Part Number Key
AutomationDirect.com (ADC)
3505 Hutchinson Road, Cumming, GA 30040
Phone: (800) 633-0405 or (770) 889-2858
ACS035/ACS400
SERIES
INSTALLATION
INSTRUCTIONS
Quick Start Guide
1. Route monitored wire through aperture.
2. Mount the sensor to a DIN rail or panel.
3. Connect power supply and output wiring.
a. Use 30-12 AWG copper wire and tighten termi-
nals to 7 in-lbs torque.
b. Ensure supply power and load matches that
shown on sensor label.
4.
Adjust setpoints.
a. Use trip adjust potentiometers to select
setpoints.
b. LED shows Green with power supply
connected, Amber when the current has
exceeded the setpoint.
®
ACTS - Inst - Rev 1 0820
P-N 394000024
Specifications
Power Supply
24VAC/DC ( +/- 8.3%)
Power Consumption
< 2VA
Output
(2) Independent Single Pole, Double Throw mechanical
Relays
Contact Rating
1A @ 120VAC, 2A @ 30VDC
Response Time
40 - 120ms
Hysteresis
4% of setpoint
Setpoint Ranges
2-35 Amps (ACS035)
25-400 Amps (ACS400)
Setpoint Adjust
Two 3/4-turn potentiometers
Sensed Current
Limit
1.1x range continuous
3x range for 6 seconds
5x range for 1 second
Isolation Voltage
UL508, UL tested to 1240VAC
Frequency Range
40-65 Hz
Sensing Aperture
1.31 in (33.3 mm) dia.
Environmental
-Temp -4 to 122°F (-20 to 50°C)
-Humidity 0-95% RH, Non-condensing
-Pollution degree 2
-Altitude 2000 meters
Case
UL 94V-0 Flammability rated thermoplastic
Certifications
cULus listed E222847
CE
A C S 035 - 2C - 24 - F
SENSOR TYPE
ACS AC current operated switch
OUTPUT
CASE STYLE
2C - (2) SPDT relay outputs,
independant setpoints
RANGE
035 - 2-35 Amps AC
400 - 25-400 Amps AC
POWER SUPPLY
24 - 24 VAC/DC
F - Fixed Core
Warning! Risk of electric shock or
personal injury
Safe operation can only be guaranteed if the
device is used for the purpose for which it was
designed and within the limits of the technical
specifications. When this symbol is used, it
means you should consult all documentation to
understand the nature of potential hazards and
the action required to avoid them.
Warning! Risk of hazardous voltage
When operating the device, certain parts may
carry hazardous live voltage (e.g., primary
conductor, secondary terminals). The device
should not be put into service if the installation is
not complete.
For products intended for the EU market, the
following is applicable to the CE compliance of
the product:
The ACS035/ACS400 Series may comply with EN 61010-1
CAT III 300V max line-to-neutral measurement category. If
insulated cable is used for the primary circuit, the voltage rating
of the measurement category can be improved according to
the characteristics given by the cable manufacturer.
Use 24V input power and fuse at 5 amps. Power source
overvoltage category I as defined per EN 61010-1.
Part No. ACS035-2C-24-F