background image

DPM2-E Electrical User Manual, 1st Edition

User Manual - DPM2-E Series Electrical Panel Meters

12

Configuration

When the power is applied to the meter, a display test begins automatically to check the  

function of LED’s and digits. Once this test is finished the display shows the internal software 

version and then the unit goes to 

RUN

 mode.

Configuration follows a structure composed of a number of menus and submenus. By pressing 

ENTER

 key, display shows 

“Pro”,

 pressing again allows access to the main menu level which 

includes the menus for input configuration (

InP

), display configuration (

dSP

) and relay 

setpoints configuration (

SEtP

) if relays are present in the meter.

If configuration has been totally locked-out, when pressing 

ENTER

 key to get into main menu, 

display shows “

dAtA

” instead of “

Pro

”. This indicates that it is only possible to see programmed 

information and that it is not allowed to modify any parameter from the entire configuration. In 

this visualization mode, the meter automatically switches back to 

RUN 

mode after 15 seconds 

since last key press.

     



   

MAIN MENU 











       

ENTER

:

 

Vertical displacement / Validates data.

 

UP

:

 

Increases active digit value.

 

SHIFT

:

 

Horizontal displacement / Changes active digit.

 

Once inside each menu, all configuration parameters are sequentially shown and they can then 

be introduced or edited by pressing 

ENTER

 key. Numeric values must be entered digit by digit, 

first selecting digit and then changing its value. When the desired display value is reached, press 

the 

ENTER

 key to validate the data and move forward to next configuration step.

Data entered or changed during configuration are stored in device memory only when 

configuration routine belonging to the respective submenu is completed, not before. On last 

routine step and after having pressed 

ENTER

 key, display indicates “

StorE

” and the unit goes 

back again to 

RUN

 mode.

Input Configuration

The first menu corresponds to input configuration. This, in turn, consists of four submenus, 

one for each input type: DC voltage (

UDC

), AC voltage (

UAC

), DC current (

AdC

) and AC 

current (

AAC

).

Содержание ProSense DPM2-E Series

Страница 1: ...ProSense DPM2 E Series Digital Panel Meter for ac or dc voltage and amperage electrical input signals Models DPM2 E HL DPM2 E 2R HL User Manual...

Страница 2: ...nals 7 Wiring Examples 9 1A DC and 0 1A AC Input Ranges Wiring 9 5A DC and 0 5A AC Input Ranges Wiring 9 60mV DC 100mV DC and 0 60mV AC 0 100mV AC Shunt Input Ranges Wiring 10 20V DC and 0 20V AC Inpu...

Страница 3: ...l User Manual 1st Edition User Manual DPM2 E Series Electrical Panel Meters 3 Configuration Lock Out Continued 21 Configuration Lock Out Continued 22 Technical Specifications 23 Instrumentation Config...

Страница 4: ...legislation regarding waste of electrical and electronic equipment from products put on the market after August 13 2005 the user can give it back without any cost to the place where it was acquired to...

Страница 5: ...about our products and our company www AutomationDirect com Agency Approvals Description The ProSense DPM2 E series offers a simple low cost digital display of AC or DC voltage or amperage electrical...

Страница 6: ...AC DC current input 1A 5A shunt 60mV shunt 100mV AC or DC powered Optional 2 Form C SPDT relays N O or N C operation Activation on increasing or decreasing input signal Hysteresis or time delay opera...

Страница 7: ...from the panel pull the rear fixing clips latching tabs outwards until they are disengaged then slide the fixing clips back over the case Wiring Terminals CN3 1 2 CN2 1 2 3 4 5 6 7 CN1 CN4 1 2 3 4 5...

Страница 8: ...te to signal terminals CN2 and power terminals CN1 2500Vrms for 1 minute to signal terminals CN2 and relays terminals CN3 or CN4 2500Vrms for 1 minute to power terminals CN1 and relays terminals CN3 o...

Страница 9: ...gauge and length should be used to prevent the total resistance of the measuring circuit R1 R2 Ri from exceeding the Burden rating of current transformer 5A DC and 0 5A AC Input Ranges Wiring DC AC D...

Страница 10: ...the shunt and the DPM meter 20V DC and 0 20V AC Input Ranges Wiring N L DPM2 E 1 5 V 20V DC AC MAX DC AC 20V RANGE CONNECTION 200V DC 600V DC and 0 200V AC 0 600V AC Input Ranges Wiring DC AC 200V RAN...

Страница 11: ...Illuminates for negative readings Illuminates for negative values 3 Key Pad 4 Setpoint 1 LED Illuminates when setpoint 1 turns active Illuminates when setpoint 1 turns active 5 UP key No application S...

Страница 12: ...ntire configuration In this visualization mode the meter automatically switches back to RUN mode after 15 seconds since last key press MAIN MENU ENTER Vertical displacement Validates data UP Increases...

Страница 13: ...C 20 Available range options for DC and AC input voltage are identical Signal Ranges V DC 600V 200V or 20V V AC 0 600V 0 200V or 0 20V DC and AC Current AdC 5A 1A AAC 60 100 Available range options fo...

Страница 14: ...the meter at the CN2 input connector and operational Display values are configured manually through the three keys as in the previous case This method is suitable when signal values at each point are...

Страница 15: ...st DISP 1 In an increasing mode display value increases proportionally to the input value whereas in a decreasing mode display value decreases Direct acting increasing proportional mode Reverse acting...

Страница 16: ...e indication 0000 Value entered in counts within display range DECIMAL POINT 00 00 Setting of decimal point position Decimal point can be located in any position and will be the same for Display 1 and...

Страница 17: ...to be configured are the following SETPOINT VALUE 00 00 Value entered in counts within display range The decimal point position is previously defined in display configuration menu ACTIVATING MODE Hi H...

Страница 18: ...ecreasing Asymmetrical Hysteresis Both relay output actions can be controlled by a hysteresis level which is configurable in counts within full available display Decimal point position is the previous...

Страница 19: ...minimum value and finally a third pressing shows run before returning to RUN mode RESET function is activated while visualizing maximum or minimum values and the SHIFT key is pressed for at least 3 s...

Страница 20: ...ation lock out is available By default the unit is delivered unlocked giving access to all programming levels Once in this menu the first option will be to choose between lock out level setting LiSt o...

Страница 21: ...ng main menu initial indication will be dAtA instead of Pro On the other hand when no option is selected routine moves on to next step to configure a selective lock out When a selective lock out is se...

Страница 22: ...to visualize maximum or minimum values by pressing SHIFT key although instrument internally continues detecting and saving new extreme values reached by input signal Once the instrument programming is...

Страница 23: ...V EMI max Influence 20V 10mV 200V 100mV 600V 300mV 0 to 20V 20mV 0 to 200V 200mV 0 to 600V 600mV 1A 500 A 5A 2 5mA Shunt 60mV 30 V Shunt 100mV 50 V 0 to 1A 1mA 0 to 5A 5mA Shunt 60mV 60 V Shunt 100mV...

Страница 24: ...8A at 250VAC 24VDC Maximum switching current resistive load 8A Maximum switching power 2000VA 192W Maximum switching voltage 400VAC 125VDC Contact resistance 100m at 6VDC 1A Contact type SPDT Operate...

Страница 25: ...DPM2 E Series Electrical Panel Meters 25 Instrumentation Configuration Notes INPUT TYPE RANGE DISPLAY CONFIG MODE INPUT 1 DISPLAY 1 INPUT 2 DISPLAY 2 FILTER 0 9 SETPOINTS SET1 MODE DLY HYS SET2 MODE D...

Отзывы: