Installation and Specifications
Communications Cable Details
The drawings on this page are for cables which
are
supplied by
Automationdirect.com
. Use this page if you need to make your own cables. We
recommend using 22 AWG shielded cable.
3 4 5 6
2
1
1= Sig ground
2= 5 VDC
3= RX
4= TX
5= not used
6= Sig ground
RJ12
RJ12 (PLC)
RJ12 (Panel)
1
6
4
3
3
4
OP--3CBL--1 (D3--340)
RJ12
RJ11
OP--2CBL--2
OP--ACBL--3
(Allen--Bradley)
OP--4CBL--3 (DL405)
1 2 3 4
1= RX
2= TX
3= not used
4= Sig ground
RJ11
RJ11 (PLC)
1
4
3
2
RJ12 (Panel)
1
4
8= not used
7= not used
6= not used
5= not used
4= Sig ground
3= RX
2= TX
1= not used
DB15 (PLC)
2
3
4
3
RJ12 (Panel)
5
11
4
15=Sig ground
14= Sig ground
13=Sig ground
12= not used
11= 5 VDC
10= not used
9= not used
1
15
1
9
1
6
1= not used
2= RX
3= TX
4= not used
DB9 (PLC)
2
4
3
3
RJ12 (Panel)
1
5
5= Sig ground
6= not used
7= RTS
8= CTS
9= not used
6
DB15
DB9
1= Sig ground
2= not used
3= RX
4= TX
6= Sig ground
5= 5 VDC
3 4 5 6
2
1
RJ12
Panel
Connection
Panel
PLC
5
2
13
14
15
(Pins)
(Sockets)
(DL05, DL105, DL205,
D3--350, D4--450)
7
8
OP400 Series
Communications
Cables