T1689 Technical Manual Rev 07
Specification
MV3000 Air Cooled DELTA
Reactors, Inductors & Transformers
Page 63
2.13.2.3
Interface
•
The airflow path is the same as DELTA modules.
•
Cross-rail fixing positions are the same as DELTA modules.
•
Phase connections are made by busbar or cable between the rectifier module and reactor.
•
The module earth connection is made via M10 stud connection.
2.13.2.4
External Requirements
•
This module must be used with the DELTA Cooling System to obtain the full current rating.
•
The reactor requires an additional 250mm (9.84”) of cross rail to attach to the standard DELTA
cross rails – this may increase overall cubicle width.
•
An external 230V a.c. supply is required to power the DELTA Cooling System.
•
An additional set of air inlet / outlet ducts are required to properly channel the cooling path using
these modules.
NOTE: These reactors will not fit into a 600mm deep cubicle without modification.
2.13.3
D.C. Link Inductor for DFE Drives
This inductor is used in conjunction with the DFE input reactor, to provide a more continuous current into the
machine bridge and reduce the harmonics that the drive imposes on the supply. This item is mandatory when
using three-phase, 6 pulse, rectifier modules.
NOTE: When using twelve pulse rectifier modules the use of an Interbridge transformer replaces the mandatory
requirement for the d.c. link inductor.
Figure 2–24. – DC Link Inductor
These naturally ventilated inductors are used with 6 pulse input rectifiers - see Table 2–32.
Содержание MV3000 DELTA
Страница 1: ...T1689 Technical Manual Rev 07 MV3000 Air Cooled DELTA...
Страница 150: ...Maintenance T1689 Technical Manual Rev 07 Capacitor Reforming MV3000 Air Cooled DELTA Page 150 Page Intentionally Blank...
Страница 152: ...T1689 Technical Manual Rev 07 MV3000 Air Cooled DELTA Page 152 Page Intentionally Blank...
Страница 184: ...T1689 Technical Manual Rev 07 MV3000 Air Cooled DELTA Page 184 Page Intentionally Blank...