background image

 

www.productivity2000.com  

Tech Support 770-844-4200

4

WARNING:

 

To minimize the risk of potential safety problems, you 

should follow all applicable local and national codes that regulate 

the installation and operation of your equipment. These codes vary 

from area to area and it is your responsibility to determine which 

codes should be followed, and to verify that the equipment, instal-

lation, and operation are in compliance with the latest revision of 

these codes.

Equipment damage or serious injury to personnel can result 

from the failure to follow all applicable codes and standards. We 

do not guarantee the products described in this publication are 

suitable for your particular application, nor do we assume any 

responsibility for your product design, installation, or operation.

If you have any questions concerning the installation or opera-

tion of this equipment, or if you need additional information, please 

call Technical Support at 770-844-4200.

This publication is based on information that was available at 

the time it was printed. At AutomationDirect.com® we constantly 

strive to improve our products and services, so we reserve the right 

to make changes to the products and/or publications at any time 

without notice and without any obligation. This publication may also 

discuss features that may not be available in certain revisions of 

the product.

General Specifications

Operating Temperature

0° to 60°C (32° to 140°F)

Storage Temperature

-20° to 70°C (-4° to 158°F)

Humidity

5 to 95% (non-condensing)

Environmental Air

No corrosive gases permitted 

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Field to Logic Side Isolation

1800VAC applied for 1 second

Insulation Resistance

>10M

Ω

 @ 500 VDC

Heat Dissipation 

1800mW

Enclosure Type

Open Equipment

Agency Approvals

UL508 file E139594, Canada & USA

CE (EN61131-2*)

Module Keying to Backplane

Electronic

Module Location

Any I/O slot in a Productivity2000 System.

Field Wiring

Use 

ZIP

Link Wiring System or removable terminal 

block (not included). See “Wiring Options” on 

page 2.

EU Directive

See the “EU Directive” topic in the Productivity 

Suite Help File. Information can also be obtained 

at: www.productivity2000.com

Connector Type (not included) 18 Position Removable Terminal Block
Weight

97.6g (3.4oz)

*Meets EMC and Safety requirements.  See the D.O.C. for details.

LED Status

Fault Condition

Fault

 

Status Indication

Operation to Reset Fault

Missing External 24VDC V1 LED is ON

Apply external 24 VDC

Open Load (Note 1)

F LED is ON (Note 2)

Connect the load

Over Temperature or 

Over Load Current

Turn the output OFF or 

cycle power

Note 1

:  Open Load Fault is always enabled, but is only valid when output is OFF. If Open 

Load Fault happens while output is ON, fault will not appear until you turn OFF 

output.

Note 2

:  The SEL button cycles between the output status and fault status. If the “F” LED is 

OFF the numbered LEDs are showing output status. If the “F” LED is ON the  

numbered LEDs are showing fault status of each output. The “V1” LED is  

independent of fault or output display.

Removable Terminal Block Specifications

Part Number

P2-RTB

P2-RTB-1

Number of 

Positions 

18 Screw Terminals

18 Spring Clamp Terminals

Wire Range 

30-16 AWG (0.051 - 1.31 mm²) 

Solid / Stranded Conductor  

3/64 in. (1.2 mm) Insulation Maximum

1/4 in. (6-7 mm) Strip Length

28-16 AWG (0.081 - 1.31 mm²) 

Solid / Stranded Conductor  

3/64 in. (1.2 mm) Insulation Maximum

19/64 in. (7-8 mm) Strip Length

Conductors

“USE COPPER CONDUCTORS, 75°C” or Equivalent.

Screw Driver 

Width 

0.1 inch (2.5 mm) Maximum*

Screw Size 

M2

N/A

Screw Torque 

2.5 lb·in (0.28 N·m)

N/A

*Recommend Screw Driver TW-SD-MSL-1