Digital Output Wiring

The U551 has five digital outputs that can be 
connected to a maximum of 24 Volts AC/DC 
(see Figure 9). Each output is a dry contact 
(rated at 1A maximum) that is configured as 
normally open.

Be sure the module’s power is off before 
connecting any inputs or outputs.

To verify each output’s operation, lock the 
output to a known condition using the 
Function Block’s Properties page in WebCTRL 
or the Parameter page in SuperVision, then 
make sure the equipment operates as 
specified.

Analog Output Wiring

The U551 has one analog output that 
supports voltage devices from 0 to 10VDC 
(see Figure 10). The device being controlled 
must have a minimum of 2000 Ohms 
resistance measured from its input to ground 
and must share the same ground as the 
module. 

Be sure the U551’s power is off before wiring 
any inputs or outputs. Connect the output 
wiring to the screw terminals on the module. 

To verify each output’s operation, lock the 
output to a known condition on the Function 
Block’s Properties page in WebCTRL or the 
Parameter page in SuperVision, then make 
sure the equipment operates as specified.

Using Flow Sensors

The U551 controls air flow in the zone using:

• a USF (single) or UDF (dual) air flow 

sensor and an actuator connected to 
two digital outputs

In a dual duct system, you can use the 
module’s built-in actuator for one duct and 
the UASF for the other. You must indicate 
which of these methods you are using for 
flow control on the UNI module driver’s 
Properties page in WebCTRL or on the 

 Figure 7. Connecting the LogiStat to the U551

Strip 1/4 inch off the ends of the wires before 
connecting.

 Figure 8. Flip Lever Wiring

 Figure 9. Digital Output Wiring

LogiStat

1 2 3 4

4
3
2
1

LogiStat

U module

LS5v

Sw

Temp

Gnd

G

n

d

T

x

R

x

P

w

r

2. Press black

tab down to
connect wire

1. Insert wire

into opening

DO

DO

BUSS

DO-1

DO-2

24VAC

Gnd

+

 Figure 10. Analog Output Wiring

0 to 10V

+

-

Gnd

AO-1

Содержание U551

Страница 1: ...ed trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions U55 1 Using the U551 2 Specifications 2 Job Start Up 3 Job Start Up for WebCTRL 3 Job Start Up for SuperVision 3 Start Up Checklist 4 Mounting 4 Addressing 4 Power Wiring 4 Communications Wiring 5 Communicating Through the LogiStat Port 6 Input Wiring 7 Using the LogiStat 7...

Страница 2: ...kon User s Guide for more information NOTE To operate this module based on a schedule the UNI must be networked with a gateway module U551 modules have been designed to meet low end high volume terminal control applications As a result time critical applications such as short time delays and trend intervals of less than one minute should not be used with these modules ALC recommends that all time ...

Страница 3: ...need these items to properly start up and support U cards UNI 16 with the U1M module driver UNI 30 with the U3M module driver UNI 32 with the UNM module driver or UNI 59 with the U5M module driver Eikon 3 0a or later Figure 1 U551 Layout and Dimensions Ones Tens Gnd Temp Sw LS5v L o g i S t a t Tx Enclosed Energy 88FO E143900 TYPE 000553 Management Equipment R Run n c Gnd AO 1 DO 5 DO 4 DO 3 DO 2 ...

Страница 4: ...fied This number is shown on the UNI Properties page in WebCTRL or on the UNI Status page in SuperVision Power Wiring The Unet follows the same specifications as a legacy CMnet Refer to the Technical Handbook for details on legacy CMnets Also refer to the Technical Handbook for detailed information on daisy chain star and hybrid wiring configurations There is a special wire available that contains...

Страница 5: ...is unshielded Shielded cable is not required for the Unet In most circumstances you should have a PROT485 within 250 feet of any U line module on the Unet for surge protection However depending on the frequency of electrical surges in your area the 250 foot recommendation may vary For example if you have frequent electrical storms in your area you may want to use more PROT485s if you have few elec...

Страница 6: ...hat it can provide power to the APT If the LED is not on you can provide power to the APT using the Supplemental Power 5V dc connection see Figure 6 on page 7 and the special power cable to a laptop keyboard jack or an external supply such as a 5V dc transformer 3 Define the connection type In SuperVision v3 0 define the connection as Access Port In SuperVision v2 6 define the connection as Direct...

Страница 7: ...behind the input port You must remove the cover to access the pull up jumpers The output impedance of a 0 to 5VDC source must not exceed 10kohms The input impedance of the U551 is approximately 1Mohm Dry Contact A 5VDC wetting voltage is used to detect contact position This results in a 0 5mA maximum sense current when the contacts are closed No pulse accumulation inputs are allowed in U551 FBs ex...

Страница 8: ...le Be sure the U551 s power is off before wiring any inputs or outputs Connect the output wiring to the screw terminals on the module To verify each output s operation lock the output to a known condition on the Function Block s Properties page in WebCTRL or the Parameter page in SuperVision then make sure the equipment operates as specified Using Flow Sensors The U551 controls air flow in the zon...

Страница 9: ...ge in WebCTRL or Parameter page in SuperVision Refer to the Eikon for WebCTRL Microblock Reference Guide or the Eikon Microblock Reference Guide for more information NOTE When installing the UDF be sure to permanently remove the W4 jumper as shown in Figure 12 prior to performing test and balance Writing GFBs for the U55 1 Depending on whether you are using a WebCTRL or a SuperVision system you mu...

Страница 10: ...ence Guide You do not need to use BACnet microblocks when writing the GFB unless you have a BACview Keypad Display connected to the UNI You must then use BACnet point microblocks to access U551 points through the keypad Point Identifiers A point can be identified in WebCTRL by its point number and point type in SuperVision a point is identified by its channel number On both systems expander number...

Страница 11: ...gital 21 IN 2 Thermistor 32 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 Volts 32 0 to 5V Digital 22 Sw Thermistor A3 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 Digital B3 LogiStat Temp Thermistor A1 or A2 45 to 100 F 7 22 to 37 8 C 0 00 0 00 15 88 15 69 LogiStat Thermistor 33 17 to 213 F 27 to 100 6 C 0 00 0 00 15 88 15 69 IN 3 or UDF 2 Volts 33 0 to 5V Digital 23 UDF 2 Flow CFM Flow inpu...

Отзывы: