background image

Revised 8/14/02 • U551

7

© 2002 Automated Logic Corporation

Reference Guide

 or the 

Eikon Microblock 

Reference Guide

 for more information 

about the LogiStat microblock.

6. Disconnect the LogiStat Adaptor cable 

from the LogiStat’s LogiPort when 
finished to allow the U551 to read inputs 
from the LogiStat.

Input Wiring

The U551 inputs support the types of signals 
listed below. The LogiStat, LogiStat Plus, and 
LogiStat Pro sensors are supported through 
the module’s LogiStat port. The U551 
provides five inputs: two on the LogiStat port 
and three analog inputs. Refer to Table 1 for 
information about wire length, gauge, and 
shielding. Make sure the U551’s power is off 
before wiring any inputs or outputs.

NOTE

If you are using both flow sensors on 

a UDF, disable the U551’s IN-3 input by 
removing its jumper. Disabling the IN-3 
allows a second flow sensor input (Flow #2) 

on the UDF to be read through the flow 
sensor on the U551.

• Thermistor: Precon type 2 (10kohm at 

77°F). Input voltages should range 
between 0.489V and 3.825V for 
thermistors.

• 0 to 5VDC: When using 0 to 5VDC 

signals, remove the pull up jumpers of 
the U551. The pull up jumpers are 
located behind the input port. You must 
remove the cover to access the pull up 
jumpers. The output impedance of a 0 
to 5VDC source must not exceed 
10kohms. The input impedance of the 
U551 is approximately 1Mohm.

• Dry Contact: A 5VDC wetting voltage is 

used to detect contact position. This 
results in a 0.5mA maximum sense 
current when the contacts are closed.

No pulse accumulation inputs are allowed in 
U551 FBs, except for the override button on 
the LogiStat.

Using the LogiStat

Use Figure 7 and Figure 8 on page 8 to wire a 
LogiStat, LogiStat Plus, or LogiStat Pro to the 
U551.

Automated Logic Corporation recommends a 
specific wire to connect the U551 to the 
LogiStat. This 22AWG solid copper wire is 
available from Magnum Cable Corporation, 
product number A3LOGISTAT.   

 Figure 6. Using the LogiPort

Gnd

24 Va c

G n d

T e m p

S w

LS 5v

U n e t +

U n e t -

U - c o m

O n

O f f

BACnet

U551

9

Rx

6 1

2- Tx out
3- Rx in
5- Gnd
1,6,8- +10Vor floating

Tx

+5V

A P T

5

Exec. 4relay

Isolate Network

ModeSelect

TTL

485

ACCESS

PORT

Supplemental

Power

+5V dc

LogiStat

Port

LogiStat Adaptor Cable

Access

Port

Mode Select

Switch

EIA-232

Port

Exec 4 Relay

Switch

LogiStat

Table 1. Input Wiring Restrictions

Input

Maximum 
Length

Minimum 
Gauge

Shielding

Universal

50 feet
15 meters

24AWG

shielded and 
grounded to 
module’s “-” 
or Gnd 
terminal

LogiStat 
Sensors

100 feet
30 meters

22AWG

unshielded

Содержание U551

Страница 1: ...ed trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions U55 1 Using the U551 2 Specifications 2 Job Start Up 3 Job Start Up for WebCTRL 3 Job Start Up for SuperVision 3 Start Up Checklist 4 Mounting 4 Addressing 4 Power Wiring 4 Communications Wiring 5 Communicating Through the LogiStat Port 6 Input Wiring 7 Using the LogiStat 7...

Страница 2: ...kon User s Guide for more information NOTE To operate this module based on a schedule the UNI must be networked with a gateway module U551 modules have been designed to meet low end high volume terminal control applications As a result time critical applications such as short time delays and trend intervals of less than one minute should not be used with these modules ALC recommends that all time ...

Страница 3: ...need these items to properly start up and support U cards UNI 16 with the U1M module driver UNI 30 with the U3M module driver UNI 32 with the UNM module driver or UNI 59 with the U5M module driver Eikon 3 0a or later Figure 1 U551 Layout and Dimensions Ones Tens Gnd Temp Sw LS5v L o g i S t a t Tx Enclosed Energy 88FO E143900 TYPE 000553 Management Equipment R Run n c Gnd AO 1 DO 5 DO 4 DO 3 DO 2 ...

Страница 4: ...fied This number is shown on the UNI Properties page in WebCTRL or on the UNI Status page in SuperVision Power Wiring The Unet follows the same specifications as a legacy CMnet Refer to the Technical Handbook for details on legacy CMnets Also refer to the Technical Handbook for detailed information on daisy chain star and hybrid wiring configurations There is a special wire available that contains...

Страница 5: ...is unshielded Shielded cable is not required for the Unet In most circumstances you should have a PROT485 within 250 feet of any U line module on the Unet for surge protection However depending on the frequency of electrical surges in your area the 250 foot recommendation may vary For example if you have frequent electrical storms in your area you may want to use more PROT485s if you have few elec...

Страница 6: ...hat it can provide power to the APT If the LED is not on you can provide power to the APT using the Supplemental Power 5V dc connection see Figure 6 on page 7 and the special power cable to a laptop keyboard jack or an external supply such as a 5V dc transformer 3 Define the connection type In SuperVision v3 0 define the connection as Access Port In SuperVision v2 6 define the connection as Direct...

Страница 7: ...behind the input port You must remove the cover to access the pull up jumpers The output impedance of a 0 to 5VDC source must not exceed 10kohms The input impedance of the U551 is approximately 1Mohm Dry Contact A 5VDC wetting voltage is used to detect contact position This results in a 0 5mA maximum sense current when the contacts are closed No pulse accumulation inputs are allowed in U551 FBs ex...

Страница 8: ...le Be sure the U551 s power is off before wiring any inputs or outputs Connect the output wiring to the screw terminals on the module To verify each output s operation lock the output to a known condition on the Function Block s Properties page in WebCTRL or the Parameter page in SuperVision then make sure the equipment operates as specified Using Flow Sensors The U551 controls air flow in the zon...

Страница 9: ...ge in WebCTRL or Parameter page in SuperVision Refer to the Eikon for WebCTRL Microblock Reference Guide or the Eikon Microblock Reference Guide for more information NOTE When installing the UDF be sure to permanently remove the W4 jumper as shown in Figure 12 prior to performing test and balance Writing GFBs for the U55 1 Depending on whether you are using a WebCTRL or a SuperVision system you mu...

Страница 10: ...ence Guide You do not need to use BACnet microblocks when writing the GFB unless you have a BACview Keypad Display connected to the UNI You must then use BACnet point microblocks to access U551 points through the keypad Point Identifiers A point can be identified in WebCTRL by its point number and point type in SuperVision a point is identified by its channel number On both systems expander number...

Страница 11: ...gital 21 IN 2 Thermistor 32 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 Volts 32 0 to 5V Digital 22 Sw Thermistor A3 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 Digital B3 LogiStat Temp Thermistor A1 or A2 45 to 100 F 7 22 to 37 8 C 0 00 0 00 15 88 15 69 LogiStat Thermistor 33 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 IN 3 or UDF 2 Volts 33 0 to 5V Digital 23 UDF 2 Flow CFM Flow inpu...

Отзывы: