Minimum Mounting Clearances
Frame A
GS4-21P0; GS4-41P0; GS4-22P0; GS4-42P0; GS4-23P0; GS4-43P0; GS4-25P0; GS4-45P0; GS4-47P5
Frame B
GS4-27P5; GS4-2010; GS4-4010; GS4-2015; GS4-4015; GS4-4020
Frame C
GS4-2020; GS4-2025; GS4-4025; GS4-2030; GS4-4030; GS4-4040
Frame D0 GS4-4050; GS4-4060
Frame D
GS4-2040; GS4-2050; GS4-4075; GS4-4100
Frame E
GS4-2060; GS4-2075; GS4-2100; GS4-4125; GS4-4150
Frame F
GS4-4175; GS4-4200
Frame G
GS4-4250; GS4-4300
←
(Blue Arrow) Inflow
←
(Red Arrow) Outflow
(Frame A~G)
Single drive:
Independent installation.
(Frame A, B, C, G)
Multiple drives:
Independent horizontal installation.
(Frame D0, D, E, F)
Multiple drives:
Independent horizontal installation.
Install a barrier between the drives.
(Frame A~G)
Multiple drives:
Independent installation.
Ta: Frame A~G
(inflow air temperature)
It is suggested to install a barrier
between the drives. Adjust
the size of the barrier until the
temperature of the fan on the
inflow side is lower than the
operation temperature. This barrier
is to prevent the lower drives’ hot
exhaust from going straight into
the upper drives’ intake.
(Refer to the right figure)
Operation temperature is the
temperature measured 50mm away
from the inflow side of the fan.
Minimum Mounting Clearance
Frame
A (mm / in)
B (mm / in)
C (mm / in)
D (mm / in)
A~C
60 / 2.4
30 / 1.2
10 / 0.4
0 / 0
D0~F
100 / 4.0
50 / 2.0
n/a
0 / 0
G
200 / 7.9
100 / 4.0
n/a
0 / 0
Note:
• The mounting clearances shown in figure to the left are NOT for installing the
GS4 drive in a confined space (such as cabinet or electric box). When installed in
a confined space, in addition to the minimum mounting clearances, ventilation
equipment or air conditioning should be installed to keep the surrounding
temperature lower than the operation temperature.
• The following table shows heat dissipation and required air volume when installing
a single GS4 drive in a confined space. When installing multiple drives, the required
air volume shall be multiplied by the number of GS4 drives.
• Refer to the chart (Air flow rate for cooling) for ventilation equipment design and
selection.
• Refer to the chart (Power Dissipation) for air conditioner design and selection.
• If GS4 drives in frames sizes A thru D are installed with clearance dimensions less
than specified, the cooling fans in these models may not adequately cool the drive.
Specifications for Wiring Terminals – Main-Circuit Terminals
Drive Models
Max Wire
Gauge
Min Wire
Gauge
Torque
(±10%)
Note
Fr
ame A
GS4-21P0
8 AWG
(8.4 mm
2
)
14 AWG
(2.1 mm
2
)
M4
20 kg·cm
(17.4 lb·in)
(1.96 N·m)
UL installations must use 600V, 75°C or 90°C wire.
Please use copper wire only.
(Fig. 1) The usage of ring terminals should comply
with this specification.
(Fig. 2) The figure shows the specification of insulated
heat shrink tubing that complies with UL
(600C, YDPU2).
Figure 1:
Figure 2:
GS4-22P0
12 AWG
(3.3 mm
2
)
GS4-23P0
10 AWG
(5.3 mm
2
)
GS4-25P0
8 AWG
(8.4 mm
2
)
GS4-41P0
14 AWG
(2.1 mm
2
)
GS4-42P0
GS4-43P0
GS4-45P0
10 AWG
(5.3 mm
2
)
GS4-47P5
Fr
ame B
GS4-27P5
4 AWG
(21.2 mm
2
)
8 AWG
(8.4 mm
2
)
M5
35 kg·cm
(30.4 lb·in)
(3.43 N·m)
Terminal D+[+2 & +1]: Torque 45 Kg·cm [39.0 lb·in]
(4.415 N·m) (±10%)
Use 600V, 90°C wire for UL installation of GS4-2015
install if ambient temperature exceeds 45°C.
UL installations of other models must use 600V, 75°C
or 90°C wire. Please use copper wire only.
(Fig. 1) The usage of ring terminals should comply
with this specification.
(Fig. 2) The figure shows the specification of insulated
heat shrink tubing that complies with UL
(600C, YDPU2).
Figure 1:
Figure 2:
GS4-2010
6 AWG
(13.3 mm
2
)
GS4-2015
4 AWG
(21.2 mm
2
)
GS4-4010
8 AWG
(8.4 mm
2
)
GS4-4015
GS4-4020
6 AWG
(13.3 mm
2
)
Specifications for Wiring Terminals – Main-Circuit Terminals (continued)
Drive Models
Max Wire
Gauge
Min Wire
Gauge
Torque
(±10%)
Note
Fr
ame C
GS4-2020
1/0 AWG
(53.5 mm
2
)
1 AWG
(42.4 mm
2
)
M8
80 kg·cm
(69.4 lb·in)
(7.85 N·m)
Terminal D+[+2 & +1]: Torque 90 Kg-cm [78.2 lb-in.]
(8.83Nm) (±10%)
Use 600V, 90°C wire for UL installation of GS4-2030
install if ambient temperature exceeds 40°C.
UL installations of other models must use 600V, 75°C
or 90°C wire. Please use copper wire only.
(Fig. 1) The usage of ring terminals should comply
with this specification.
(Fig. 2) The figure shows the specification of insulated
heat shrink tubing that complies with UL (600C,
YDPU2).
Figure 1:
Figure 2:
GS4-2025
1/0 AWG
(53.5 mm
2
)
GS4-2030
GS4-4025
4 AWG
(21.2 mm
2
)
GS4-4030
GS4-4040
2 AWG
(33.6 mm
2
)
Fr
ame D0
For models without conduit box
M8
81.6 kg·cm
(70.8 lb·in)
(8N·m)
UL installations must use 600V, 75°C or 90°C wire.
Please use copper wire only.
(Fig. 1) The usage of ring terminals should comply
with this specification.
(Fig. 2) Ground wire spec: 2AWG*2 [33.6mm
2
*2]
(Fig. 3) The figure shows the specification of insulated
heat shrink tubing that complies with UL
(600C, YDPU2).
GS4-4050
2/0 AWG
(67.4 mm
2
)
1/0 AWG
(53.5 mm
2
)
GS4-4060
2/0 AWG
(67.4 mm
2
)
For models with conduit box
Figure 1:
+0 -2
8.2 Min.
Ring lug
Figure 2:
Ring lug
22 Max.
8.2 Min.
11
M
ax
.
32
M
ax
.
GS4-4050
2/0 AWG
(67.4 mm
2
)
1/0 AWG
(53.5 mm
2
)
GS4-4060
Figure
3:
WIRE
Heat Shrink Tube
13
M
in
.
WIRE
Heat Shrink Tube
13
M
in
.
13
¡Ó1
.5
Fr
ame D
For models without conduit box
M8
200 kg·cm
(173 lb·in)
(19.62 N·m)
UL installations must use 600V, 75°C or 90°C wire.
Please use copper wire only.
(Fig. 1) The usage of ring terminals should comply
with this specification.
(Fig. 2) The figure shows the specification of insulated
heat shrink tubing that complies with UL
(600C, YDPU2).
Figure 1:
Figure 2:
GS4-2040
300 MCM
(152 mm
2
)
4/0 AWG
(107 mm
2
)
GS4-2050
250 MCM
(127 mm
2
)
GS4-4075
3/0 AWG
(85mm
2
)
GS4-4100
300 MCM
(152 mm
2
)
For models with conduit box
GS4-2040
4/0 AWG
(107 mm
2
)
3/0 AWG
(85 mm
2
)
GS4-2050
4/0 AWG
(107 mm
2
)
GS4-4075
2/0 AWG
(67.4 mm
2
)
GS4-4100
4/0 AWG
(107 mm
2
)