Azbil ACTIVAL FVY5130J Скачать руководство пользователя страница 2

AB-7042 

Safety Instructions 

Please read instructions carefully and use the product as 
specified in this manual. Be sure to keep this manual 
nearby for quick reference.  

Usage Restrictions 

This product is targeted for general air conditioning. Do not 
use this product in a situation where human life may be 
affected. If this product is used in a clean room or a place 
where reliability or control accuracy is particularly required, 
please contact Azbil Corporation’s sales representative. 
Azbil Corporation will not bear any responsibility for the 
results produced by the operators. 

 

 

Warnings and Cautions 

 WARNING

 

Alerts users that improper handling 
may cause death or serious injury. 

 CAUTION

 

Alerts users that improper handling may 
cause minor injury or material loss. 

 

 

Signs 

 

Alerts users possible hazardous conditions caused 
by erroneous operation or erroneous use. The 
symbol inside 

 indicates the specific type of 

danger.  
(For example, the sign on the left warns of the risk of 
electric shock.) 

 

Notifies users that specific actions are prohibited to 
prevent possible danger. The symbol inside 

 

graphically indicates the prohibited action.  
(For example, the sign on the left notifies that 
disassembly is prohibited.)  

 

Instructs users to carry out a specific obligatory 
action to prevent possible danger. The symbol 
inside 

 graphically indicates the actual action to 

be carried out.   
(For example, the sign on the left indicates general 
instructions.) 

 

 WARNING  

 

When handling or transporting any heavy product 
(more than 18 kg), carefully move the product with 
a hand truck or the like, or with 2 or more people.  
Careless lifting or accidental dropping of the 
product may result in injury or product damage. 

 

 

 CAUTION 

(1/2)

 



Provide a circuit protector (e.g., a fuse or circuit 
breaker) for the power source.  
Failure to do so may cause a short circuit leading to 
fire or device failure. 

 

Do not freeze this product.  
Doing so may damage the valve body and cause 
leakage. 

 

When piping this product, be sure there is no 
foreign matter in the pipes. 
If foreign matter remains in the pipes, the product 
may break down. 

 
 

 

 CAUTION 

(2/2)

 



Install, wire, and use this product under the 
conditions specified by this manual.  
Failure to do so may cause fire or device failure. 

 

Use full face gaskets for flat face flanges.  
Failure to do so may damage the flanges or cause 
leakage outside of the valve. 

 

When installing this product, hold it in the proper 
position and securely fasten it to the pipes. 
Excessive tightening or improper installation 
position may damage the valve. 

 

After installation, make sure no fluid leaks from the 
valve-pipe connections. 
Improper piping may cause fluid leakage outside of 
the valve. 

 

Do not put a load or weight on this product.  
Doing so may damage the product. 

 

Installation and wiring of the actuator must be 
performed by personnel qualified to do 
instrumentation and electrical work.  
Mistakes in installation or wiring may cause fire or 
electric shock. 

 

Before wiring, setting, maintenance, or replacement, 
be sure to turn off the power to this product.  
Failure to do so may result in electric shock or 
device failure. 

 

All wiring must comply with applicable codes and 
ordinances.  
Otherwise there is a danger of fire. 

 

For wiring, strip the insulation from cables as 
specified in this manual.  
If the length of exposed wire is longer than 
specified, it may cause electric shock or short 
circuit between adjacent terminals.  
If it is too short, it may not make proper contact. 

 

Use crimp terminals with insulation for connections 
to the product terminals.  
Failure to do so may cause short circuit leading to 
fire or device failure. 

 

Tighten the terminal screws with the specified 
torque.  
Insufficient tightening of the terminal screws may 
cause fire or overheating. 

 

After wiring, setting, engineering, maintenance, or 
replacement work, be sure to reattach the cover. 
Failure to do so may result in electric shock. 

 

Do not carelessly touch this product when it is used 
to control hot water.  
Doing so may result in burns, because the product 
reaches a high temperature. 

 

Содержание ACTIVAL FVY5130J

Страница 1: ...ol in combination with a DDC controller Flow data stored in the Model FVY5130J FVY5140J FVY5150J is retrieved via RS 485 communication Modbus protocol The retrieved flow data is effective for energy s...

Страница 2: ...valve body and cause leakage When piping this product be sure there is no foreign matter in the pipes If foreign matter remains in the pipes the product may break down CAUTION 2 2 Install wire and us...

Страница 3: ...inside the valve Rust or foreign object inside the valve lowers flow rate measuring accuracy Thermally insulate the valve and do not allow the process fluid to freeze Frozen process fluid around the...

Страница 4: ...Insertion type pipe temperature sensor Model TY783 For the specifications of the insertion type pipe temperature sensor refer to AB 5429 Specifications Instructions of Pipe Temperature Sensor Outdoor...

Страница 5: ...s FVY5130J0011 FVY5140J0011 FVY5150J0011 DN15 1 2 1 0 1 0 MPa FVY5130J0012 FVY5140J0012 FVY5150J0012 DN15 1 2 2 5 1 0 MPa FVY5130J0013 FVY5140J0013 FVY5150J0013 DN15 1 2 6 0 1 0 MPa FVY5130J0021 FVY51...

Страница 6: ...ication 6 pin 3 pin 2 connector Display Panel 4 pin connector Operation status indicator LED 1 red LED Status LED indication Normal Repetition of 1 second ON 1 second OFF Major alarm Continuous ON Min...

Страница 7: ...0 l min FVY5130J0061 FVY5140J0061 FVY5150J0061 DN65 2 1 2 95 950 l min FVY5130J0081 FVY5140J0081 FVY5150J0081 DN80 3 125 1250 l min Measuring accuracy Factory preset Notes 1 The flow measurement accur...

Страница 8: ...sensing accuracy of the temperature sensors connected the conversion accuracy and the error due to wiring length 7 Energy calculation accuracy is calculated from the flow rate measuring accuracy at 1...

Страница 9: ...f the product relay terminal block wiring and the relay terminal block load device in connection 2 JCS Japanese Electric Wire and Cable Makes Association 3 KPEV Wire standard provided by Furukawa Elec...

Страница 10: ...nal cover O ring Gland packing Stem Spring Seat ring Heat insulation Connector for Pt100 input Row T1 Supply water temperature Row T2 Return water temperature Reset switch Connector for Display Panel...

Страница 11: ...o remove foreign substances Provide a strainer on the inflow side of the valve For chilled hot water 40 or more meshes If the strainer cannot be installed just before the inlet of each valve install i...

Страница 12: ...or faces downward Flow direction Flow direction Flow direction Figure 5 Incorrect mounting orientations Piping CAUTION When installing this product hold it in the proper position and securely fasten i...

Страница 13: ...oduct Heat insulating Apply heat insulation as illustrated by in Fig 6 If the yoke and or the actuator are covered with insulation material the point cannot be checked or may be distorted If the heat...

Страница 14: ...ve the actuator may break down Do not manually open or close the valve more than 100 or less than 0 scale 1 Turn off the power 2 Hold the joint using a wrench etc gently turn the wrench to the desired...

Страница 15: ...ke proper contact Use crimp terminals with insulation for connections to the product terminals Failure to do so may cause short circuit leading to fire or device failure Tighten the terminal screws wi...

Страница 16: ...Pt100 input Terminal Wire color Description Temperature sensor for pipe surface Insertion type pipe temperature sensor T1A Red Red Pt100 A supply water temperature T1B White Black Pt100 B supply water...

Страница 17: ...e recommended cable 1 Pass the 4 core cable of Display Panel through the actuator port for Display Panel See Fig 3 for the location of the port 2 Strip the wire sheath Strip length is 8 mm See Fig 15...

Страница 18: ...iring port to share the wiring port with signal lines Connect the wires of RS 485 communication cable to the unplugged connector from the actuator socket After connecting the wires to the connector pl...

Страница 19: ...0 mA input type products See Figs 23 and 24 4 20 mA control signal input is not isolated from the power and the 4 20 mA input impedance is 282 For connecting a controller the relations among the input...

Страница 20: ...Terminals 2 6 and 8 of the product are internally connected 3 Refer to 6 Single transformer with two products in the Precautions for connection section Figure 24 Connection example Two Model FVY5130J...

Страница 21: ...ter Slave Model R series Slave Model FVY51X0J this product 1 2 3 4 5 6 Figure 27 Connection example 3 wire RS 485 communication Model FVY51X0J This product Pulse counter 3 4 V 0 V Figure 29 Connection...

Страница 22: ...erform 1 and 2 to release the other 2 latches 4 Lift and remove the cover from the base Figure 31 Cover removal from the base Attaching the cover to the base Attach the cover to the base and fix them...

Страница 23: ...o the base IMPORTANT Carefully attach the cable gland so that O rings do not fall from the cable gland Without the O rings water proof protection is not assured Figure 35 Attaching the cover to the ba...

Страница 24: ...el Numbers Options For conduit connection use a water proof plica tube or the like Maintenance CAUTION Do not put a load or weight on this product Doing so may damage the product Before doing maintena...

Страница 25: ...nlet pressure equal to outlet pressure No flow across the valve in open position e g when supply pump is OFF or when hand valves on the inflow and or outflow sides of the valve are is fully closed Val...

Страница 26: ...AB 7042 26 This blank page was added for page layout purposes...

Страница 27: ...AB 7042 27 This blank page was added for page layout purposes...

Страница 28: ...251 8522 JAPAN https www azbil com Rev 9 0 Apr 2020 J AI 7042 Rev 4 0 28 ACTIVAL and ACTIVAL are trademarks of Azbil Corporation in Japan or in other countries KPEV is a registered trademark of Furuka...

Отзывы: