Installing and Cabling the Cabinets
AC Power and Ground
Installation, Upgrades and Additions for Avaya CMC1 Media Gateways
39
June 2004
CMC Power Switch
CAUTION:
The latch only removes DC power from the cabinet. Unseating the power supply removes
AC power from the power supply, but not from the cabinet. To remove AC power from the
cabinet, pull the AC power cord from the AC appliance connector on the rear of the
cabinet. See
Figure 9
.
Figure 9: CMC Power Supply
Connect Cabinet Grounds and Other Grounds
The following additional grounding requirements must be met:
•
The approved ground wire must be green, 6 AWG (#40) (16 mm
2
), copper, stranded wire (this is
in addition to the ground wire in the AC power cord)
•
Bond all approved grounds at the single-point ground to form a single grounding electrode system
Install the Ground Block
1
Mount the ground block as shown in
Figure 10
.
2
Make the cable connections as shown in
Figure 11
.
Figure notes
1
Latch
psdmdc RPY 011998
1