Azbil ACTIVAL FVY5130J Скачать руководство пользователя страница 8

AB-7042 

(2/2) 

Item Specification 

Valve sensor 

Pressure 
measuring 

Measuring  range  0 MPa to 1.0 MPa*

3

 

Accuracy of  
the displayed  
pressure 

 0.5 %FS (factory preset) *

4

 

Temperature  
measuring 

Measuring range  0 

C to 80 

Accuracy 

 1.0 

C (factory preset) in the 0 

C to 80 

C measuring range*

5

 

(within 0 

C to 80 

C measuring range, at -25 

C to 40 

C temperature difference between measuring 

temperature and ambient temperature) 

Pt100 input

  Temperature 

measuring 

Accuracy*

6

 Conversion 

accuracy: 

 0.4 

C (at 0 

C to 50 

C ambient temperature) 

 

 

 0.6 

C (at -20 

C to 0 

C ambient temperature) 

Error due to wiring length: 

 0.15 

C (15 

 15 m) 

in the 0 to 80 

C measuring range 

Energy 
calculation*

7

 

(with two 
temperature 
sensors (Pt100 
input) connected) 

Accuracy 

Temperature 

difference b/w 

supply and 

return water 

Flow rate measuring accuracy*

8

 

 5 %RD 

 7 %RD 

 10 %RD 

 1 %FS 

 3 %FS 

T = 5 

 25 %RD 

 27 %RD 

 29 %RD 

 21 %FS 

 23 %FS 

T = 10 

 15 %RD 

 17 %RD 

 20 %RD 

 11 %FS 

 13 %FS 

T = 15 

 12 %RD 

 14 %RD 

 17 %RD 

 8 %FS 

 10 %FS 

Notes: 

3  When you test the withstand pressure of the valve sensor manufactured on and after Nov. 1, 2011 (date code: 1144 or greater), up to  

1.6 MPa pressure can be applied to the valve sensor. 

4  Accuracy of the displayed pressure was calibrated with the conditions, temperature of fluid: 7 °C to 65 °C, barometric pressure: 99 kPa. 

If the actual conditions are out of the estimated ones, the accuracy may degrade. 
(This specification is applied for the products manufactured on Dec. 1, 2016 or later (date code: 1648).) 

5  For accurate measuring of flow temperature, thermal insulation is required. Refer to the subsection 

Heat insulation

 for applying thermal 

insulation.

 

6  Overall accuracy is calculated based on the sensing accuracy of the temperature sensors connected, the conversion accuracy, and the 

error due to wiring length. 

7  Energy calculation accuracy is calculated from the flow rate measuring accuracy at 1 

C measuring error of the temperature difference. 

8  The flow rate measuring accuracy in the table corresponds to the data shown in the above flow rate measuring accuracy graph. 

 

 

Data in Model FVY5130J/FVY5140J/FVY5150J 

Data type 

Description 

Flow data 

Following items are displayed on Display Panel (Model QY5010S1000): 
Actual flow, supply water temperature, return water temperature, valve inlet pressure, valve outlet pressure, 
actual flow (% in bar graph), actual valve position (% in bar graph) 

 

Following items are output in analog signal using RS-485/analog output signal converter (Model 
RYY792C3001): 
Control setting value, actual valve position, actual flow, set flow, supply water temperature, return water 
temperature, valve inlet pressure, valve outlet pressure, instantaneous energy 

 

Following items are retrieved via RS-485 communication (Modbus protocol): 
Control setting value, actual valve position, actual flow, set flow, supply water temperature, return water 
temperature, valve inlet pressure, valve outlet pressure, instantaneous energy, totalized flow, totalized 
energy, cool/heat status, point status*

1

 

Device data 

Following items are retrieved via RS-485 communication (Modbus protocol): 
Model number, date of manufacture, version of hardware, version of software, serial number, power-ON time, 
operating time, operating level, number of operations, number of reverse, range, device status*

2

 

Notes: 

1  Point status indicates an error of analog data. Refer to 

AB-7044 Instruction Manual of A

 Standalone Model

 for details. 

2  Device status indicates the status of this product. Refer to 

AB-7044 Instruction Manual of A

 Standalone Model

 for details. 

 

Содержание ACTIVAL FVY5130J

Страница 1: ...ol in combination with a DDC controller Flow data stored in the Model FVY5130J FVY5140J FVY5150J is retrieved via RS 485 communication Modbus protocol The retrieved flow data is effective for energy s...

Страница 2: ...valve body and cause leakage When piping this product be sure there is no foreign matter in the pipes If foreign matter remains in the pipes the product may break down CAUTION 2 2 Install wire and us...

Страница 3: ...inside the valve Rust or foreign object inside the valve lowers flow rate measuring accuracy Thermally insulate the valve and do not allow the process fluid to freeze Frozen process fluid around the...

Страница 4: ...Insertion type pipe temperature sensor Model TY783 For the specifications of the insertion type pipe temperature sensor refer to AB 5429 Specifications Instructions of Pipe Temperature Sensor Outdoor...

Страница 5: ...s FVY5130J0011 FVY5140J0011 FVY5150J0011 DN15 1 2 1 0 1 0 MPa FVY5130J0012 FVY5140J0012 FVY5150J0012 DN15 1 2 2 5 1 0 MPa FVY5130J0013 FVY5140J0013 FVY5150J0013 DN15 1 2 6 0 1 0 MPa FVY5130J0021 FVY51...

Страница 6: ...ication 6 pin 3 pin 2 connector Display Panel 4 pin connector Operation status indicator LED 1 red LED Status LED indication Normal Repetition of 1 second ON 1 second OFF Major alarm Continuous ON Min...

Страница 7: ...0 l min FVY5130J0061 FVY5140J0061 FVY5150J0061 DN65 2 1 2 95 950 l min FVY5130J0081 FVY5140J0081 FVY5150J0081 DN80 3 125 1250 l min Measuring accuracy Factory preset Notes 1 The flow measurement accur...

Страница 8: ...sensing accuracy of the temperature sensors connected the conversion accuracy and the error due to wiring length 7 Energy calculation accuracy is calculated from the flow rate measuring accuracy at 1...

Страница 9: ...f the product relay terminal block wiring and the relay terminal block load device in connection 2 JCS Japanese Electric Wire and Cable Makes Association 3 KPEV Wire standard provided by Furukawa Elec...

Страница 10: ...nal cover O ring Gland packing Stem Spring Seat ring Heat insulation Connector for Pt100 input Row T1 Supply water temperature Row T2 Return water temperature Reset switch Connector for Display Panel...

Страница 11: ...o remove foreign substances Provide a strainer on the inflow side of the valve For chilled hot water 40 or more meshes If the strainer cannot be installed just before the inlet of each valve install i...

Страница 12: ...or faces downward Flow direction Flow direction Flow direction Figure 5 Incorrect mounting orientations Piping CAUTION When installing this product hold it in the proper position and securely fasten i...

Страница 13: ...oduct Heat insulating Apply heat insulation as illustrated by in Fig 6 If the yoke and or the actuator are covered with insulation material the point cannot be checked or may be distorted If the heat...

Страница 14: ...ve the actuator may break down Do not manually open or close the valve more than 100 or less than 0 scale 1 Turn off the power 2 Hold the joint using a wrench etc gently turn the wrench to the desired...

Страница 15: ...ke proper contact Use crimp terminals with insulation for connections to the product terminals Failure to do so may cause short circuit leading to fire or device failure Tighten the terminal screws wi...

Страница 16: ...Pt100 input Terminal Wire color Description Temperature sensor for pipe surface Insertion type pipe temperature sensor T1A Red Red Pt100 A supply water temperature T1B White Black Pt100 B supply water...

Страница 17: ...e recommended cable 1 Pass the 4 core cable of Display Panel through the actuator port for Display Panel See Fig 3 for the location of the port 2 Strip the wire sheath Strip length is 8 mm See Fig 15...

Страница 18: ...iring port to share the wiring port with signal lines Connect the wires of RS 485 communication cable to the unplugged connector from the actuator socket After connecting the wires to the connector pl...

Страница 19: ...0 mA input type products See Figs 23 and 24 4 20 mA control signal input is not isolated from the power and the 4 20 mA input impedance is 282 For connecting a controller the relations among the input...

Страница 20: ...Terminals 2 6 and 8 of the product are internally connected 3 Refer to 6 Single transformer with two products in the Precautions for connection section Figure 24 Connection example Two Model FVY5130J...

Страница 21: ...ter Slave Model R series Slave Model FVY51X0J this product 1 2 3 4 5 6 Figure 27 Connection example 3 wire RS 485 communication Model FVY51X0J This product Pulse counter 3 4 V 0 V Figure 29 Connection...

Страница 22: ...erform 1 and 2 to release the other 2 latches 4 Lift and remove the cover from the base Figure 31 Cover removal from the base Attaching the cover to the base Attach the cover to the base and fix them...

Страница 23: ...o the base IMPORTANT Carefully attach the cable gland so that O rings do not fall from the cable gland Without the O rings water proof protection is not assured Figure 35 Attaching the cover to the ba...

Страница 24: ...el Numbers Options For conduit connection use a water proof plica tube or the like Maintenance CAUTION Do not put a load or weight on this product Doing so may damage the product Before doing maintena...

Страница 25: ...nlet pressure equal to outlet pressure No flow across the valve in open position e g when supply pump is OFF or when hand valves on the inflow and or outflow sides of the valve are is fully closed Val...

Страница 26: ...AB 7042 26 This blank page was added for page layout purposes...

Страница 27: ...AB 7042 27 This blank page was added for page layout purposes...

Страница 28: ...251 8522 JAPAN https www azbil com Rev 9 0 Apr 2020 J AI 7042 Rev 4 0 28 ACTIVAL and ACTIVAL are trademarks of Azbil Corporation in Japan or in other countries KPEV is a registered trademark of Furuka...