background image

Description

The ACS035 and ACS400 Series products are powered, 
current-operated switches which trigger when sensed 
current levels exceed the adjusted setpoint.  There are two 
independent setpoints, one for higher than normal current and 
another for lower than normal, or one for alarm at too high 
and the second for shut down at an excessive current level. 
The two independent outputs are single pole, double throw 
relay contacts.

Installation

The ACS035 and ACS400 switches can be located in the 
same environment as motors, contactors, heaters, pull-boxes, 
and other electrical enclosures.
Mounting can be made in any position to a panel or a 35mm 
DIN rail, or hung directly on wires with a wire tie.  Keep at 
least one inch clearance between sensor and other magnetic 
devices.

Wiring

Run wire to be monitored through aperture (opening) in the 
sensor.
For power supply and output wiring, use 30-12AWG copper 
wire and tighten terminals to 7 in-lbs torque.  Be sure the 
output load requirement does not exceed the contact rating.
Connect power supply to terminals 4 and 5 on the sensor. 
Check to ensure supply power matches voltage and type 
required by sensor. Once powered, the LEDs on the unit 
should indicate unit is on by glowing green.
Connect output wiring to be controlled by Setpoint #1 to 
terminals 1-2 for the normally closed (opens on current rise) 
or 2-3 for the normally open (closes on current rise) contact. 
Connect output wiring to be controlled by Setpoint #2 to 
terminals 6-7 for the normally closed (opens on current rise) 
or 7-8 for the normally open (closes on current rise) contact. 
Note that if unit is powered and monitored conductor has 
current flow, the output contacts may change state depending 
on setpoint adjustment settings.

Power Supply and Output Wiring

24VAC or DC

Power Supply

Common

Common

NO (Closes to Common on Current Rise)

NO (Closes to Common on Current Rise)

NC (Opens to Common on Current Rise)

NC (Opens to Common on Current Rise)

Set Point #1

Adjustment

LED Shows Contact Status

Set Point #2

Adjustment

LED Shows Contact Status

1

2

3

4

5

6

7

8

Setpoint Adjustment

The ACS035 and ACS400 Series setpoints are adjusted 
using two 3/4-turn pots which have arrow indication of the 
selected value.  The arrow points to the current magnitude 
which will cause the output relay(s) to energize or change 
state. Possible to control one DC circuit and one AC circuit. 

Typical Adjustment
1.   Turn the setpoint adjustment pot #1 to the point where 

you want the first relay to change state.

2.   Turn the setpoint adjustment pot #2 to the point where 

you want the second relay to change state.

3.   

Thread the load conductor(s) through the sensing 
aperture. If multiple conductors are used to power the 
monitored load, each conductor must be connected to 
the same phase. 

4.  Energize the sensor with 24VAC/DC (+/-8.3%)
5.  Both indicating LEDs will be illuminated Green.
6.   After energizing the monitored load, if the current used 

is over the adjustment level of Setpoint #1 the LED will 
change to Amber to indicate that the output relay has 
changed state. 

7.   When the monitored current exceeds the level of Setpoint 

#2, that LED will also change from Green to Amber. 

8.   The most common use would be to adjust Setpoint #1 to 

be in the tripped condition during normal load operation, 
reverting to “normal” if current falls below that point; and 
to have Setpoint #2 adjusted so it is “untripped during 
normal operation, and change state in an over current 
condition. 

9.   The output contacts are floating, and can be wired in 

parallel (OR wiring) or in series (AND wiring) for a two 
wire over/under switch action. See Application Examples. 

Troubleshooting

1. Sensor is always tripped.

A.  The setpoints may be too low.  

Turn pot Clockwise to increase setpoint. 

B.  Switch has been overloaded and contacts are burned out. 

Check the output load, remembering to include inrush on 
inductive loads (coils, motors, ballasts)

2. Sensor will not trip.

A.  The setpoints  may be too high.  

Turn pot Counter Clockwise  to decrease setpoint. 

NC

NC NO

NO

POWER

Closed at Normal   

Closed at Normal

Open at Low Current 

Open at High Current

Control circuit is open at either

over or under normal current conditions.

Series Over/Under Current Window

(AND wiring) Example

NC

NC NO

NO

POWER

Open at Normal   

Open at Normal

Closed at Low Current 

Closed at High Current

Control circuit is closed at either 

over or under current conditions. 

Parallel Connection Current Alarm 

(OR wiring) Example

AC

 Cu

rren

t

Setpoint #2

Setpoint #1

Setpoint #2 Contact Action

Setpoint #1 Contact Action

Red Line Indicates Current Rising and Falling

1-2     Closed

Open

Closed

Open

2-3    

   

Open

Open

Closed

Closed

5-6     Closed

Closed

Open

6-7     Open

Open

Closed

Troubleshooting continuted:

B.  Monitored current is below minimum required. 

Loop the monitored wire several times through the aperture 
until the “sensed” current rises above minimum.  Sensed 
Amps = (Actual Amps) x (Number of Loops).  Count loops on 
the inside of the aperture.

C.  Switch  has been overloaded and contacts are burned out. 

Check the output load, remembering to include inrush on 
inductive loads (coils, motors, ballasts). 

3. LEDs do not illuminate.

A.  Power supply is not energized. 
B.  Power supplied is not sufficient, 24VAC/DC (+/-8.3%).

Application Examples

Отзывы: