Azbil C35 Скачать руководство пользователя страница 4

4

Setup of 

PV input range type

1

Press [display] once 
to get the operation 
display.

If the sensor has not been 
wired or is disconnected, 
an alarm for abnormal PV 
input (any one from 

AL0

 

1

 

to 

AL

 

1

 

1

)  may appear on 

the upper display.

2

Press and hold [para] 
for more than 2s to get 
the parameter setup 
display. 

MOde

 flashes on the 

upper display.

3

Press [ ] or [ ] repeat-
edly, and 

Stup

 flashes 

on the upper display.

4

Press [enter]. 
The current set value  
for 

C0

 

1

 (PV input 

range type) is 
displayed.

5

Press [enter]. 
The rightmost digit on the lower display flashes and its value 
can be changed. 
Press [<], [ ] or [ ] to change to the desired sensor type in the 
PV input range list. 
Then press [enter] to finalize your selection. 
If the number is flashing, the [enter] key has not yet been 
pressed, and the setting has not yet been saved.

Setup of 

event operation type

In this example, the event 1 operation type is set to deviation high 
limit.

1

Press [display] once 
to get the operation 
display.

2

Press and hold [para] 
for more than 2s to get 
the parameter setup 
display. 

MOde

 flashes on the 

upper display.

3

Press [ ] or [ ] repeat-
edly to get 

evCf

 

flashing on the upper 
display.

4

Press [enter] to get 

e

 

1.c

 

1

 on the upper 

display and 

0

 is dis-

played on the lower 
display.

0

 on the lower display indi-

cates that the event opera-
tion type is set to "none."

5

When [enter] is 
pressed, the rightmost 
digit on the lower dis-
play flashes. 
Press [ ] or [ ] to get 

4

 

flashing on the display.

4

 on the lower display 

indicates that the event 
operation type is set for 
deviation high limit.

6

Press [enter], and the 
displayed value 

4

 

on the lower display 
changes from flashing 
to continuously lit and 
the displayed value 
is set.

Similarly, use 

e2.C

 

1

 to set the event 2 operation type, and use 

e3.C

 

1

 for event 3.

Red

 letters

: Items before operation

Blue

 letters : Items during operation

Execution of 

auto tuning (AT)

AT forces ON/OFF of the MV a number of times (a limit cycle) to cal-
culate PID values. 
Check that this operation does not create any problems for the as-
sociated equipment before executing AT.

1

Press [display] once 
to get the operation 
display.

2

Press and hold [para] 
for more than 2s to get 
the parameter setup 
display. 

MOde

 flashes on the 

upper display.

3

Press [enter] or [<] 
to get 

A--M

 on the 

upper display and 

autO

 on the lower 

display.

If the control method is 
ON/OFF control and if Bit 
3 (AT stop/start display) of 
the mode display setting 
(

C73

) is set to "disabled: 0," 

nothing is displayed.

4

Press [ ] as needed 
until 

At

 and 

at.Of

 

appear on the upper 
and lower displays 
respectively.

5

When [enter] is 
pressed, 

at.Of

 flashes 

on the lower display.

The display flashes only 
in RUN and AUTO modes, 
and only if there is no PV 
problem. 
Also, if DI is set to "AT stop/
start", the display does not 
flash and the setting can-
not be changed.

6

Press [ ] or [ ] once, 
and 

at.Of

 flashes on 

the lower display.

7

If [enter] is pressed, 

at.ON

 remains steadily lit and AT begins. 

During AT, the rightmost decimal point flashes twice repeat-
edly. 
When AT is done, the light goes off and the new PID values 
go into effect.

During the AT process, if the mode is changed to READY or MANUAL, if PV 
input is faulty, or if a power failure occurs, AT stops automatically without 
changing the PID values. 
AT can also be stopped by changing the setting from 

At.ON

 to 

At.OF

 (return 

to step 4 above).

Setup of 

SP value

1

Press [display] re-
peatedly so that the 
orange SP indicator 
lights up on the lower 
display. 
The operation display 
now shows the SP.

2

If [enter] is pressed, 
the rightmost digit 
on the lower display 
flashes and numerical 
value can be changed.

3

Press [<], [ ] or [ ] to 
change to the desired 
SP value. 
The flashing of the 
number indicates that 
the setting has not yet 
been finalized.

If an SP limit is in effect, the 
numerical value cannot be 
changed to a value above 
the limit. The SP limit must 
be changed first.

4

If [enter] is pressed, 
the displayed value 
is set and the display 
changes from flashing 
to continuously lit.

If the [display] key is 
pressed without pressing 
[enter] key, the status re-
turns to that of step 1.

Operation examples

Содержание C35

Страница 1: ...en left and right it performs MV graph DI monitor internal event monitor and other display functions Mode indicators man Lights when MANUAL AUTO mode if not lit rsp Lights when RSP LSP mode if not lit ev1 ev2 ev3 Lights when event relays are ON ot1 ot2 Lights when the control output is ON always lit when the current output is used mode key When this key is pressed and held for more than 1 second i...

Страница 2: ... No Step remaining time PV value MV value Timer remaining time 3 Internal event 3 delay time Internal event 3 sub setting Setting value Internal event 3 main setting Setting value SP Event PID Parameter Extendedtuning 2 second press hold of para key display key 3 Mode 2 second press hold of para key para key or key enter key key While AUtO is flashing enter key While MAn is flashing enter key to 1...

Страница 3: ...b setting Setting value Internal event 2 main setting Setting value Timer remaining time 1 Internal event 1 delay time Internal event 1 sub setting Setting value Internal event 1 main setting Setting value Coolmanipulated variable MV value MFB MFB value Setup Lock key enter key Instrumentinformation 2 second press hold of para key Event configuration DIassignment DO assignment User function para k...

Страница 4: ...ulate PID values Check that this operation does not create any problems for the as sociated equipment before executing AT 1 Press display once to get the operation display 2 Press and hold para for more than 2s to get the parameter setup display MOde flashes on the upper display 3 Press enter or to get A M on the upper display and autO on the lower display If the control method is ON OFF control a...

Страница 5: ... Press or to get 1 Press enter and auto adjustment starts 6 CA CL is displayed on the upper display and open contact is ON The lower display shows the MFB count value and when count is stable CA OP is dis played on the upper diplay and closed con tact is ON When the count value is stable auto adjust completes to get op eration display After starting auto adjust press display key to stop auto adjus...

Страница 6: ...D Conventional PID 1 Ra PID High performance PID 0 JF Ov Just FiTTER assistance coefficient 0 to 100 0 1 Normal Standard control characteristics Immediate response Control characteristics that respond immediately to external disturbance Stable Control characteristics having less up down fluctuation of PV ZOne Zone bank Display Item Contents Initial value Settingvalue ZO 1 to ZO 7 Zone 1 to 7 1999 ...

Страница 7: ...ication DI1 to 4 22 MANUAL 23 READY 24 RSP 25 AT running 26 During SP ramp 27 Undefined 28 Alarm occurs 29 PV alarm occurs 30 Undefined 31 mode key pressing status 32 Event output 1 status 33 Control output 1 status 2 to 5 or 0 dI 1 4 to dI 5 4 Internal contact 1 to 5 Input assignment B 0 dI 1 5 to dI 5 5 Internal contact 1 to 5 Input assignment C 0 dI 1 6 to dI 5 6 Internal contact 1 to 5 Input a...

Страница 8: ... or 2 or both A current exceeding the upper limit of the display range was measured The number of CT turns or the number of CT power wire loops is incorrectly set or wiring is incorrect Use a CT with the cor rect number of turns for the display range Reset the number of CT turns Reset the number of CT power wire loops Check the wiring Unit failure AL70 A D conversion failure A D converter is fault...

Отзывы: