UNI. You must then use BACnet point 
microblocks to access U253 points through 
the keypad. 

Point Identifiers

A point can be identified in WebCTRL by its 
point number and point type; in SuperVision, 
a point is identified by its channel number. On 
both systems, expander number zero 
represents I/O points on the U253.

Point Identifiers in WebCTRL

Enter the point identifiers in Eikon for 
WebCTRL before the FB is made or on the FB’s 
Properties page in WebCTRL. Set the type, 
number, and minimum and maximum 
present values for each point on the U253. 
Select a physical point type from the 

Point 

Type

 field and enter the number of the input 

or output. If needed, enter an expander 
number. To scale a linear signal type, enter 
the appropriate minimum and maximum 
present values on the microblock’s dialog 
box.

If you are not using a LogiStat in a WebCTRL 
system but would like to use the two inputs 
that are available on the LogiStat port, assign 
an address of 16 for the temperature input 
and 17 for the setpoint input. 

Channel Numbers in SuperVision

Refer to Table 2 and Table 3 for channel 
numbers for each physical point on the U253. 
The channel number, offset, and gain for each 
point can be entered in Eikon before the 
Function Block is made, or on the FB’s 
Parameter page in SuperVision.

LEDs

The U253 modules have diagnostic LEDs to 
assist troubleshooting.  

Table 2. Digital Outputs

I/O Type

Signal Type

Channel Number

DO 1

Digital

11

DO 2

Digital

12

Table 3. Inputs

I/O Type

Signal Type

Channel 
Number

Range

Offset

Gain

IN-1

Thermistor

31

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

Volts

31

0 to 5V

Digital

21

IN-2

Thermistor

32

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

Volts

32

0 to 5V

Digital

22

Sw

Thermistor

A3

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

Digital

B3

LogiStat

Temp

Thermistor

A1 or
A2‡‡

45° to 100° F
7.22° to 37.8° C

0.00
0.00

15.88
15.69

LogiStat

Thermistor

33

-17° to 213° F
-27° to 100.6° C

0.00
0.00

15.88
15.69

IN-3

Volts

33

0 to 5V

Digital

23

Flow 
input

Flow (sensor 
units)

‡‡‡

† Use the Point Help feature of SuperVision for Windows v2.0 or later to 
determine offset and gain for these types of inputs.
‡ Channel numbers for these inputs are set by the LogiStat microblock and do 
not need to be manually entered in SuperVision or Eikon.
‡‡ A1 is 10-second averaged. A2 is not averaged.
‡‡‡ Channel numbers for these inputs are set by the Airflow Control 
microblock and do not need to be manually entered in SuperVision or Eikon.

Table 4. Analog Outputs

Point

Signal Type

Channel 
Number

Range

Offset

Gain

AO 1

Analog

41

0 to 10VDC

0.00

0.0625

AO 2

Analog

42

0 to 10VDC

0.00

0.0625

AO 3

Analog

43

0 to 10VDC

0.00

0.0625

Table 5. Run LED

Status

Meaning

2 times per second

Normal operation.

5 times per second

Transferring firmware.

Once every 2 seconds

Auto-detecting baud rate.

Содержание U253

Страница 1: ...d trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions U253 Using the U253 2 Specifications 2 Job Start Up 3 Job Start Up for WebC...

Страница 2: ...n User s Guide for more information NOTE To operate this module based on a schedule the UNI must be networked with a gateway module U253 modules have been designed to meet low end high volume terminal...

Страница 3: ...NI 16 with the U1M module driver UNI 30 with the U3M module driver UNI 32 with the UNM module driver or UNI 59 with the U5M module driver Eikon 3 0a or later U Line Zone GFBs If you have InterOp Tools...

Страница 4: ...bCTRL or on the UNI Status page in SuperVision Power Wiring The Unet follows the same specifications as a legacy CMnet Refer to the Technical Handbook for details on legacy CMnets Also refer to the Te...

Страница 5: ...s you should have a PROT485 within 250 feet of any U line module on the Unet for surge protection However depending on the frequency of electrical surges in your area the 250 foot recommendation may v...

Страница 6: ...PT using the Supplemental Power 5V dc connection see Figure 6 on page 7 and the special power cable to a laptop keyboard jack or an external supply such as a 5V dc transformer 3 Define the connection...

Страница 7: ...0 5mA maximum sense current when the contacts are closed No pulse accumulation inputs are allowed in U253 FBs except for the override button on the LogiStat Using the LogiStat Use Figure 7 and Figure...

Страница 8: ...utput s operation lock the output to a known condition on the Function Block s Properties page in WebCTRL or the Parameter page in SuperVision then make sure the equipment operates as specified Using...

Страница 9: ...he DRV_UNI16 or DRV_UNI32 module driver For SuperVision systems the U1M U3M UNM or U5M module driver When using a LogiStat sensor with the U253 include a LogiStat microblock and a Zone Control microbl...

Страница 10: ...e in SuperVision LEDs The U253 modules have diagnostic LEDs to assist troubleshooting Table 2 Digital Outputs I O Type Signal Type Channel Number DO 1 Digital 11 DO 2 Digital 12 Table 3 Inputs I O Typ...

Страница 11: ...report for the module in WebCTRL or SuperVision Refer to the appropriate user s guide for more information about the module status report A sticker on the back of the module also shows the date the mo...

Отзывы: