G-16

PSQ Series

 Preset Setting

NPN or PNP open collector output(OUT1/2)

1.  Select OUT1/2 operation mode 

[

OUT1

/

2

] to use in parameter 1 

group.

 

( OUT1/2 operation mode

: easy, hysteresis, window comparison, auto 

sensitivity setting, 

forced output control

)

2.  Enter the preset setting mode from RUN mode. 

( set items are displayed in the order of OUT1 - OUT2)

3. Set the value for each item.

Analog output/External input 

1.  Select analog output/extenal input mode 

[

I/O

] to use in 

parameter 1 group.

 

Analog output/extenal input

: analog voltage output, analog current 

output, auto Shift, remote zero, hold)

2.  Enter the preset setting mode from RUN mode. 

( analog output/external input items are displayed after OUT1 - 

OUT2)

3. Set the value for each item.

 

 Setting guide

  To enter the preset setting mode, 

 press the 

,   key in RUN mode. 

  

 Press the 

,   key to change preset value, the 

M

 key to move to the next mode.

  

 

If there is no additional key or the 

M

 key 

input for over 2 sec during setting, the value is automatically set and it returns to RUN mode. (except 

forced output control mode) 

●Note

  

Setting items and setting value are displayed at the setting value (SV) display part alternatively.

   

Operation mode (

easy, hysteresis, window comparison, auto sensitivity setting) 

that can be set separately per each output (OUT1/OUT2) 

display parameter name with identification number.([

ST

]: 

[

ST1

]

/[

 ST2

]

)

  

When changing pressure unit or analog output/extenal input

, the 

preset value is initialized corresponding to changed item.

  

When changing operation mode, the preset value is reset for the changed mode. 

●Preset setting by output operation mode

Output 

operation 

mode

Preset

Setting range

Factory default

-100.0 to

100.0kPa

-100 to

1,000kPa

EASY

Easy

P

Pressure detection 

level

Min. display pressure

[

P

] ≤ Max. display pressure

05)0

0500

HYsM

Hysteresis

ST

Pressure detection  

level

Min. display pressure

[

ST

] ≤ Max. display pressure

05)0

0500

HYS

Hysteresis level

Min. display pressure ≤ [

HYS

]

[

ST

]

-5)0

0000

WIN

Window com

-

parison

LO

Pressure detection  

level low-limit

Min. display pressure ≤ [

LO

] ≤ Max. display pressure  

- (3 × min. display unit)

-5)0

0000

HI

Pressure detection  

level high-limit

[

LO

] + (3 × min. display unit) ≤ [

HI

] ≤ Max. display pressure

05)0

0500

AUTO

Auto sensitivity 

setting

ST1

Pressure detection  

level 1

Min. display pressure ≤ [

ST1

] ≤ Max. display pressure  

- 1% of rated pressure

-5)0

0000

ST2

Pressure detection  

level 2

[

ST1

] + 1% of rated pressure ≤ [

ST2

] ≤ Max. display pressure

05)0

0500

SET

Pressure detection  

level 

 

SET

=(

ST1

+

ST2

)

2

, [

ST1

] ≤ [

SET

] ≤ [

ST2

]

Pressure detection  level [

SET

] can be selectable by pressing 

the  ,   key.

00)0

0250

fOUT

Forced output 

control

-

-

-

-

-

A-V

Analog voltage 

output

A-1V

1V output SV

0% F.S. ≤ [

A-1V

] ≤ 100% F.S.

`0)0

0000

A-5V

5V output SV

[

A-1V

] + 10% F.S. ≤ [

A-5V

] ≤ 100% F.S. or

0% F.S.≤ [

A-5V

] ≤ [

A-1V

] - 10% F.S.

10)0

1000

A-C

Analog current 

output

A-04

4mA output SV

0% F.S. ≤ [

A-04

] ≤ 100% F.S.

`0)0

0000

A-20

20mA output SV

[

A-04

] + 10% F.S. ≤ [

A-20

] ≤ 100% F.S. or 

0% F.S. ≤ [

A-20

] ≤ [

A-04

] - 10% F.S.                                      

10)0

1000

  Setting example 

OUT1: 

Hysteresis mode

 

OUT2: 

Window comparison mode

Run mode

M

 for over 

2 sec

05)0

HI2

Pressure 

detection level 2 

low-limit value

Pressure 

detection level 2 

high-limit value

LO2

-5)0

Hysteresis 

level 1

-5)0

HYS1

Pressure  

detection 

level 1  

ST1

05)0

OUT1: 

Hysteresis 

mode

OUT2:  

Window 

comparison 

mode

M

M

M

4mA 

output 

SV

20mA 

output 

SV

OUT1, OUT2 Preset setting

A-04

`0)0

10)0

A-20

  Setting example 

Analog current output scale

M

 

M

 

M

 

Содержание PSQ Series

Страница 1: ...60 0 133322kPa 101 32472kPa Features Pressure Conversion Chart to from Pa kPa MPa kgf cm2 mmHg mmH2O psi bar inHg 1Pa 1 0 001 0 000001 0 000010197 0 007501 0 101972 0 000145038 0 00001 0 0002953 1kPa 1000 000 1 0 001 0 010197 7 500617 101 971626 0 145038 0 01 0 2953 1MPa 1000000 1000 1 10 197162 7500 61683 101971 626 145 038243 10 295 299875 1kgf cm2 98066 5 98 0665 0 098067 1 735 55924 10000 0005...

Страница 2: ...0ms 500ms 1 000ms 5 000ms Protection circuit Output short over current protection circuit Analog output 3 Voltage output Output voltage 1 5VDCᜡ 2 5 F S Linear max 1 F S Resolution 1 2 000 Output impedance approx 240Ω Response time 50ms Current output Output current DC4 20mA 2 5 F S Linear max 1 F S Resolution 1 2 000 Output impedance approx 100kΩ Response time 50ms External input 3 Auto shift Remo...

Страница 3: ...y for over 4 sec to enter parameter 2 group Setting mode Press the M key to select the setting items Press the M key for over 2 sec to return RUN mode 5 key RUN mode Press the key to set preset value of output operation mode Press the M keys to set key lock unlock Press the keys to adjust zero point Press the M keys to set peak hold Preset value setting mode Press the key to increase decrease sett...

Страница 4: ...ss 0 5 to 7mm 31 0 0 4 When N units are installed in series 31 0 0 4 31 N 3 5 N 1 Min 55 Integrated installation set Pneumatic Fluid type Separate installation set Pneumatic type 28 2 40 30 40 42 35 26 3 20 25 8 Rear panel bracket Front panel bracket Front cover PSO P01 Front cover PSO P02 Panel cut out Front Rear pael bracket set PSO B04 Panel bracket PSO B02 Panel cut out 6 75 7 37 41 34 2 42 39...

Страница 5: ...own V blue 0V black OUT1 white OUT2 12 24VDC orange analog output external input Load Load RUN mode Preset value setting Zero point adjustment Parameter 2 group Key lock High Low peak hold for over 1 sec It sets reference pressure to the current atmospheric pressure as zero for over 1 sec for over 1 sec Output short over current protection circuit Output short over current protection circuit Outpu...

Страница 6: ...ld The function to hold present value PV and control output while signal is input When OUT1 operation mode is set as fOUT or applied pressure is higher lower than the display pressure range auto shift SHFT remote zero ZERO functions are not available A V ShOT 1 Auto shift applied terminal OUT1 OUT2 ALL OUT1 OUT2 OUT1 OUT2 Select auto shift applied terminal Appears when Analog output External input...

Страница 7: ... Only checking parameters 0000 sOUT Control output switching NPN PNP NPN PNP Select type of control output NPN HYS Hysteresis for easy mode 1 to 1 1 1 1 1 1 1 1 Bar type Min 1ea Max 8ea Set the hysteresis for easy mode Rated pressure range Hysteresis per 1 Bar 100 0 to 100 0kPa 0 1kPa 100 0 to 1 000kPa 1kPa Appears when OUT1 or OUT2 operation mode is easy mode Although the display unit is changed ...

Страница 8: ...setting by output operation mode Output operation mode Preset Setting range Factory default 100 0 to 100 0kPa 100 to 1 000kPa EASY Easy P Pressure detection level Min display pressure P Max display pressure 05 0 0500 HYsM Hysteresis ST Pressure detection level Min display pressure ST Max display pressure 05 0 0500 HYS Hysteresis level Min display pressure HYS ST 5 0 0000 WIN Window com parison LO ...

Страница 9: ...tput voltage or current and external input auto shift remote zero hold are not available at the same time Analog output A V Analog voltage output A C Analog current output External input SHFT Auto shift ZERO Remote zero HOLD Hold Preset setting by external input mode External input mode Preset Setting range Factory default SHFT Auto shift ShIN Auto shift correction value Min preset setting value S...

Страница 10: ...1 ST2 Hysteresis is fixed as Min display interval The pressure detection level SET is shown in the below formula ST1 ST2 2 SET Pressure 1 Min display interval 1 1 1 ST1 ST2 SET SET ST1 ST2 OUT1 N O OUT2 N O OUT1 N C OUT2 N C ST2 SET ST1 ON OFF ON OFF ON OFF ON OFF Time Time Time Time Time Forced output control mode fOUT RUN mode fOUT Regardless of setting value it maintains comparison output OFF a...

Страница 11: ...COPY Slave unit PV display arbitrary value SV display OK M Master Slave brown V blue 0V black OUT1 black OUT1 white OUT2 white OUT2 Auto Shift Remote Zero Hold input Output mode change OUT1 operation mode There are 4 kinds of control output mode in order to realize the various pressure detection Hysteresis mode HYsM When needed to change hysteresis for detecting pressure Window comparison output m...

Страница 12: ...the SV display part in RUN mode There are 3 types displaying SV STD displaying unit UNIT none OFF RESET This function is to reset all parameters as factory default except control output SV to prevent wrong settings or difficult operation Password This function is to limit parameter settings to check the parameter or to change the parameter settings only for entering the set password 0000 Password ...

Страница 13: ...t this unit must avoid direct touch with water oil thinner etc 5 PSQ Series has panel bracket PSO B02 front cover PSO P01 are sold separately When mounting the unit on panel please follow the below figure The tightening torque of one touch fitting should be max 10N m It may cause mechanical problems Front cover PSO P01 Mounting panel panel thickness 0 8 3 5mm Panel bracket PSO B02 Body PSQ SMPS F ...

Отзывы: