background image

G-14

PSQ Series

 Parameter Setting

After entering parameter 1/2 group, if there is no additional key input for 60 sec, it maintains previous setting value and it returns to RUN mode.

Press the 

 

 

 key to set the setting value.

After entering parameter 1/2 group, press the 

M

 key for over 2 sec to return to RUN mode. 

When pressing the 

M

 key once returning RUN mode from parameter 1 group, 2 group within 2 sec, it enters the previous parameter group.

Some parameters are activated/deactivated according to the setting of other parameters. Refer to the description of each parameter.

 Parameter Group

Parameter 1 group
Parameter name

Setting range

Description

Factory 

default

OUT1

OUT1 operation 

mode

EASY 
HYsM 

WIN 

AUTO 
fOUT

Easy 

Hysteresis

Window comparison  

Auto sensitivity setting 

Forced output control

Select OUT1 operation mode.

 

When setting OUT1 operation mode as auto sensitivity setting mode [

AUTO

] or 

forced output control mode [

fOUT

], OUT2 operation mode is set automatically 

same as the setting value of OUT1 operation mode.

EASY

OUT2

OUT2 operation 

mode

OFF 

EASY 
HYsM 

WIN

OFF 

Easy 

Hysteresis

Window comparison 

Select OUT2 operation mode.

OFF

I/O

1

Analog output/

External input

A-V 
A-C 

SHFT 
ZERO 
HOLD

Analog voltage output 

Analog current output 

Auto shift 

Remote zero 

Hold

Select analog output/external input operation mode.

Auto shift:  

When reference pressure of the pressure sensor changes, It 

corrects present pressure to reference pressure and by moving 

detection level as much as fluctuation level.

Remote zero:  I

t is the same function as auto shift but remote zero 

makes the measured pressure as 0 forcibly.

Hold:  The function to hold present value (PV) and control output while 

signal is input.

 

When OUT1 operation mode is set as [

fOUT

] or applied pressure 

is higher/lower than the display pressure range, auto shift [

SHFT

], 

remote zero [

ZERO

] functions are not available.

A-V

ShOT

1

Auto shift 

applied terminal

OUT1 
OUT2 

ALL

OUT1 

OUT2 

OUT1 & OUT2

Select auto shift applied terminal. 

 

 

Appears when Analog output/External input is [

SHFT

].

OUT1

ZeOT

1

Remote zero  

applied terminal

OUT1 
OUT2 

ALL

OUT1 

OUT2 

OUT1 & OUT2

Select remote zero applied terminal. 

 

Appears when analog output/external input is [

ZERO

].

OUT1

NoNC

Output type

OUT1

OUT2

NO

Normally Open

OFF

 

Appears when OUT2 operation mode is [

OFF

].

NC

Normally Closed  OFF

1O2O

Normally Open

Normally Open 

 

Appears when OUT1 operation mode is [

AUTO

], 

or OUT2 operation mode is [

HYsM

], [

WIN

].

1O2C

Normally Closed

Normally Open

1C2O

Normally Closed

Normally Open

1C2C

Normally Closed

Normally Closed

NO

SPD

Response time

@5

,

 5

,

10

,

 25

,

 50

,

 100

,

 250

,

 

500

,

 1000

,

  5000

It can prevent control output from chattering by changing response time.

 If the response time is getting longer, the detection will be more stable 

but present value (PV)  might be different from the real pressure 

value.

@5

CLOR

PV display color

R-ON 
G-ON 

RED 

GREN

Normal: Green / Output: Red

Normal: Red / Output: Green

Fixed red

Fixed green

Select the present value (PV) display and the color linked output.

R-ON

DISP

Color linked 

output

OUT1 
OUT2 

ALL

OUT1 

OUT2 

OUT1 & OUT2

Select the color linked output.

 

 Appears when OUT2 operation mode is not [

OFF

] and PV display color 

is set as [

R-ON

] and [

G-ON

].

OUT1

UNIT

Display unit

KPA 
MPA 
KGF 
BAR 
PSI 

MMHG 
INHG 

H2O

kPa 

MPa 

kgf/cm

2

 

bar 

psi 

mmHg 

inHg 

mmH

2

O

Select the display unit.

 

For using 

mmH

2

O unit, multiply display value by 100.

KPA

1: Appears only in NPN or PNP open collector analog output or external input model.

Содержание PSQ Series

Страница 1: ...60 0 133322kPa 101 32472kPa Features Pressure Conversion Chart to from Pa kPa MPa kgf cm2 mmHg mmH2O psi bar inHg 1Pa 1 0 001 0 000001 0 000010197 0 007501 0 101972 0 000145038 0 00001 0 0002953 1kPa 1000 000 1 0 001 0 010197 7 500617 101 971626 0 145038 0 01 0 2953 1MPa 1000000 1000 1 10 197162 7500 61683 101971 626 145 038243 10 295 299875 1kgf cm2 98066 5 98 0665 0 098067 1 735 55924 10000 0005...

Страница 2: ...0ms 500ms 1 000ms 5 000ms Protection circuit Output short over current protection circuit Analog output 3 Voltage output Output voltage 1 5VDCᜡ 2 5 F S Linear max 1 F S Resolution 1 2 000 Output impedance approx 240Ω Response time 50ms Current output Output current DC4 20mA 2 5 F S Linear max 1 F S Resolution 1 2 000 Output impedance approx 100kΩ Response time 50ms External input 3 Auto shift Remo...

Страница 3: ...y for over 4 sec to enter parameter 2 group Setting mode Press the M key to select the setting items Press the M key for over 2 sec to return RUN mode 5 key RUN mode Press the key to set preset value of output operation mode Press the M keys to set key lock unlock Press the keys to adjust zero point Press the M keys to set peak hold Preset value setting mode Press the key to increase decrease sett...

Страница 4: ...ss 0 5 to 7mm 31 0 0 4 When N units are installed in series 31 0 0 4 31 N 3 5 N 1 Min 55 Integrated installation set Pneumatic Fluid type Separate installation set Pneumatic type 28 2 40 30 40 42 35 26 3 20 25 8 Rear panel bracket Front panel bracket Front cover PSO P01 Front cover PSO P02 Panel cut out Front Rear pael bracket set PSO B04 Panel bracket PSO B02 Panel cut out 6 75 7 37 41 34 2 42 39...

Страница 5: ...own V blue 0V black OUT1 white OUT2 12 24VDC orange analog output external input Load Load RUN mode Preset value setting Zero point adjustment Parameter 2 group Key lock High Low peak hold for over 1 sec It sets reference pressure to the current atmospheric pressure as zero for over 1 sec for over 1 sec Output short over current protection circuit Output short over current protection circuit Outpu...

Страница 6: ...ld The function to hold present value PV and control output while signal is input When OUT1 operation mode is set as fOUT or applied pressure is higher lower than the display pressure range auto shift SHFT remote zero ZERO functions are not available A V ShOT 1 Auto shift applied terminal OUT1 OUT2 ALL OUT1 OUT2 OUT1 OUT2 Select auto shift applied terminal Appears when Analog output External input...

Страница 7: ... Only checking parameters 0000 sOUT Control output switching NPN PNP NPN PNP Select type of control output NPN HYS Hysteresis for easy mode 1 to 1 1 1 1 1 1 1 1 Bar type Min 1ea Max 8ea Set the hysteresis for easy mode Rated pressure range Hysteresis per 1 Bar 100 0 to 100 0kPa 0 1kPa 100 0 to 1 000kPa 1kPa Appears when OUT1 or OUT2 operation mode is easy mode Although the display unit is changed ...

Страница 8: ...setting by output operation mode Output operation mode Preset Setting range Factory default 100 0 to 100 0kPa 100 to 1 000kPa EASY Easy P Pressure detection level Min display pressure P Max display pressure 05 0 0500 HYsM Hysteresis ST Pressure detection level Min display pressure ST Max display pressure 05 0 0500 HYS Hysteresis level Min display pressure HYS ST 5 0 0000 WIN Window com parison LO ...

Страница 9: ...tput voltage or current and external input auto shift remote zero hold are not available at the same time Analog output A V Analog voltage output A C Analog current output External input SHFT Auto shift ZERO Remote zero HOLD Hold Preset setting by external input mode External input mode Preset Setting range Factory default SHFT Auto shift ShIN Auto shift correction value Min preset setting value S...

Страница 10: ...1 ST2 Hysteresis is fixed as Min display interval The pressure detection level SET is shown in the below formula ST1 ST2 2 SET Pressure 1 Min display interval 1 1 1 ST1 ST2 SET SET ST1 ST2 OUT1 N O OUT2 N O OUT1 N C OUT2 N C ST2 SET ST1 ON OFF ON OFF ON OFF ON OFF Time Time Time Time Time Forced output control mode fOUT RUN mode fOUT Regardless of setting value it maintains comparison output OFF a...

Страница 11: ...COPY Slave unit PV display arbitrary value SV display OK M Master Slave brown V blue 0V black OUT1 black OUT1 white OUT2 white OUT2 Auto Shift Remote Zero Hold input Output mode change OUT1 operation mode There are 4 kinds of control output mode in order to realize the various pressure detection Hysteresis mode HYsM When needed to change hysteresis for detecting pressure Window comparison output m...

Страница 12: ...the SV display part in RUN mode There are 3 types displaying SV STD displaying unit UNIT none OFF RESET This function is to reset all parameters as factory default except control output SV to prevent wrong settings or difficult operation Password This function is to limit parameter settings to check the parameter or to change the parameter settings only for entering the set password 0000 Password ...

Страница 13: ...t this unit must avoid direct touch with water oil thinner etc 5 PSQ Series has panel bracket PSO B02 front cover PSO P01 are sold separately When mounting the unit on panel please follow the below figure The tightening torque of one touch fitting should be max 10N m It may cause mechanical problems Front cover PSO P01 Mounting panel panel thickness 0 8 3 5mm Panel bracket PSO B02 Body PSQ SMPS F ...

Отзывы: