Chapter 2: Installation
9
Daisy Chaining PM IPDUs
You may manage a maximum of 128 outlets by connecting multiple PM IPDUs to the main PM
IPDU device.
To daisy chain a PM IPDU:
This procedure assumes that a main PM IPDU is already connected to a workstation or
management appliance.
1.
Connect one end of an RJ-45 cable to the OUT port of the main PM IPDU, which is connected
to a workstation or management appliance.
2.
Connect the other end of the RJ-45 cable to the IN port of the secondary Cyclades PM IPDU.
3.
Repeat these steps until you have connected the desired number of PM IPDUs.
Accessing the Console
Users and administrators may access the PM IPDU either by making a direct console connection to
the PM IPDU’s IN port or by connecting the PM IPDU to an Avocent console or KVM switch
management device.
Direct console access
While using the PM IPDU device independently of other Avocent devices, local users may connect
directly to the system console port (the IN port) of the PM IPDU using the console cable with the
corresponding adaptor(s).
The system administrator must specify basic settings on the PM IPDU before users may connect to
and manage the unit and the connected devices. To perform necessary basic configuration, make a
direct connection to the PM IPDU by connecting a terminal or computer to the IN port.
To access the console:
Perform the following steps to connect a computer to the console port of the PM IPDU. This
procedure assumes that you know how to use a terminal emulation program.
1.
Connect an RJ-45 serial cable to the IN port on the PM IPDU.
2.
Connect the RJ-45 serial cable to a computer with a terminal emulation program using the RJ-
45 to DB-9F straight-through adaptor or a USB serial adaptor.
3.
Using a terminal emulation program, connect to the PM IPDU with the following settings:
ANSI emulation, 9600 bps, 8 bits, no parity, 1stop bit and no flow control.
When prompted, enter the username
admin
with the default password
pm8
.
If this is a first-time installation, see
Initial configuration using the command prompt
on page 10
for instructions on changing the default password, adding users and assigning outlets to users.
pm_install_admin_user.book Page 9 Tuesday, March 24, 2009 3:02 PM
Содержание CYCLADES PM IPDU
Страница 1: ...CYCLADES PM IPDU Installer User Guide...
Страница 61: ......
Страница 62: ...For Technical Support www avocent com support 590 667 501D...