![Avid Technology MV3000 DELTA Скачать руководство пользователя страница 137](http://html1.mh-extra.com/html/avid-technology/mv3000-delta/mv3000-delta_technical-manual_3031206137.webp)
T1689 Technical Manual Rev 07
PDS Commissioning Guidance
MV3000 Air Cooled DELTA
System Configuration When Non-operational
Page 137
7.4
SYSTEM CONFIGURATION WHEN NON-OPERATIONAL
The installation, configuration and modes of operation of this equipment may require internal heating during
periods when the main drive is not powered to prevent condensation forming.
The implementation of this type of heating is dependent on the following:
•
External environmental conditions;
•
Required internal environmental limits;
•
External power sources;
•
Safety implications of powered heater elements.
7.5
FUNCTIONAL TESTS
7.5.1
Software
Drive software will already be installed in the controller. This will need to be checked to ensure it is the latest
version. If not, the latest version must be installed.
The drive controller will need to be loaded with the relevant application code. A PC with Drive Coach
TM
software will be required for this.
For information on how to perform software updates / installation, see T1676 (or T2002 for AEM drives), T1679
and the specific application notes prepared for the system.
7.5.2
Fans
Ensure that all fans operate as they should, fans could include:
•
DELTA cooling fans;
•
Enclosure fans;
•
Controller fan.
7.5.3
Communication Links
Ensure that the communication links to the drive are operational. These should be initialised by following the
guidance provided by the relevant Instruction Sheet. The communication links could include CANopen,
Ethernet and Serial Links.
7.5.4
Plant I/O
Check all feedback signals into the I/O circuits are functioning. This could include cooling system feedbacks,
and “User Daisy Chain” healthy signals. The operation of these circuits will be detailed in the circuit diagrams
and the Test Specification produced by the enclosure manufacturer.
7.5.5
Power Circuit
The commissioning procedure for the power circuit should be determined by the final customer. Reference
should be made to the Getting Started Manual T1676 (or T2002 for AEM drives) and the enclosure
manufacturer installation instructions.
Содержание MV3000 DELTA
Страница 1: ...T1689 Technical Manual Rev 07 MV3000 Air Cooled DELTA...
Страница 150: ...Maintenance T1689 Technical Manual Rev 07 Capacitor Reforming MV3000 Air Cooled DELTA Page 150 Page Intentionally Blank...
Страница 152: ...T1689 Technical Manual Rev 07 MV3000 Air Cooled DELTA Page 152 Page Intentionally Blank...
Страница 184: ...T1689 Technical Manual Rev 07 MV3000 Air Cooled DELTA Page 184 Page Intentionally Blank...