Commissioning and Operation
92
AVENTICS
| PROFINET-IO | R412015162–BDL–001–AE
6.1.2
Setting the diagnostic messages
The S3 mode switch used to set the diagnostic messages is
located under the PG fitting A (see Fig. 6 and Fig. 7 on page 88).
When delivered, the diagnosis is deactivated (S3.1 – 3.6 set
to OFF)
O
Activate or deactivate the diagnostic message to the
IO controller with switches S3.1 – 3.6.
The modified switch position will only be activated after
a new “power on”.
The queued diagnoses are shown on the LEDs of the
BDC-B-DCP_32 even if the diagnostic message on the
IO controller is turned off!
Table 19:
S3, defining the monitoring threshold for valve voltage
Bit
8
7
6
5
4
3
2
1
Meaning
3.1
OFF Valve driver diagnosis switched off
ON
Valve driver diagnosis switched on
3.2
OFF
Low voltage message U
Q1
switched off
ON
Low voltage message U
Q1
active
3.3
OFF
Low voltage message U
Q2
switched off
ON
Low voltage message U
Q2
active
3.4
OFF
Message U
Q1
missing switched off
ON
Message U
Q1
missing active
3.5
OFF
Message U
Q2
missing switched off
ON
Message U
Q2
missing active
3.6
OFF
SREG short circuit message off
ON
SREG short circuit message active
3.7
OFF
U
Q1
tolerance - 15%
ON
U
Q1
tolerance - 10%
3.8
OFF
U
Q2
tolerance - 15%
ON
U
Q2
tolerance - 10%
Содержание PROFINET-IO
Страница 2: ......
Страница 114: ...Disposal 114 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Страница 174: ...Elimination des d chets 174 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Страница 236: ...ndice 236 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Страница 347: ...Nyckelordsregister AVENTICS PROFINET IO R412015162 BDL 001 AE 347 Svenska...