DPM2-E Electrical User Manual, 1st Edition
User Manual - DPM2-E Series Electrical Panel Meters
16
In “
SCAL
” method, all values must be manually introduced through the
three frontal keys whereas in “
tEAC
” method, input signal value must be
present at the conector at each point that is intended to be configured.
FIRST POINT INPUT AND DISPLAY VALUE:
InP1
: Input value indication.
000:
Value entered in counts within available model display range.
dSP1
: Display value indication.
0000
: Value entered in counts within display range.
DECIMAL POINT:
00.00
: Setting of decimal point position. (Decimal point can be located in
any position, and will be the same for Display 1 and Display 2. This
position remains fixed for all configuration steps and also for RUN
mode).
SECOND POINT INPUT AND DISPLAY VALUE:
InP2
: Input value indication.
0000
: Value entered in counts within display range.
dSP2
: Display value indication.
0000
: Value entered in counts within display range.
WEIGHTED AVERAGE FILTER:
FiLt:
0 to 9 selectable for low pass filter cut-off frequency.
Value Fc (Hz) Value Fc (Hz)
0
--
5
2.2
1
7.3
6
1.6
2
5.1
7
1.1
3
3.8
8
0.5
4
2.9
9
0.2
.