DPM2-E Electrical User Manual, 1st Edition
User Manual - DPM2-E Series Electrical Panel Meters
23
Technical Specifications
Technical Specifications
Input
DC Voltage
AC Voltage
DC Current
AC Current
Range....Input
Impedance
±20V....100kΩ
±200V....1MΩ
±600V....3MΩ
0 to 20V....100kΩ
0 to 200V....1MΩ
0 to 600V....3MΩ
±1A....70mΩ
±5A....14mΩ
Shunt ±60mV....2.5 kΩ
Shunt ±100mV....2.5 kΩ
0 to 1A....70mΩ
0 to 5A....14mΩ
Shunt 0 to 60mV....2.5 kΩ
Shunt 0 to 100mV....2.5 kΩ
Input
Frequency
Range
–
45 Hz to 1 kHz sine wave
–
45 Hz to 1 kHz sine wave
Maximum
Permanent
Overload
±20V.....100V
±200V....600V
±600V...1000V
0 to 20V.....100V
0 to 200V....600V
0 to 600V...1000V
±1A....1.2 A
±5A....7A
±60mV....20V
±100mV....20V
0 to 1A....1.2 A
0 to 5A....7A
0 to 60mV....20V
0 to 100mV....20V
EMI max.
Influence
±20V.....±10mV
±200V....±100mV
±600V....±300mV
0 to 20V.....±20mV
0 to 200V....±200mV
0 to 600V....±600mV
±1A.... ±500µA
±5A....±2.5mA
Shunt 60mV....±30µV
Shunt 100mV....±50µV
0 to 1A.... ±1mA
0 to 5A....±5mA
Shunt 60mV....±60µV
Shunt 100mV....±100µV
Resolution
±20V....1mV
±200V....10mV
±600V....25mV
0 to 20V....1mV
0 to 200V....10mV
0 to 600V....25mV
±1A....50µA
±5A....200µA
Shunt ±60mV....5µV
Shunt ±100mV....10µV
0 to 1A....50µA
0 to 5A....200µA
Shunt 0 to 60mV....5µV
Shunt 0 to 100mV....10µV
Accuracy
±20V....±(0.05%rdg +
25mV)
±200V....±(0.05%rdg +
250mV)
±600V....±(0.05%rdg +
0.7V)
0 to 20V....±(0.35%rdg +
30mV)
0 to 200V....±(0.25%rdg
+ 0.3V)
0 to 600V....±(0.1%rdg +
0.9V)
±1A....±(0.05%rdg + 1mA)
±5A....±(0.05%rdg + 6mA)
Shunt ±60mV....±(0.05%rdg +
70µV)
Shunt ±100mV....±(0.05%rdg
+ 120µV)
0 to 1A....±(0.1%rdg + 5mA)
0 to 5A....±(0.1%rdg + 20mA)
Shunt 0 to 60mV....±(0.1%rdg +
300µV)
Shunt 0 to 100mV....±(0.1%rdg
+ 300µV)
Accuracy
Conditions
5 minutes warmup time
23°C +/-5°C ambient temperature
100 ppm/°C temperature coefficient (200 ppm/°C for AC Amp input)