PSQ Series

 Error and troubleshooting

Display Cause

Troubleshooting

ERR1

When adjusting zero point 

while external pressure is 

input.

Try again after removing 

external pressure.

ERR2

When over current is 

applied on control output

Remove the over current 

conditions by adjusting load 

resistance. 

ERR3

When the range of Auto 

sensitivity setting mode 

ST1, ST2 is set incorrectly.

Check the setting range and 

set 

ST1

ST2

.

ERR4

When connection between 

master and slave is wrong

during copying parameters.

Check the cables between 

sensors and the connection 

of the same models.

ERR5

When entering invalid 

password. 

Enter valid password. 

HHHH

When applied pressure 

exceeds the high-limit of 

display pressure range.

Apply pressure within the 

display pressure range. 

LLLL

When applied pressure 

exceeds the low-limit of 

display pressure range.

-HH-

When the correction value 

of auto shift, remote zero 

exceeds the high-limit of 

the setting range.

Set the correction value 

of auto shift, remove zero 

within the setting range. 

-LL-

When the correction value 

of auto shift, remote zero 

exceeds the low-limit of the 

setting range.

-HL-

When [

HH

], [

LL

] occur both. 

 

This function is to diagnose malfunction of the system 

caused by parasitic pressure through memorizing input the 

max./min. pressure occurred from the system. 

Press the 

M

 

+

 

 

key more than 1 sec in RUN mode and set 

the 

Peak Hold. 

 High/Low Peak Hold

 Pressure unit change  

PSQ series has 8 kinds of pressure unit.  

Please select the proper unit for application.  

• kPa, MPa, kgf/cm

2

, bar, psi, mmHg, inHg, mmH

2

O

When using mmH

2

O unit, multiply display value by 100.

It can prevent control output from chattering by changing 

response time. 

There are 10 types of response time; 2.5ms, 5ms, 10ms, 

25ms, 50ms, 100ms, 250ms, 500ms, 1,000ms, 5,000ms. 

If the response time is getting longer, the detection will be 

more stable by increasing the number of digital filter.

 

Response time (chattering prevention) 

 SV display part

Select the display type at the SV display part in RUN mode.  

There are 3 types; displaying SV [

STD

], displaying unit 

[

UNIT

], none [

OFF

]

 RESET

This function is to reset all parameters as factory default 

except control output SV to prevent wrong settings or 

difficult operation.

 Password

This function is to limit parameter settings, to check the 

parameter or to change the parameter settings only for 

entering the set password.

• 

 

0000: Password function OFF

• 0001: Only checking parameters 

• Setting range: 0002 to 9999 

 Control output change

Select between NPN open collector output or PNP open 

collector output. 

 

PV display color and color linked output 

You can select PV display color to the linked output status. 

There are 4 types as below. 

Select color linked output among [

OUT1

], [

OUT2

], or [

ALL

].

SV

PV display color

R-ON

Green in normal status. When the set color linked output 

turns ON, it displays red. 

G-ON

Red in normal status. When the set color linked output 

turns ON, it displays green. 

RED

Red is fixed.

GREN

Green is fixed.

 Zero-point adjustment

The zero-point adjustment function forcibly sets the 

pressure value to "zero" when the pressure port is opened 

to atmospheric pressure. When the zero  adjustment is 

applied, analog output [Voltage or Current] is changed by 

this function.

To set zero atmospheric pressure forcibly, 

press the 

 

+

 

 keys over 1 sec in RUN mode with the 

opened pressure port.

 Key lock

The key lock function prevents key operations so that 

conditions set in each mode. 

Press the 

M

 

+

 

 key over 1 sec in RUN mode to lock 

  keys. The PV display part displays [

LOCK

], and the SV 

  display part displays [

ON

] for 1 sec and it returns in RUN

  mode.

Press the 

M

 

+

 

 key over 1 sec in RUN mode to unlock 

  keys. The PV display part displays [

LOCK

], and the SV

  display part displays [

OFF

] for 1 sec and it returns in 

  RUN mode. 

 Output type change 

Output type for OUT1 and OUT2 can be able to set Nor

-

mally Open or Normally Closed.   

Note that Normally Open and Normally Closed provide 

opposite output.

SV

OUT1 output

OUT2 output

NO

Normally Open

OFF

NC

Normally Closed

OFF

1O2O

Normally Open

Normally Open

1O2C

Normally Open

Normally Closed

1C2O

Normally Closed

Normally Open

1C2C

Normally Closed

Normally Closed

Содержание PSQ Series

Страница 1: ...60 0 133322kPa 101 32472kPa Features Pressure Conversion Chart to from Pa kPa MPa kgf cm2 mmHg mmH2O psi bar inHg 1Pa 1 0 001 0 000001 0 000010197 0 007501 0 101972 0 000145038 0 00001 0 0002953 1kPa 1000 000 1 0 001 0 010197 7 500617 101 971626 0 145038 0 01 0 2953 1MPa 1000000 1000 1 10 197162 7500 61683 101971 626 145 038243 10 295 299875 1kgf cm2 98066 5 98 0665 0 098067 1 735 55924 10000 0005...

Страница 2: ...0ms 500ms 1 000ms 5 000ms Protection circuit Output short over current protection circuit Analog output 3 Voltage output Output voltage 1 5VDCᜡ 2 5 F S Linear max 1 F S Resolution 1 2 000 Output impedance approx 240Ω Response time 50ms Current output Output current DC4 20mA 2 5 F S Linear max 1 F S Resolution 1 2 000 Output impedance approx 100kΩ Response time 50ms External input 3 Auto shift Remo...

Страница 3: ...y for over 4 sec to enter parameter 2 group Setting mode Press the M key to select the setting items Press the M key for over 2 sec to return RUN mode 5 key RUN mode Press the key to set preset value of output operation mode Press the M keys to set key lock unlock Press the keys to adjust zero point Press the M keys to set peak hold Preset value setting mode Press the key to increase decrease sett...

Страница 4: ...ss 0 5 to 7mm 31 0 0 4 When N units are installed in series 31 0 0 4 31 N 3 5 N 1 Min 55 Integrated installation set Pneumatic Fluid type Separate installation set Pneumatic type 28 2 40 30 40 42 35 26 3 20 25 8 Rear panel bracket Front panel bracket Front cover PSO P01 Front cover PSO P02 Panel cut out Front Rear pael bracket set PSO B04 Panel bracket PSO B02 Panel cut out 6 75 7 37 41 34 2 42 39...

Страница 5: ...own V blue 0V black OUT1 white OUT2 12 24VDC orange analog output external input Load Load RUN mode Preset value setting Zero point adjustment Parameter 2 group Key lock High Low peak hold for over 1 sec It sets reference pressure to the current atmospheric pressure as zero for over 1 sec for over 1 sec Output short over current protection circuit Output short over current protection circuit Outpu...

Страница 6: ...ld The function to hold present value PV and control output while signal is input When OUT1 operation mode is set as fOUT or applied pressure is higher lower than the display pressure range auto shift SHFT remote zero ZERO functions are not available A V ShOT 1 Auto shift applied terminal OUT1 OUT2 ALL OUT1 OUT2 OUT1 OUT2 Select auto shift applied terminal Appears when Analog output External input...

Страница 7: ... Only checking parameters 0000 sOUT Control output switching NPN PNP NPN PNP Select type of control output NPN HYS Hysteresis for easy mode 1 to 1 1 1 1 1 1 1 1 Bar type Min 1ea Max 8ea Set the hysteresis for easy mode Rated pressure range Hysteresis per 1 Bar 100 0 to 100 0kPa 0 1kPa 100 0 to 1 000kPa 1kPa Appears when OUT1 or OUT2 operation mode is easy mode Although the display unit is changed ...

Страница 8: ...setting by output operation mode Output operation mode Preset Setting range Factory default 100 0 to 100 0kPa 100 to 1 000kPa EASY Easy P Pressure detection level Min display pressure P Max display pressure 05 0 0500 HYsM Hysteresis ST Pressure detection level Min display pressure ST Max display pressure 05 0 0500 HYS Hysteresis level Min display pressure HYS ST 5 0 0000 WIN Window com parison LO ...

Страница 9: ...tput voltage or current and external input auto shift remote zero hold are not available at the same time Analog output A V Analog voltage output A C Analog current output External input SHFT Auto shift ZERO Remote zero HOLD Hold Preset setting by external input mode External input mode Preset Setting range Factory default SHFT Auto shift ShIN Auto shift correction value Min preset setting value S...

Страница 10: ...1 ST2 Hysteresis is fixed as Min display interval The pressure detection level SET is shown in the below formula ST1 ST2 2 SET Pressure 1 Min display interval 1 1 1 ST1 ST2 SET SET ST1 ST2 OUT1 N O OUT2 N O OUT1 N C OUT2 N C ST2 SET ST1 ON OFF ON OFF ON OFF ON OFF Time Time Time Time Time Forced output control mode fOUT RUN mode fOUT Regardless of setting value it maintains comparison output OFF a...

Страница 11: ...COPY Slave unit PV display arbitrary value SV display OK M Master Slave brown V blue 0V black OUT1 black OUT1 white OUT2 white OUT2 Auto Shift Remote Zero Hold input Output mode change OUT1 operation mode There are 4 kinds of control output mode in order to realize the various pressure detection Hysteresis mode HYsM When needed to change hysteresis for detecting pressure Window comparison output m...

Страница 12: ...the SV display part in RUN mode There are 3 types displaying SV STD displaying unit UNIT none OFF RESET This function is to reset all parameters as factory default except control output SV to prevent wrong settings or difficult operation Password This function is to limit parameter settings to check the parameter or to change the parameter settings only for entering the set password 0000 Password ...

Страница 13: ...t this unit must avoid direct touch with water oil thinner etc 5 PSQ Series has panel bracket PSO B02 front cover PSO P01 are sold separately When mounting the unit on panel please follow the below figure The tightening torque of one touch fitting should be max 10N m It may cause mechanical problems Front cover PSO P01 Mounting panel panel thickness 0 8 3 5mm Panel bracket PSO B02 Body PSQ SMPS F ...

Отзывы: