Description
The ACS035 and ACS400 Series products are powered,
current-operated switches which trigger when sensed
current levels exceed the adjusted setpoint. There are two
independent setpoints, one for higher than normal current and
another for lower than normal, or one for alarm at too high
and the second for shut down at an excessive current level.
The two independent outputs are single pole, double throw
relay contacts.
Installation
The ACS035 and ACS400 switches can be located in the
same environment as motors, contactors, heaters, pull-boxes,
and other electrical enclosures.
Mounting can be made in any position to a panel or a 35mm
DIN rail, or hung directly on wires with a wire tie. Keep at
least one inch clearance between sensor and other magnetic
devices.
Wiring
Run wire to be monitored through aperture (opening) in the
sensor.
For power supply and output wiring, use 30-12AWG copper
wire and tighten terminals to 7 in-lbs torque. Be sure the
output load requirement does not exceed the contact rating.
Connect power supply to terminals 4 and 5 on the sensor.
Check to ensure supply power matches voltage and type
required by sensor. Once powered, the LEDs on the unit
should indicate unit is on by glowing green.
Connect output wiring to be controlled by Setpoint #1 to
terminals 1-2 for the normally closed (opens on current rise)
or 2-3 for the normally open (closes on current rise) contact.
Connect output wiring to be controlled by Setpoint #2 to
terminals 6-7 for the normally closed (opens on current rise)
or 7-8 for the normally open (closes on current rise) contact.
Note that if unit is powered and monitored conductor has
current flow, the output contacts may change state depending
on setpoint adjustment settings.
Power Supply and Output Wiring
24VAC or DC
Power Supply
Common
Common
NO (Closes to Common on Current Rise)
NO (Closes to Common on Current Rise)
NC (Opens to Common on Current Rise)
NC (Opens to Common on Current Rise)
Set Point #1
Adjustment
LED Shows Contact Status
Set Point #2
Adjustment
LED Shows Contact Status
1
2
3
4
5
6
7
8
Setpoint Adjustment
The ACS035 and ACS400 Series setpoints are adjusted
using two 3/4-turn pots which have arrow indication of the
selected value. The arrow points to the current magnitude
which will cause the output relay(s) to energize or change
state. Possible to control one DC circuit and one AC circuit.
Typical Adjustment
1. Turn the setpoint adjustment pot #1 to the point where
you want the first relay to change state.
2. Turn the setpoint adjustment pot #2 to the point where
you want the second relay to change state.
3.
Thread the load conductor(s) through the sensing
aperture. If multiple conductors are used to power the
monitored load, each conductor must be connected to
the same phase.
4. Energize the sensor with 24VAC/DC (+/-8.3%)
5. Both indicating LEDs will be illuminated Green.
6. After energizing the monitored load, if the current used
is over the adjustment level of Setpoint #1 the LED will
change to Amber to indicate that the output relay has
changed state.
7. When the monitored current exceeds the level of Setpoint
#2, that LED will also change from Green to Amber.
8. The most common use would be to adjust Setpoint #1 to
be in the tripped condition during normal load operation,
reverting to “normal” if current falls below that point; and
to have Setpoint #2 adjusted so it is “untripped during
normal operation, and change state in an over current
condition.
9. The output contacts are floating, and can be wired in
parallel (OR wiring) or in series (AND wiring) for a two
wire over/under switch action. See Application Examples.
Troubleshooting
1. Sensor is always tripped.
A. The setpoints may be too low.
Turn pot Clockwise to increase setpoint.
B. Switch has been overloaded and contacts are burned out.
Check the output load, remembering to include inrush on
inductive loads (coils, motors, ballasts)
2. Sensor will not trip.
A. The setpoints may be too high.
Turn pot Counter Clockwise to decrease setpoint.
NC
NC NO
NO
POWER
Closed at Normal
Closed at Normal
Open at Low Current
Open at High Current
Control circuit is open at either
over or under normal current conditions.
Series Over/Under Current Window
(AND wiring) Example
NC
NC NO
NO
POWER
Open at Normal
Open at Normal
Closed at Low Current
Closed at High Current
Control circuit is closed at either
over or under current conditions.
Parallel Connection Current Alarm
(OR wiring) Example
AC
Cu
rren
t
Setpoint #2
Setpoint #1
Setpoint #2 Contact Action
Setpoint #1 Contact Action
Red Line Indicates Current Rising and Falling
1-2 Closed
Open
Closed
Open
2-3
Open
Open
Closed
Closed
5-6 Closed
Closed
Open
6-7 Open
Open
Closed
Troubleshooting continuted:
B. Monitored current is below minimum required.
Loop the monitored wire several times through the aperture
until the “sensed” current rises above minimum. Sensed
Amps = (Actual Amps) x (Number of Loops). Count loops on
the inside of the aperture.
C. Switch has been overloaded and contacts are burned out.
Check the output load, remembering to include inrush on
inductive loads (coils, motors, ballasts).
3. LEDs do not illuminate.
A. Power supply is not energized.
B. Power supplied is not sufficient, 24VAC/DC (+/-8.3%).
Application Examples