6. Disconnect the LogiStat Adaptor cable 

from the LogiStat’s LogiPort when 
finished to allow the U253 to read inputs 
from the LogiStat.

Input Wiring

The U253 inputs support the types of signals 
listed below. The LogiStat, LogiStat Plus, and 
LogiStat Pro sensors are supported through 
the module’s LogiStat port. Refer to Table 1 
for information about wire length, gauge, and 
shielding. Make sure the U253’s power is off 
before wiring any inputs or outputs.

• Thermistor: Precon type 2 (10kohm at 

77°F). Input voltages should range 
between 0.489V and 3.825V for 
thermistors.

• 0 to 5VDC: When using 0 to 5VDC 

signals, remove the pull up jumpers of 
the U253. The pull up jumpers are 
located behind the input port. You must 
remove the cover to access the pull up 
jumpers. The output impedance of a 0 

to 5VDC source must not exceed 
10kohms. The input impedance of the 
U253 is approximately 1Mohm.

• Dry Contact: A 5VDC wetting voltage is 

used to detect contact position. This 
results in a 0.5mA maximum sense 
current when the contacts are closed.

No pulse accumulation inputs are allowed in 
U253 FBs, except for the override button on 
the LogiStat.

Using the LogiStat

Use Figure 7 and Figure 8 to wire a LogiStat, 
LogiStat Plus, or LogiStat Pro to the U253.

Automated Logic Corporation recommends a 
specific wire to connect the U253 to the 
LogiStat. This 22AWG solid copper wire is 
available from Magnum Cable Corporation, 
product number A3LOGISTAT.   

 Figure 6. Using the LogiPort

Gnd

2 4 Vac

G n d

T e m p

S w

LS 5v

U n e t +

U n e t -

U -c o m

O n

O f f

BACnet

U253

9

Rx

6 1

2- Tx out

3- Rx in

5- Gnd
1,6,8- +10Vor floating

Tx

+5V

A P T

5

Exec. 4relay

Isolate Network

ModeSelect

TTL

485

ACCESS

PORT

LogiS tat

Port

Supplemental

Power

+5V dc

LogiStat Adaptor Cable

LogiStat

Access

Port

Mode Select

Switch

EIA-232

Port

Exec 4 Relay

Switch

Table 1. Input Wiring Restrictions

Input

Maximum 
Length

Minimum 
Gauge

Shielding

Universal

50 feet
15 meters

24AWG

shielded and 
grounded to 
module’s “-” 
or Gnd 
terminal

LogiStat 
Sensors

100 feet
30 meters

22AWG

unshielded

 Figure 7. Connecting the LogiStat to the U253

Strip 1/4 inch off the ends of the wires before 
connecting.

LogiStat

1 2 3 4

4
3
2
1

LogiStat

U module

LS5v

Sw

Temp

Gnd

G

n

d

T

x

R

x

Pw

r

Содержание U253

Страница 1: ...d trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions U253 Using the U253 2 Specifications 2 Job Start Up 3 Job Start Up for WebC...

Страница 2: ...n User s Guide for more information NOTE To operate this module based on a schedule the UNI must be networked with a gateway module U253 modules have been designed to meet low end high volume terminal...

Страница 3: ...NI 16 with the U1M module driver UNI 30 with the U3M module driver UNI 32 with the UNM module driver or UNI 59 with the U5M module driver Eikon 3 0a or later U Line Zone GFBs If you have InterOp Tools...

Страница 4: ...bCTRL or on the UNI Status page in SuperVision Power Wiring The Unet follows the same specifications as a legacy CMnet Refer to the Technical Handbook for details on legacy CMnets Also refer to the Te...

Страница 5: ...s you should have a PROT485 within 250 feet of any U line module on the Unet for surge protection However depending on the frequency of electrical surges in your area the 250 foot recommendation may v...

Страница 6: ...PT using the Supplemental Power 5V dc connection see Figure 6 on page 7 and the special power cable to a laptop keyboard jack or an external supply such as a 5V dc transformer 3 Define the connection...

Страница 7: ...0 5mA maximum sense current when the contacts are closed No pulse accumulation inputs are allowed in U253 FBs except for the override button on the LogiStat Using the LogiStat Use Figure 7 and Figure...

Страница 8: ...utput s operation lock the output to a known condition on the Function Block s Properties page in WebCTRL or the Parameter page in SuperVision then make sure the equipment operates as specified Using...

Страница 9: ...he DRV_UNI16 or DRV_UNI32 module driver For SuperVision systems the U1M U3M UNM or U5M module driver When using a LogiStat sensor with the U253 include a LogiStat microblock and a Zone Control microbl...

Страница 10: ...e in SuperVision LEDs The U253 modules have diagnostic LEDs to assist troubleshooting Table 2 Digital Outputs I O Type Signal Type Channel Number DO 1 Digital 11 DO 2 Digital 12 Table 3 Inputs I O Typ...

Страница 11: ...report for the module in WebCTRL or SuperVision Refer to the appropriate user s guide for more information about the module status report A sticker on the back of the module also shows the date the mo...

Отзывы: