3. Connect the Unet communication wires to 

the Unet Port (see Figure 1 on page 3). 

Replace the module's power jumper. You 
must transfer memory to the UNI before the 
U253 is recognized.

Communicating Through the 

LogiStat Port

You can connect your workstation to the Unet 
and the ARC156 or Legacy CMnet network 
segment using a LogiStat sensor. While 
connected, the UNI does not allow a restart 
(zap), a memory transfer, or any other action 
that would break the passthrough 
connection.

The LogiStat Port connection does not apply 
in WebCTRL.

To communicate through the LogiStat port, 
the U253 must:

• be connected to a UNI on an ARC156 

network segment

• use the appropriate module driver

For SuperVision systems, use a version 
6.01d or later of the U1M, U3M, U5M, or 
UNM module driver

Communication speed is fixed at 1200 baud.

1. Connect the computer’s serial port to the 

EIA-232 port of the APT using a standard 
straight-through cable.

2. Set the APT’s Mode Select switch to TTL 

(see Figure 6 on page 7).

If you are using a LogiStat Plus without 
supplemental power to the APT, make 
sure the LED on the Logistat Plus is on 
indicating that it can provide power to the 
APT. If the LED is not on, you can provide 
power to the APT using the Supplemental 
Power +5V dc connection (see Figure 6 on 
page 7
) and the special power cable to a 
laptop keyboard jack, or an external 
supply, such as a 5V dc transformer.

3. Define the connection type.

In SuperVision v3.0, define the connection 
as Access Port.

In SuperVision v2.6, define the connection 
as Direct Connect.

4. Set the baud rate at 1200 bps.

5. Attach the LogiStat Adaptor cable (ALC 

part number 235022) to the APT cable. 
Use this assembly to connect the APT’s 
Access Port to the LogiStat’s LogiPort.

While connected, the LogiStat Pro 
displays “LP” indicating that the LogiStat 
Pro will not respond to input from the 
keypad.

NOTE

When the LogiStat Adaptor cable 

is inserted into the LogiPort, the U253 can 
no longer read the LogiStat inputs. The 
U253 continues to use the last valid 
temperature and setpoint adjust readings 
obtained before the cable was inserted 
into the LogiPort. If the occupancy 
override timer was active when the 
connection was made, it continues to 
count down, but no new values can be 
obtained for these inputs until the 
LogiStat Adaptor cable is removed. See 
the 

Eikon for WebCTRL Microblock 

Reference Guide

 or the 

Eikon Microblock 

Reference Guide

 for more information 

about the LogiStat microblock.

 Figure 5. Using the PROT485 on the Unet

U n f u s e d :

U s e f o r in s id e

w i r i n g

E A R T H G R O U N D

PROT485

E ART H GRO U ND

RE V 0

Au tomated Logic, C orp

S h a r e d c o n n e c t i o n :
F u s e d o r u n f u s e d

-

+

+

-

To UNI

To U modules

Содержание U253

Страница 1: ...d trademark of ASHRAE All other brand and product names are trademarked by their respective companies Technical Instructions U253 Using the U253 2 Specifications 2 Job Start Up 3 Job Start Up for WebC...

Страница 2: ...n User s Guide for more information NOTE To operate this module based on a schedule the UNI must be networked with a gateway module U253 modules have been designed to meet low end high volume terminal...

Страница 3: ...NI 16 with the U1M module driver UNI 30 with the U3M module driver UNI 32 with the UNM module driver or UNI 59 with the U5M module driver Eikon 3 0a or later U Line Zone GFBs If you have InterOp Tools...

Страница 4: ...bCTRL or on the UNI Status page in SuperVision Power Wiring The Unet follows the same specifications as a legacy CMnet Refer to the Technical Handbook for details on legacy CMnets Also refer to the Te...

Страница 5: ...s you should have a PROT485 within 250 feet of any U line module on the Unet for surge protection However depending on the frequency of electrical surges in your area the 250 foot recommendation may v...

Страница 6: ...PT using the Supplemental Power 5V dc connection see Figure 6 on page 7 and the special power cable to a laptop keyboard jack or an external supply such as a 5V dc transformer 3 Define the connection...

Страница 7: ...0 5mA maximum sense current when the contacts are closed No pulse accumulation inputs are allowed in U253 FBs except for the override button on the LogiStat Using the LogiStat Use Figure 7 and Figure...

Страница 8: ...utput s operation lock the output to a known condition on the Function Block s Properties page in WebCTRL or the Parameter page in SuperVision then make sure the equipment operates as specified Using...

Страница 9: ...he DRV_UNI16 or DRV_UNI32 module driver For SuperVision systems the U1M U3M UNM or U5M module driver When using a LogiStat sensor with the U253 include a LogiStat microblock and a Zone Control microbl...

Страница 10: ...e in SuperVision LEDs The U253 modules have diagnostic LEDs to assist troubleshooting Table 2 Digital Outputs I O Type Signal Type Channel Number DO 1 Digital 11 DO 2 Digital 12 Table 3 Inputs I O Typ...

Страница 11: ...report for the module in WebCTRL or SuperVision Refer to the appropriate user s guide for more information about the module status report A sticker on the back of the module also shows the date the mo...

Отзывы: