Using the U253

The U253 is part of a family of control 
modules designed specifically for heat pump 
and fan coil applications. The U253 has:

• two digital outputs

• two LogiStat inputs

• three general purpose inputs

• three analog outputs

The U253 communicates with other U-Line 
modules on the Unet using BACnet MS/TP 
protocol over EIA-485 twisted pair wire. The 
U253 module communicates with the CMnet 
through Unet Interface modules (UNIs). The 
UNI must use one of the following module 
drivers to communicate with the U253:

• For WebCTRL systems, the DRV_UNI16 

or DRV_UNI32 module driver

• For SuperVision systems, the U1M, 

U3M, U5M, or UNM module driver

If communication with the UNI is lost, the 
U253 can be programmed with a backup 
default algorithm to maintain space 
temperature. Refer to the appropriate UNI 
module driver technical instruction for 
instructions on setting up this default 
algorithm.

The U253 module is programmed with a 
Graphic Function Block (GFB), which is 
transferred into the UNI. Depending on the 
software you are using, GFBs written for U-
Line modules must be created in Eikon for 
WebCTRL or Eikon using the Zone GFB 
option; refer to the 

Eikon for WebCTRL User’s 

Guide

 or the 

Eikon User’s Guide 

for more 

information. 

NOTE

To operate this module based on a 

schedule, the UNI must be networked with a 
gateway module.

U253 modules have been designed to meet 
low-end, high-volume terminal control 
applications. As a result, time-critical 
applications (such as short time delays and 
trend intervals of less than one minute) 
should not be used with these modules. ALC 
recommends that all time delay functions and 
trend intervals in U253 FBs be set to at least 
one minute.

CAUTION

If the equipment is used in a 

manner not specified by the manufacturer, 
the protection provided by the equipment 
may be impaired.

Specifications

Power

24VAC 

±

10%, 10VA, 50-60Hz.

Inputs

three inputs configurable for 

thermistor, 0 to 5VDC, or dry contact; two 
LogiStat inputs. 

Input Resolution

10 bit.

Digital Outputs

two relay outputs, rated 

at 1A. 

Analog Outputs

three analog outputs, 0-

10VDC, 5mA maximum drive capability.

Output Resolution

8 bit.

Communication

9600 bps or 38.4 kbps, 

automatically detected (determined by 
UNI module).

Environmental Operating Range

0 to 

130 °F (-17.8 to 54.4 °C); 5 to 95% relative 
humidity, non-condensing.

Status Indication

Visual (LED) indicators.

Memory

60KB Flash EPROM and 2KB of 

RAM, 8KB non-volatile storage for 
default algorithm and configuration data.

Protection

Metal oxide Varistor (power, 

analog inputs, and output relay). 
Transient voltage suppressor (analog 
output). Zener and opto isolation 
protection (communications).

Listed by

PAZX (UL 916).

Содержание U253

Страница 1: ...d trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions U253 Using the U253 2 Specifications 2 Job Start Up 3 Job Start Up for WebC...

Страница 2: ...n User s Guide for more information NOTE To operate this module based on a schedule the UNI must be networked with a gateway module U253 modules have been designed to meet low end high volume terminal...

Страница 3: ...NI 16 with the U1M module driver UNI 30 with the U3M module driver UNI 32 with the UNM module driver or UNI 59 with the U5M module driver Eikon 3 0a or later U Line Zone GFBs If you have InterOp Tools...

Страница 4: ...bCTRL or on the UNI Status page in SuperVision Power Wiring The Unet follows the same specifications as a legacy CMnet Refer to the Technical Handbook for details on legacy CMnets Also refer to the Te...

Страница 5: ...s you should have a PROT485 within 250 feet of any U line module on the Unet for surge protection However depending on the frequency of electrical surges in your area the 250 foot recommendation may v...

Страница 6: ...PT using the Supplemental Power 5V dc connection see Figure 6 on page 7 and the special power cable to a laptop keyboard jack or an external supply such as a 5V dc transformer 3 Define the connection...

Страница 7: ...0 5mA maximum sense current when the contacts are closed No pulse accumulation inputs are allowed in U253 FBs except for the override button on the LogiStat Using the LogiStat Use Figure 7 and Figure...

Страница 8: ...utput s operation lock the output to a known condition on the Function Block s Properties page in WebCTRL or the Parameter page in SuperVision then make sure the equipment operates as specified Using...

Страница 9: ...he DRV_UNI16 or DRV_UNI32 module driver For SuperVision systems the U1M U3M UNM or U5M module driver When using a LogiStat sensor with the U253 include a LogiStat microblock and a Zone Control microbl...

Страница 10: ...e in SuperVision LEDs The U253 modules have diagnostic LEDs to assist troubleshooting Table 2 Digital Outputs I O Type Signal Type Channel Number DO 1 Digital 11 DO 2 Digital 12 Table 3 Inputs I O Typ...

Страница 11: ...report for the module in WebCTRL or SuperVision Refer to the appropriate user s guide for more information about the module status report A sticker on the back of the module also shows the date the mo...

Отзывы: