Azbil ACTIVAL FVY5130J Скачать руководство пользователя страница 16

AB-7042 

16 

3)  Refer to Figs. 3 and 11 and correctly connect the wires to the M3.5 screw terminals. Note that  the wires of the temperature 

sensor, Display Panel, and RS-485 communication lines are connected to the connectors.

 

 

 

 

 

 

 

 

Figure 11.  Terminals arrangement 

 

4)  Separate the power supply line from the signal lines. Do not lead the power supply line through the wiring port (knockout 

hole) for the signal lines since the power supply line may generate noise causing operation error and failure. 

5)  Connect the wires of each line. After connecting the wires, lightly pull them from the wiring ports so that minimum wire slack 

remains inside the actuator. Too long wire slack inside the actuator may block the terminal cover to close or may hold down 
the reset switch and interrupt the operation. See Fig. 3 for the location of the reset switch. 

 

6)  Tighten the seal connectors of the wiring ports. On the wiring ports for Display Panel cable and temperature sensor (Pt100 

input) cable, tighten the seal connectors until the clearance between the wiring port and the seal connector becomes 
narrower than 1 mm.  
Cable may get twisted as you tighten the seal connector. In such a case, loosen and remove the seal connector and untwist 
the cable, then re-tighten the seal connector.   

 

 

 

 

 

 

 

 

 

 

 

 

Wires connection of the temperature sensor (Pt100 input) 

 

 

Figure 14.  6-pin connector for temperature 

sensor (Pt100 input) 

Terminal 

Wire color* 

Description 

Temperature 

sensor for pipe 

surface 

Insertion-type pipe 

temperature sensor 

T1A 

Red 

Red 

Pt100 A (supply water temperature) 

T1B 

White 

Black 

Pt100 B (supply water temperature) 

T1B 

White 

White 

Pt100 B (supply water temperature) 

T2A 

Red 

Red 

Pt100 A (return water temperature)  

T2B 

White 

Black 

Pt100 B (return water temperature) 

T2B 

White 

White 

Pt100 B (return water temperature) 

 

Note:   

 

Wire color of the insertion-type pipe temperature sensor shown in the above 

 

table is the wire colors of the recommended cable. 

 

1)  Pass the 3-core cable of the temperature sensor (Temperature sensor for pipe surface/Insertion-type pipe temperature 

sensor) through the actuator port for the temperature sensor (Pt100 input). (See Fig. 3 for the location of the port.)  Use JIS 
VTCF 0.3 mm

2

 

 3 cores cable or equivalent for the insertion-type pipe temperature sensor. 

 

2)  Strip the wire sheath. Strip length is 7 mm. (See Fig. 15.)   

 

       Figure 

15. 

 

Wire 

sheath 

strip 

length 

 

T1A  T1B  T1B 

T2A T2B T2B 

Actuator of Model FVY5130J/FVY5140J/FVY5150J 

1   2   3   4   5   6   7  8 

            

 

24 V AC cable 

Pulse output 

+            - 

DI 

(Cooling/heating 

switch signal) 

+            - 

+            - 

Control signal 

input 

Seal 
connectors 

1 mm (max.) 
clearance 

1 mm (max.) 
clearance 

Figure 13.  Clearance for seal connector connection 

Wiring port for

valve sensor

Wiring port for

temperature sensor

(Pt100 input)

Knockout hold for

the wiring port

6-pin connector for

RS-485 communication

6-pin connector for  
temperature sensor 
(Pt100 input) 

4-pin connector for 
Display Panel 

Figure 12.  Connectors for the temperature sensor,

Display Panel, and RS-485 communication 

7 mm 

Содержание ACTIVAL FVY5130J

Страница 1: ...ol in combination with a DDC controller Flow data stored in the Model FVY5130J FVY5140J FVY5150J is retrieved via RS 485 communication Modbus protocol The retrieved flow data is effective for energy s...

Страница 2: ...valve body and cause leakage When piping this product be sure there is no foreign matter in the pipes If foreign matter remains in the pipes the product may break down CAUTION 2 2 Install wire and us...

Страница 3: ...inside the valve Rust or foreign object inside the valve lowers flow rate measuring accuracy Thermally insulate the valve and do not allow the process fluid to freeze Frozen process fluid around the...

Страница 4: ...Insertion type pipe temperature sensor Model TY783 For the specifications of the insertion type pipe temperature sensor refer to AB 5429 Specifications Instructions of Pipe Temperature Sensor Outdoor...

Страница 5: ...s FVY5130J0011 FVY5140J0011 FVY5150J0011 DN15 1 2 1 0 1 0 MPa FVY5130J0012 FVY5140J0012 FVY5150J0012 DN15 1 2 2 5 1 0 MPa FVY5130J0013 FVY5140J0013 FVY5150J0013 DN15 1 2 6 0 1 0 MPa FVY5130J0021 FVY51...

Страница 6: ...ication 6 pin 3 pin 2 connector Display Panel 4 pin connector Operation status indicator LED 1 red LED Status LED indication Normal Repetition of 1 second ON 1 second OFF Major alarm Continuous ON Min...

Страница 7: ...0 l min FVY5130J0061 FVY5140J0061 FVY5150J0061 DN65 2 1 2 95 950 l min FVY5130J0081 FVY5140J0081 FVY5150J0081 DN80 3 125 1250 l min Measuring accuracy Factory preset Notes 1 The flow measurement accur...

Страница 8: ...sensing accuracy of the temperature sensors connected the conversion accuracy and the error due to wiring length 7 Energy calculation accuracy is calculated from the flow rate measuring accuracy at 1...

Страница 9: ...f the product relay terminal block wiring and the relay terminal block load device in connection 2 JCS Japanese Electric Wire and Cable Makes Association 3 KPEV Wire standard provided by Furukawa Elec...

Страница 10: ...nal cover O ring Gland packing Stem Spring Seat ring Heat insulation Connector for Pt100 input Row T1 Supply water temperature Row T2 Return water temperature Reset switch Connector for Display Panel...

Страница 11: ...o remove foreign substances Provide a strainer on the inflow side of the valve For chilled hot water 40 or more meshes If the strainer cannot be installed just before the inlet of each valve install i...

Страница 12: ...or faces downward Flow direction Flow direction Flow direction Figure 5 Incorrect mounting orientations Piping CAUTION When installing this product hold it in the proper position and securely fasten i...

Страница 13: ...oduct Heat insulating Apply heat insulation as illustrated by in Fig 6 If the yoke and or the actuator are covered with insulation material the point cannot be checked or may be distorted If the heat...

Страница 14: ...ve the actuator may break down Do not manually open or close the valve more than 100 or less than 0 scale 1 Turn off the power 2 Hold the joint using a wrench etc gently turn the wrench to the desired...

Страница 15: ...ke proper contact Use crimp terminals with insulation for connections to the product terminals Failure to do so may cause short circuit leading to fire or device failure Tighten the terminal screws wi...

Страница 16: ...Pt100 input Terminal Wire color Description Temperature sensor for pipe surface Insertion type pipe temperature sensor T1A Red Red Pt100 A supply water temperature T1B White Black Pt100 B supply water...

Страница 17: ...e recommended cable 1 Pass the 4 core cable of Display Panel through the actuator port for Display Panel See Fig 3 for the location of the port 2 Strip the wire sheath Strip length is 8 mm See Fig 15...

Страница 18: ...iring port to share the wiring port with signal lines Connect the wires of RS 485 communication cable to the unplugged connector from the actuator socket After connecting the wires to the connector pl...

Страница 19: ...0 mA input type products See Figs 23 and 24 4 20 mA control signal input is not isolated from the power and the 4 20 mA input impedance is 282 For connecting a controller the relations among the input...

Страница 20: ...Terminals 2 6 and 8 of the product are internally connected 3 Refer to 6 Single transformer with two products in the Precautions for connection section Figure 24 Connection example Two Model FVY5130J...

Страница 21: ...ter Slave Model R series Slave Model FVY51X0J this product 1 2 3 4 5 6 Figure 27 Connection example 3 wire RS 485 communication Model FVY51X0J This product Pulse counter 3 4 V 0 V Figure 29 Connection...

Страница 22: ...erform 1 and 2 to release the other 2 latches 4 Lift and remove the cover from the base Figure 31 Cover removal from the base Attaching the cover to the base Attach the cover to the base and fix them...

Страница 23: ...o the base IMPORTANT Carefully attach the cable gland so that O rings do not fall from the cable gland Without the O rings water proof protection is not assured Figure 35 Attaching the cover to the ba...

Страница 24: ...el Numbers Options For conduit connection use a water proof plica tube or the like Maintenance CAUTION Do not put a load or weight on this product Doing so may damage the product Before doing maintena...

Страница 25: ...nlet pressure equal to outlet pressure No flow across the valve in open position e g when supply pump is OFF or when hand valves on the inflow and or outflow sides of the valve are is fully closed Val...

Страница 26: ...AB 7042 26 This blank page was added for page layout purposes...

Страница 27: ...AB 7042 27 This blank page was added for page layout purposes...

Страница 28: ...251 8522 JAPAN https www azbil com Rev 9 0 Apr 2020 J AI 7042 Rev 4 0 28 ACTIVAL and ACTIVAL are trademarks of Azbil Corporation in Japan or in other countries KPEV is a registered trademark of Furuka...

Отзывы: