G-16
PSQ Series
Preset Setting
●
NPN or PNP open collector output(OUT1/2)
1. Select OUT1/2 operation mode
[
OUT1
/
2
] to use in parameter 1
group.
( OUT1/2 operation mode
: easy, hysteresis, window comparison, auto
sensitivity setting,
forced output control
)
2. Enter the preset setting mode from RUN mode.
( set items are displayed in the order of OUT1 - OUT2)
3. Set the value for each item.
●
Analog output/External input
1. Select analog output/extenal input mode
[
I/O
] to use in
parameter 1 group.
(
Analog output/extenal input
: analog voltage output, analog current
output, auto Shift, remote zero, hold)
2. Enter the preset setting mode from RUN mode.
( analog output/external input items are displayed after OUT1 -
OUT2)
3. Set the value for each item.
Setting guide
To enter the preset setting mode,
press the
, key in RUN mode.
Press the
, key to change preset value, the
M
key to move to the next mode.
If there is no additional key or the
M
key
input for over 2 sec during setting, the value is automatically set and it returns to RUN mode. (except
forced output control mode)
●Note
Setting items and setting value are displayed at the setting value (SV) display part alternatively.
Operation mode (
easy, hysteresis, window comparison, auto sensitivity setting)
that can be set separately per each output (OUT1/OUT2)
display parameter name with identification number.([
ST
]:
[
ST1
]
/[
ST2
]
)
When changing pressure unit or analog output/extenal input
, the
preset value is initialized corresponding to changed item.
When changing operation mode, the preset value is reset for the changed mode.
●Preset setting by output operation mode
Output
operation
mode
Preset
Setting range
Factory default
-100.0 to
100.0kPa
-100 to
1,000kPa
EASY
Easy
P
Pressure detection
level
Min. display pressure
<
[
P
] ≤ Max. display pressure
05)0
0500
HYsM
Hysteresis
ST
Pressure detection
level
Min. display pressure
<
[
ST
] ≤ Max. display pressure
05)0
0500
HYS
Hysteresis level
Min. display pressure ≤ [
HYS
]
<
[
ST
]
-5)0
0000
WIN
Window com
-
parison
LO
Pressure detection
level low-limit
Min. display pressure ≤ [
LO
] ≤ Max. display pressure
- (3 × min. display unit)
-5)0
0000
HI
Pressure detection
level high-limit
[
LO
] + (3 × min. display unit) ≤ [
HI
] ≤ Max. display pressure
05)0
0500
AUTO
Auto sensitivity
setting
ST1
Pressure detection
level 1
Min. display pressure ≤ [
ST1
] ≤ Max. display pressure
- 1% of rated pressure
-5)0
0000
ST2
Pressure detection
level 2
[
ST1
] + 1% of rated pressure ≤ [
ST2
] ≤ Max. display pressure
05)0
0500
SET
Pressure detection
level
SET
=(
ST1
+
ST2
)
2
, [
ST1
] ≤ [
SET
] ≤ [
ST2
]
Pressure detection level [
SET
] can be selectable by pressing
the , key.
00)0
0250
fOUT
Forced output
control
-
-
-
-
-
A-V
Analog voltage
output
A-1V
1V output SV
0% F.S. ≤ [
A-1V
] ≤ 100% F.S.
`0)0
0000
A-5V
5V output SV
[
A-1V
] + 10% F.S. ≤ [
A-5V
] ≤ 100% F.S. or
0% F.S.≤ [
A-5V
] ≤ [
A-1V
] - 10% F.S.
10)0
1000
A-C
Analog current
output
A-04
4mA output SV
0% F.S. ≤ [
A-04
] ≤ 100% F.S.
`0)0
0000
A-20
20mA output SV
[
A-04
] + 10% F.S. ≤ [
A-20
] ≤ 100% F.S. or
0% F.S. ≤ [
A-20
] ≤ [
A-04
] - 10% F.S.
10)0
1000
Setting example
OUT1:
Hysteresis mode
OUT2:
Window comparison mode
Run mode
M
for over
2 sec
05)0
HI2
Pressure
detection level 2
low-limit value
Pressure
detection level 2
high-limit value
LO2
-5)0
Hysteresis
level 1
-5)0
HYS1
Pressure
detection
level 1
ST1
05)0
OUT1:
Hysteresis
mode
OUT2:
Window
comparison
mode
,
M
M
M
4mA
output
SV
20mA
output
SV
OUT1, OUT2 Preset setting
A-04
`0)0
10)0
A-20
Setting example
Analog current output scale
M
M
M