Specifications for Wiring Terminals – Main-Circuit Terminals (continued)

Drive Models

Max Wire 

Gauge

Min Wire 

Gauge

Torque 

(±10%)

Note

Fr

ame E

For models without conduit box

M8

200 kg·cm

(173 lb·in)

(19.62 N·m)

UL installations must use 600V, 75°C or 90°C wire.  

Please use copper wire only.

(Fig. 1)  The usage of ring terminals should comply 

with this specification.

(Fig. 2)  Grounding wire specification: 

• 300MCM*2 [152 mm

2

*2] 

• Torque M8 180 kg·cm 

   [156 lb·in] (17.64 N·m) (±10%)

(Fig. 3)  The figure shows the specification of insulated 

heat shrink tubing that complies with UL 

(600C, YDPU2).

Figure 1:

 

31MAX.

8.2MIN.

26.5MAX.

70

M

A

X

.

16

+0 -4

 

Figure 2:

 

8.2MIN.

65

.0

M

AX

.

17

.0

M

AX

.

28.0MAX.

Figure 3:

 

GS4-2060

300 MCM*2  

(152 mm

2

*2)

1/0 AWG*2 

(53.5 mm

2

*2)

GS4-2075

3/0 AWG*2 

(85 mm

2

*2)

GS4-2100

4/0 AWG*2 

(107 mm

2

*2)

GS4-4125

1/0 AWG*2 

(53.5 mm

2

*2)

GS4-4150

3/0 AWG*2 

(85 mm

2

*2)

For models with conduit box

GS4-2060

4/0 AWG*2  

(107 mm

2

*2)

1/0 AWG*2 

(53.5 mm

2

*2)

GS4-2075

2/0 AWG*2

(67.4 mm

2

*2)

GS4-2100

3/0 AWG*2

(85 mm

2

*2)

GS4-4125

1/0 AWG*2

(53.5 mm

2

*2)

GS4-4150

2/0 AWG*2

(67.4 mm

2

*2)

Fr

ame F

For models without conduit box

M8

200kg·cm

(173 lb·in)

(19.62 N·m)

UL installations must use 600V, 75°C or 90°C wire.  

Please use copper wire only.

Grounding wire specification:  

300MCM*2 [152 mm

2

*2].

(Fig. 1)  The usage of ring terminals should comply 

with this specification.

(Fig. 2)  The figure shows the specification of insulated 

heat shrink tubing that complies with UL 

(600C, YDPU2).

Figure 1:

 

31MAX.

8.2MIN.

26.5MAX.

70

M

A

X

.

16

+0 -4

 

Figure 2:

 

GS4-4175

300 MCM*2

(152 mm

2

*2)

4/0 AWG*2

(107 mm

2

*2)

GS4-4200

300 MCM*2 

(152 mm

2

*2)

For models with conduit box
GS4-4175

4/0 AWG*2

(107 mm

2

*2)

3/0 AWG*2 

(85mm

2

*2)

GS4-4200

4/0 AWG*2 

(107 mm

2

*2)

Fr

ame G

For main circuit terminals:

R/L11, R/L12, S/L21, S/L22, T/L31, T/L32

M8

200 kg·cm

(173 lb·in)

(19.62 N·m)

Use 600V, 90°C wired for UL installation for GS4-4300; 

install in ambient temperature that exceeds 45°C.

UL installations of other models must use 600V, 75°C 

or 90°C wire.

Please use copper wire only.

(Fig. 1)  The usage of ring terminals for R/L11, R/L12, 

S/L21, S/L22, T/L31, and T/L32 should comply 

with this specification.

(Fig. 2)  The usage of ring terminals for U/T1, V/T2, W/

T3, +1/DC+, and -/DC- should comply with 

this specification.

(Fig. 3 & 4)  The figure shows the specification of 

insulated heat shrink tubing that complies 

with UL (600C, YDPU2).

Figure 1:

31MAX.

Ø8.2MIN.

Ø26.5MAX.

54

M

A

X

.

16

+0 -4

 

Figure 2:

 

42.0(MAX.)

12.2(MIN.)

21

.0

(M

A

X

.)

70

.0

(M

A

X

.)

42.0(MAX.)

Figure 3:

 

Figure 4:

 

For models without conduit box
GS4-4250

300 MCM*4 

(152 mm

2

*4)

2/0 AWG*4 

(67.4 mm

2

*4)

GS4-4300

3/0 AWG*4

(85mm

2

*4)

For models with conduit box
GS4-4250

300 MCM*4  

(152 mm

2

*4)

1/0 AWG*4 

(53.5 mm

2

*4)

GS4-4300

2/0 AWG*4 

(67.4 mm

2

*4)

For main circuit terminals:

U/T1, V/T2, W/T3, +1/DC+, -/DC-

M12

408 kg·cm

(354 lb·in)

(40 N·m)

For models without conduit box
GS4-4250

500 MCM*2

(253 mm

2

*2)

400 MCM*2

(203 mm

2

*2

GS4-4300

500 MCM*2

(253mm

2

*2)

For model with conduit box
GS4-4250

500 MCM*2

(253 mm

2

*2)

300 MCM*2

(152 mm

2

*2)

GS4-4300

400 MCM*2

(203 mm

2

*2)

Dimension Diagrams

GS4 Frame A

Units = mm [in]     

W1

W

H1

H

D

Ø3

Ø3

D1

Ø1

Ø1

Ø2

S1

S1

See Detail A

See Detail B

Detail A (Mounting Hole)

Detail B (Mounting Hole)

Frame A:  GS4-21P0; GS4-22P0, GS4-23P0, GS4-25P0, GS4-41P0, GS4-42P0, GS4-43P0, GS4-45P0, GS4-47P5

W

H

D

W1

H1

D1*

S1

Φ1

Φ2

Φ3

130.0 

[5.12]

250.0 

[9.84]

170.0 

[6.69]

116.0 

[4.57]

236.0 

[9.29]

45.8 

[1.80]

6.2 

[0.24]

22.2 

[0.87]

34.0 

[1.34]

28.0 

[1.10]

*D1 = Flange mounting.

Dimension Diagrams
GS4 Frame B

Units = mm [in]     

  Detail A (Mounting Hole)

  Detail B (Mounting Hole)

  See Detail A

  See Detail B

S1

S1

D1

Ø3

Ø1

Ø2

Ø1

Ø3

Ø1

D

W

H

W1

H1

Frame B:  GS4-27P5, GS4-2010, GS4-2015, GS4-4010, GS4-4015, GS4-4020

W

H

D

W1

H1

D1*

S1

Φ1

Φ2

Φ3

190.0

[7.48]

320.0

[12.60]

190.0

[7.48

173.0

[6.81]

303.0

[11.93]

77.9

[3.07]

8.5

[0.33

22.2

[0.87]

34.0

[1.34]

28.0

[1.10]

*D1 = Flange mounting.

GS4 Frame C

Units = mm [in]     

W1

W

H1

H

D

Ø1

Ø1

Ø3

Ø1

Ø1

Ø2

Ø3

D1

S1

S1

Detail A (Mounting Hole)

Detail B (Mounting Hole)

  See Detail A

  See Detail B

Frame C:  GS4-2020, GS4-2025, GS4-2030, GS4-4025, GS4-4030, GS4-4040

W

H

D

W1

H1

D1*

S1

Φ1

Φ2

Φ3

250.0

[9.84]

400.0

[15.75]

210.0

[8.27]

231.0

[9.09]

381.0

[15.00]

92.9

[3.66]

8.5

[0.33]

22.2

[0.87]

34.0

[1.34]

34.0

[1.34]

*D1 = Flange mounting.

Содержание DURApulse GS4

Страница 1: ...ardware so that the motor cannot produce torque This method of removing power from the motor is considered an emergency stop also known as coast to stop To use this feature disconnect the appropriate...

Страница 2: ...er to P3 00 P3 01 P4 00 and P4 01 for defining LOCAL and REMOTE sources of operation and frequency Descriptions of LED Functions Steady ON Drive is running Blinking Drive is stopping or in base block...

Страница 3: ...e five menus described in the following table Then set the applicable parameters for that application as shown Please refer to the user manual if you need more detailed information about the parameter...

Страница 4: ...VDC 390 0 780 0 11 P6 29 Line Start Lockout 0 Enable start up lockout 1 Disable start up lockout 0 12 P6 31 Cooling Fan Control 0 Always ON 1 Fan OFF 1 minute after Stop 2 Run fan ON Stop fan OFF 3 He...

Страница 5: ...Rate for Cooling Power Dissipation Model Number Flow Rate cfm Flow Rate m3 hr Power Dissipation Watt External Internal Total External Internal Total Loss External Heat sink Internal Total GS4 21P0 33...

Страница 6: ...cification Fig 2 The figure shows the specification of insulated heat shrink tubing that complies with UL 600C YDPU2 Figure 1 Figure 2 GS4 22P0 12 AWG 3 3 mm2 GS4 23P0 10 AWG 5 3 mm2 GS4 25P0 8 AWG 8...

Страница 7: ...t exceeds 45 C UL installations of other models must use 600V 75 C or 90 C wire Please use copper wire only Fig 1 The usage of ring terminals for R L11 R L12 S L21 S L22 T L31 and T L32 should comply...

Страница 8: ...11 22 550 0 21 65 525 0 20 67 492 0 19 37 107 2 4 22 16 0 0 63 11 0 0 43 18 0 0 71 D1 Flange mounting GS4 Frame D with conduit box Units mm in W W1 1 2 3 H H1 H2 S1 S1 SEE DETAIL A DETAIL A MOUNTING H...

Страница 9: ...ge during Accel ovA 8 Overvoltage during Decel ovd 9 Overvoltage during normal speed ovn 10 Overvoltage during Stop ovS 11 Low voltage during Accel LvA 12 Low voltage during Decel Lvd 13 Low voltage d...

Отзывы: