 GS4 AC Drive Quick-Start Guide – 1st Ed, Rev.C  07/02/2021

DURA

pulse

 GS4 AC Drive Quick-Start Guide

GS4_QSP_1edRevC 07/02/2021

Minimum Mounting Clearances

Frame A

GS4-21P0; GS4-41P0; GS4-22P0; GS4-42P0; GS4-23P0; GS4-43P0; GS4-25P0; GS4-45P0; GS4-47P5

Frame B

GS4-27P5; GS4-2010; GS4-4010; GS4-2015; GS4-4015; GS4-4020

Frame C

GS4-2020; GS4-2025; GS4-4025; GS4-2030; GS4-4030; GS4-4040

Frame D0 GS4-4050; GS4-4060
Frame D

GS4-2040; GS4-2050; GS4-4075; GS4-4100

Frame E

GS4-2060; GS4-2075; GS4-2100; GS4-4125; GS4-4150

Frame F

GS4-4175; GS4-4200

Frame G

GS4-4250; GS4-4300

 (Blue Arrow) Inflow 

 

 (Red Arrow) Outflow

(Frame A~G)

Single drive:   

Independent installation.

(Frame A, B, C, G)

Multiple drives:  

Independent horizontal installation.

(Frame D0, D, E, F)

Multiple drives:  

Independent horizontal installation.

Install a barrier between the drives.

(Frame A~G)

Multiple drives:  

Independent installation.

Ta: Frame A~G

(inflow air temperature)

It is suggested to install a barrier 

between the drives.  Adjust 

the size of the barrier until the 

temperature of the fan on the 

inflow side is lower than the 

operation temperature.  This barrier 

is to prevent the lower drives’ hot 

exhaust from going straight into 

the upper drives’ intake. 

(Refer to the right figure)

Operation temperature is the 

temperature measured 50mm away 

from the inflow side of the fan.

Minimum Mounting Clearance

Frame

A (mm / in)

B (mm / in)

C (mm / in)

D (mm / in)

A~C

60 / 2.4

30 / 1.2

10 / 0.4

0 / 0

D0~F

100 / 4.0

50 / 2.0

n/a

0 / 0

G

200 / 7.9

100 / 4.0

n/a

0 / 0

Note:

•  The mounting clearances shown in figure to the left are NOT for installing the 

GS4 drive in a confined space (such as cabinet or electric box).  When installed in 

a confined space, in addition to the minimum mounting clearances, ventilation 

equipment or air conditioning should be installed to keep the surrounding 

temperature lower than the operation temperature.

•  The following table shows heat dissipation and required air volume when installing 

a single GS4 drive in a confined space.  When installing multiple drives, the required 

air volume shall be multiplied by the number of GS4 drives.

•  Refer to the chart (Air flow rate for cooling) for ventilation equipment design and 

selection.

•  Refer to the chart (Power Dissipation) for air conditioner design and selection.

•  If GS4 drives in frames sizes A thru D are installed with clearance dimensions less 

than specified, the cooling fans in these models may not adequately cool the drive.

Specifications for Wiring Terminals – Main-Circuit Terminals

Drive Models

Max Wire 

Gauge

Min Wire 

Gauge

Torque 

(±10%)

Note

Fr

ame A

GS4-21P0

8 AWG  

(8.4 mm

2

)

14 AWG 

(2.1 mm

2

)

M4

20 kg·cm

(17.4 lb·in)

(1.96 N·m)

UL installations must use 600V, 75°C or 90°C wire. 

Please use copper wire only.

(Fig. 1)  The usage of ring terminals should comply 

with this specification.

(Fig. 2)  The figure shows the specification of insulated 

heat shrink tubing that complies with UL 

(600C, YDPU2).

Figure 1:

Figure 2:

GS4-22P0

12 AWG 

(3.3 mm

2

)

GS4-23P0

10 AWG 

(5.3 mm

2

)

GS4-25P0

8 AWG 

(8.4 mm

2

)

GS4-41P0

14 AWG 

(2.1 mm

2

)

GS4-42P0
GS4-43P0

GS4-45P0

10 AWG 

(5.3 mm

2

)

GS4-47P5

Fr

ame B

GS4-27P5

4 AWG 

(21.2 mm

2

)

8 AWG 

(8.4 mm

2

)

M5

35 kg·cm

(30.4 lb·in)

(3.43 N·m)

Terminal D+[+2 & +1]: Torque 45 Kg·cm [39.0 lb·in] 

(4.415 N·m) (±10%)

Use 600V, 90°C wire for UL installation of GS4-2015 

install if ambient temperature exceeds 45°C.

UL installations of other models must use 600V, 75°C 

or 90°C wire.  Please use copper wire only.

(Fig. 1)  The usage of ring terminals should comply 

with this specification.

(Fig. 2)  The figure shows the specification of insulated 

heat shrink tubing that complies with UL 

(600C, YDPU2).

Figure 1:

Figure 2:

GS4-2010

6 AWG 

(13.3 mm

2

)

GS4-2015

4 AWG 

(21.2 mm

2

)

GS4-4010

8 AWG 

(8.4 mm

2

)

GS4-4015

GS4-4020

6 AWG 

(13.3 mm

2

)

Specifications for Wiring Terminals – Main-Circuit Terminals (continued)

Drive Models

Max Wire 

Gauge

Min Wire 

Gauge

Torque 

(±10%)

Note

Fr

ame C

GS4-2020

1/0 AWG 

(53.5 mm

2

)

1 AWG 

(42.4 mm

2

)

M8

80 kg·cm

(69.4 lb·in)

(7.85 N·m)

Terminal D+[+2 & +1]: Torque 90 Kg-cm [78.2 lb-in.] 

(8.83Nm) (±10%)

Use 600V, 90°C wire for UL installation of GS4-2030 

install if ambient temperature exceeds 40°C.

UL installations of other models must use 600V, 75°C 

or 90°C wire.  Please use copper wire only.

(Fig. 1)  The usage of ring terminals should comply 

with this specification.

(Fig. 2)  The figure shows the specification of insulated 

heat shrink tubing that complies with UL (600C, 

YDPU2).

Figure 1:

Figure 2:

GS4-2025

1/0 AWG 

(53.5 mm

2

)

GS4-2030
GS4-4025

4 AWG 

(21.2 mm

2

)

GS4-4030

GS4-4040

2 AWG 

(33.6 mm

2

)

Fr

ame D0

For models without conduit box

M8

81.6 kg·cm

(70.8 lb·in)

(8N·m)

UL installations must use 600V, 75°C or 90°C wire.  

Please use copper wire only.

(Fig. 1)  The usage of ring terminals should comply 

with this specification.

(Fig. 2)  Ground wire spec: 2AWG*2 [33.6mm

2

*2]

(Fig. 3)  The figure shows the specification of insulated 

heat shrink tubing that complies with UL 

(600C, YDPU2).

GS4-4050

2/0 AWG 

(67.4 mm

2

)

1/0 AWG 

(53.5 mm

2

)

GS4-4060

2/0 AWG 

(67.4 mm

2

)

For models with conduit box

Figure 1:

+0 -2

8.2 Min.

Ring lug

Figure 2:

Ring lug

22 Max.

8.2 Min.

11

 M

ax

.

32

 M

ax

.

GS4-4050

2/0 AWG 

(67.4 mm

2

)

1/0 AWG 

(53.5 mm

2

)

GS4-4060

  Figure 

3:

WIRE

Heat Shrink Tube

13

 M

in

.

WIRE

Heat Shrink Tube

13

 M

in

.

13

¡Ó1

.5

Fr

ame D

For models without conduit box

M8

200 kg·cm

(173 lb·in)

(19.62 N·m)

UL installations must use 600V, 75°C or 90°C wire.  

Please use copper wire only.

(Fig. 1)  The usage of ring terminals should comply 

with this specification.

(Fig. 2)  The figure shows the specification of insulated 

heat shrink tubing that complies with UL 

(600C, YDPU2).

Figure 1:

 

Figure 2:

GS4-2040

300 MCM  

(152 mm

2

)

4/0 AWG 

(107 mm

2

)

GS4-2050

250 MCM 

(127 mm

2

)

GS4-4075

3/0 AWG 

(85mm

2

)

GS4-4100

300 MCM 

(152 mm

2

)

For models with conduit box
GS4-2040

4/0 AWG  

(107 mm

2

)

3/0 AWG 

(85 mm

2

)

GS4-2050

4/0 AWG 

(107 mm

2

)

GS4-4075

2/0 AWG 

(67.4 mm

2

)

GS4-4100

4/0 AWG 

(107 mm

2

)

Содержание DURApulse GS4

Страница 1: ...ardware so that the motor cannot produce torque This method of removing power from the motor is considered an emergency stop also known as coast to stop To use this feature disconnect the appropriate...

Страница 2: ...er to P3 00 P3 01 P4 00 and P4 01 for defining LOCAL and REMOTE sources of operation and frequency Descriptions of LED Functions Steady ON Drive is running Blinking Drive is stopping or in base block...

Страница 3: ...e five menus described in the following table Then set the applicable parameters for that application as shown Please refer to the user manual if you need more detailed information about the parameter...

Страница 4: ...VDC 390 0 780 0 11 P6 29 Line Start Lockout 0 Enable start up lockout 1 Disable start up lockout 0 12 P6 31 Cooling Fan Control 0 Always ON 1 Fan OFF 1 minute after Stop 2 Run fan ON Stop fan OFF 3 He...

Страница 5: ...Rate for Cooling Power Dissipation Model Number Flow Rate cfm Flow Rate m3 hr Power Dissipation Watt External Internal Total External Internal Total Loss External Heat sink Internal Total GS4 21P0 33...

Страница 6: ...cification Fig 2 The figure shows the specification of insulated heat shrink tubing that complies with UL 600C YDPU2 Figure 1 Figure 2 GS4 22P0 12 AWG 3 3 mm2 GS4 23P0 10 AWG 5 3 mm2 GS4 25P0 8 AWG 8...