bit   1: 2 bits

0

C70

Communication minimum response time 1 to 250ms

3

Key oper

ation • displa

y

C7

 

1

Key operation type

0: Standard type   1: Special type

0

C72

[mode] key function

0: Invalid   1: AUTO/MANUAL selection    

2: RUN/READY selection   3: AT Stop/Start 

4: LSP group selection   5: Release all DO latches 

6: LSP/RSP selection    

7: Communication DI1 selection   8: Invalid

1

C73

MODE display setup 

(Sum of the weighting)

Bit 0: AUTO/MANUAL display (Enabled: +1) 

Bit 1: RUN/READY display (Enabled: +2) 

Bit 2: LSP/RSP display (Enabled: +4) 

Bit 3: AT Stop/Start display (Enabled: +8) 

Bit 4: Release all DO latches display (Enabled: +16) 

Bit 5: Communication DI1 ON/OFF display (Enabled: +32) 

Other invalid setting, 0, +64, +128

255

C74

PV/SP display setup 

(Sum of the weighting)

Bit 0: PV display (Enabled: +1) 

Bit 1: SP display (Enabled: +2) 

Bit 2: LSP group number display (Enabled: +4) 

Other invalid setting, 0, +8

15

List of parameters

Содержание C35

Страница 1: ...en left and right it performs MV graph DI monitor internal event monitor and other display functions Mode indicators man Lights when MANUAL AUTO mode if not lit rsp Lights when RSP LSP mode if not lit ev1 ev2 ev3 Lights when event relays are ON ot1 ot2 Lights when the control output is ON always lit when the current output is used mode key When this key is pressed and held for more than 1 second i...

Страница 2: ... No Step remaining time PV value MV value Timer remaining time 3 Internal event 3 delay time Internal event 3 sub setting Setting value Internal event 3 main setting Setting value SP Event PID Parameter Extendedtuning 2 second press hold of para key display key 3 Mode 2 second press hold of para key para key or key enter key key While AUtO is flashing enter key While MAn is flashing enter key to 1...

Страница 3: ...b setting Setting value Internal event 2 main setting Setting value Timer remaining time 1 Internal event 1 delay time Internal event 1 sub setting Setting value Internal event 1 main setting Setting value Coolmanipulated variable MV value MFB MFB value Setup Lock key enter key Instrumentinformation 2 second press hold of para key Event configuration DIassignment DO assignment User function para k...

Страница 4: ...ulate PID values Check that this operation does not create any problems for the as sociated equipment before executing AT 1 Press display once to get the operation display 2 Press and hold para for more than 2s to get the parameter setup display MOde flashes on the upper display 3 Press enter or to get A M on the upper display and autO on the lower display If the control method is ON OFF control a...

Страница 5: ... Press or to get 1 Press enter and auto adjustment starts 6 CA CL is displayed on the upper display and open contact is ON The lower display shows the MFB count value and when count is stable CA OP is dis played on the upper diplay and closed con tact is ON When the count value is stable auto adjust completes to get op eration display After starting auto adjust press display key to stop auto adjus...

Страница 6: ...D Conventional PID 1 Ra PID High performance PID 0 JF Ov Just FiTTER assistance coefficient 0 to 100 0 1 Normal Standard control characteristics Immediate response Control characteristics that respond immediately to external disturbance Stable Control characteristics having less up down fluctuation of PV ZOne Zone bank Display Item Contents Initial value Settingvalue ZO 1 to ZO 7 Zone 1 to 7 1999 ...

Страница 7: ...ication DI1 to 4 22 MANUAL 23 READY 24 RSP 25 AT running 26 During SP ramp 27 Undefined 28 Alarm occurs 29 PV alarm occurs 30 Undefined 31 mode key pressing status 32 Event output 1 status 33 Control output 1 status 2 to 5 or 0 dI 1 4 to dI 5 4 Internal contact 1 to 5 Input assignment B 0 dI 1 5 to dI 5 5 Internal contact 1 to 5 Input assignment C 0 dI 1 6 to dI 5 6 Internal contact 1 to 5 Input a...

Страница 8: ... or 2 or both A current exceeding the upper limit of the display range was measured The number of CT turns or the number of CT power wire loops is incorrectly set or wiring is incorrect Use a CT with the cor rect number of turns for the display range Reset the number of CT turns Reset the number of CT power wire loops Check the wiring Unit failure AL70 A D conversion failure A D converter is fault...