Commissioning and Operation
100
AVENTICS
| PROFINET-IO | R412015162–BDL–001–AE
Table 22:
Diagnostic values
Value for
Info
Description
VS
channel
open
loop
VS
channel
short
circuit
VS
over-
load
U
Q1
under-
Voltage
U
Q2
under-
Voltage
U
Q1
missing
U
Q2
missing
System
error
SREG
short
circuit
Slot
Indicates which
module reports
the diagnosis.
1 (VS)
1 (VS)
1 (VS)
0 (DAP) 0 (DAP) 0 (DAP) 0 (DAP) 0 (DAP) 0 (DAP)
Subslot
Indicates which
sub-module
reports the
diagnosis.
1
1
1
1
1
1
1
1
1
Channel
Indicates which
channel reports
the diagnosis.
0 means it is
unassigned.
1...32
1...32
0
1
2
1
2
0
0
Channel
Error-
Type
Indicates the
type of error.
These values
are interpreted
by the
controller, as
they are
defined values
that were pre-
assigned and
pre-suggested.
0x0012
rec. for
“fuse
blown/
open”
0x0001
“short
circuit”
0x0004
“overlo
ad”
0x0002
“under
voltage”
0x0002
“under
voltage”
0x0011
rec. for
“power
supply
fault”
0x0011
rec. for
“power
supply
fault”
0x0009
“error”
0x0001
“short
circuit”
Extended
Channel
Error-
Type
Provides more
details on the
diagnostic
information.
The transferred
values are
internal
diagnostic IDs.
11
11
10
12
13
14
15
16
18
Channel
Additional
Value
Also serves to
further specify
the reported
error. Remains
empty here
(0x0000).
0
0
0
0
0
0
0
0
0
Содержание PROFINET-IO
Страница 2: ......
Страница 114: ...Disposal 114 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Страница 174: ...Elimination des d chets 174 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Страница 236: ...ndice 236 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Страница 347: ...Nyckelordsregister AVENTICS PROFINET IO R412015162 BDL 001 AE 347 Svenska...