9. Adjusting instructions
Adjusting instructions in case of leakage for AZ plug valves type:
ISO-STANDARD DN15-100 NPS ½“-4“ / ISO-EXTRA DN15-80 NPS ½“-3
“
1. Plug should be in an open position
2. Both adjusting bolts shall be turned ¼ to ½ rotations clock-
wise one after another.
3. Afterwards move the plug 10-15 degrees and back.
4. If the valve is still leaking please repeat step 2) and 3).
Please do not over tighten the adjustment bolts as the breakaway
torque may increase beyond the normal limits.
Adjusting screws
(plug)
Thrust collar
Stainless
diaphragm
PTFE
V-diaphragm
with delta
thrust collar
PTFE
sealing ring
PTFE sleeve
Plug