![Avid Technology MV3000 DELTA Скачать руководство пользователя страница 100](http://html1.mh-extra.com/html/avid-technology/mv3000-delta/mv3000-delta_technical-manual_3031206100.webp)
Drive (CDM) Design
T1689 Technical Manual Rev 07
Component Selection - Mechanical
MV3000 Air Cooled DELTA
Page 100
3.9.1.4
Enclosure Type
Panels
Material
Steel
To provide a conductive and magnetic screen in addition to
safety segregation.
This minimises electrical radiated emissions from the drive
and helps protect the drive from radiating sources
Finish
External Painted
Good environmental protection
Internal plated or galvanised (e.g. Zintec) For good electrical bonding
Frame
Material
Steel
Strength and cost
Finish
Plated or galvanised
This gives good low inductance connections for electrical
bonding
Recommended
Rittal TS range:
•
with galvanized frame and
•
painted steel cladding
•
without the rear mounting panel
or the EMV version for higher emission shielding.
3.9.1.5
Enclosure Further Requirements
Earthing / Bonding
The enclosure bonding must comply with instructions given in Section 3.5.3: Electrical Bonding.
Openings
Avoid all unnecessary apertures. All doors and covers to hazardous parts to be closed when the equipment is
energized.
Cable Glanding
The cables entering the enclosure must be correctly bonded through the gland plates. See Section 3.5.3:
Содержание MV3000 DELTA
Страница 1: ...T1689 Technical Manual Rev 07 MV3000 Air Cooled DELTA...
Страница 150: ...Maintenance T1689 Technical Manual Rev 07 Capacitor Reforming MV3000 Air Cooled DELTA Page 150 Page Intentionally Blank...
Страница 152: ...T1689 Technical Manual Rev 07 MV3000 Air Cooled DELTA Page 152 Page Intentionally Blank...
Страница 184: ...T1689 Technical Manual Rev 07 MV3000 Air Cooled DELTA Page 184 Page Intentionally Blank...